30309534
Issue 1.04
panel or the addressable zone monitor unit from GST, if a 4.7K
Ω
terminal resistor is connected to the end of output loop, then DB-01 base
is used. The system connection is shown in Fig. 6.
Fig. 6
When a remote indicator connects with a few of detectors, a diode
1N5819 needs connecting with Terminal 4 of the orientation base in
series and with anode of the remote indicator. The system connection is
shown in Fig. 7.
Fig. 7
Output loop of the addressable zone monitor unit can be connected with
up to 15 conventional field devices. The addressable zone monitor unit
features loop checking. When the loop is broken, the addressable zone
monitor unit will send fault signal to fire alarm control panel. When any
field device in the output loop is removed, the addressable zone monitor
unit reports fault. If a DP-9907 Active End of Line Unit is connected, it will
not affect the normal operation of other field devices.
Testing
Before testing, please ensure that the detector has been installed
correctly and powered up. After 10 seconds, testing begins.
1.
The detector must be tested after installation and periodical
maintenance.
2.
Testing method
1)
Magnetic test
Test zone is shown in Fig. 8. Put the magnet of commission tool close to
that of the detector and hold on for a few seconds until the detector
generates alarm.
Test Zone
Fig.8 Fig.9
2)
Smoke test
Taking a cotton rope burning without flame close to the detector, blow the
smoke into the detector until the detector generates alarm.
3)
Temperature test
Approach a heater (such as a hair drier) to the thermistor of the detector
until it alarms.
3.
After testing, cut power for 10 seconds at least and reset the detector.
Notify the proper authorities that the system returns to normal state.
Clean the failure detector in the test according to
Maintenance
, and test it
again. If it is still fail to pass, please return it to repair.
Maintenance
1. The detector should be installed just before commission and kept well
before installation, taken corresponding measures for dust-proof,
damp-proof and corrosion-proof.
2. The dust cover cannot be removed until the project has been plunged
into usage. Otherwise it can’t alarm normally.
3. Clean the detector at least once a year to ensure normal operation of
the system.
4. If nuisance alarms are often found of the detector on site, the sensing
chamber should be cleaned and replaced when necessary.
a)
Open the top cover of detector, and draw out the sensing
chamber by slightly lifting its two sides using a straight
screwdriver, as shown in Fig. 9.
b)
Clean the sensing chamber by alcohol cotton swab clipped by
tweezers, and also by clear water and brush. Please note not
to leave any cotton in the chamber.
c)
Install the sensing chamber and top cover back.
5. Before cleaning, notify the proper authorities that the system is
undergoing maintenance and will temporarily be out of service. Disable
the zone or system undergoing maintenance to avoid unwanted alarms.
6. The detector should be tested again after cleaning and re-installing.
7. Fire simulation test should be made to the detector at least once half a
year
.
Specification
Operating Voltage
24VDC(16VDC
~
28VDC)
Standby Current
≤
6
0μA
Alarm Current
≤
55mA
Fire LED
Red, flash in polling and illuminate in
alarming.
Remote
indication
output
Polarized output.
Directly connect to
remote indicator (built in 10k
resistor in series, output current is
2mA); Flash in alarming and do not
illuminate in normal.
Max. ripple voltage
2V(peak to peak value)
Alarm reset
Instant power down (2s Min, 1.0VDC Max)
Wiring
Two-wire, polarity sensitive. When the
polarity is reversed, the detector can give
alarm but the remote indicator doesn
’
t
work normally.
Setting of sensitivity
and range
The sensitivity can be set by programmer
with two levels: Level 1(default), level 2.
Detector Class
A2R
Action Temperature
62
℃
Environment
Temperature
-10
℃~
+50
℃
Relative Humidity
≤
95%, non condensing
Material of Enclosure
ABS
Ingress
Protection
Rating
IP2X
Dimension
Diameter:100mm Height: 54.5mm (with
base)
Mounting
Hole
Spacing
45mm
~
75mm
Weight
About 110g
Accessories and Tools
Model
Name
Remark
P-9910B
Hand held programmer
Supplied separately
DB-01
Base
Supplied separately
DB-01D
Base
Supplied separately
T-MT
Commission tool
Supplied separately
WEEE Information
2012/19/EU (WEEE directive): Products marked with this
symbol cannot be disposed of as unsorted municipal waste in
the European Union. For proper recycling, return this product
to your local supplier upon the purchase of equivalent new
equipment, or dispose of it at designated collection points.
Limited Warranty
GST
warrants that the product will be free from defects in design,
materials and workmanship during the warranty period. This warranty
shall not apply to any product that is found to have been improperly
installed or used in any way not in accordance with the instructions
supplied with the product. Anybody, including the agents, distributors or
employees, is not in the position to amend the contents of this warranty.
Please contact your local distributor for products not covered by this
warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.