panel  or  the  addressable  zone  monitor  unit  from  GST,  if  a  4.7K

Ω  

terminal resistor is connected to the end of output loop, then DB-01 base 
is used. The system connection is shown in Fig. 6.

 

 

Fig. 6 

 

When a remote indicator connects with a few of detectors, a diode 

1N5819  needs  connecting  with  Terminal  4  of  the  orientation  base  in 
series  and with anode  of the remote indicator.  The system connection is 
shown in Fig. 7.

 

 

Fig. 7 

Output loop  of the  addressable zone monitor unit can be connected with 
up  to  15  conventional  field  devices.  The  addressable  zone  monitor  unit 
features  loop  checking. When  the  loop  is  broken,  the  addressable  zone 
monitor  unit  will  send  fault  signal  to  fire  alarm  control  panel.  When  any 
field device in the  output loop is removed, the  addressable zone monitor 
unit reports fault. If a DP-9907 Active End of Line Unit is connected, it will 
not affect the normal operation of other field devices.

 

Testing 

Before  testing,  please  ensure  that  the  detector  has  been  installed 
correctly and powered up. After 10 seconds, testing begins.   

1. 

The  detector  must  be  tested  after  installation  and  periodical 

maintenance.   
2. 

Testing method 

1) 

Magnetic test 

Test zone is shown in Fig. 8. Put the magnet of commission tool close to 
that  of  the  detector  and  hold  on  for  a  few  seconds  until  the  detector 
generates alarm.   

Test Zone

                   

 

Fig.8                                                    Fig.9 

2) 

Smoke test 

Taking a cotton rope burning without flame close to the detector, blow the 
smoke into the detector until the detector generates alarm.   
3) 

Temperature test 

Approach a heater (such as a hair drier) to the thermistor of the detector 
until it alarms. 
3. 

After testing, cut power for 10 seconds at least and reset the detector. 

Notify the proper authorities that the system returns to normal state.  

Clean the failure detector in the test according to 

Maintenance

, and test it 

again. If it is still fail to pass, please return it to repair.

 

Maintenance

 

1. The detector should be installed just before commission and kept well 
before  installation,  taken  corresponding  measures  for  dust-proof, 
damp-proof and corrosion-proof. 
2. The dust cover cannot be removed until the project has been plunged 
into usage. Otherwise it can’t alarm normally. 
3. Clean the detector  at least  once  a year to  ensure normal  operation  of 
the system. 
4. If nuisance alarms are often found of the detector on site, the sensing 
chamber should be cleaned and replaced when necessary.

 

 
 
 
 

a) 

Open  the  top  cover  of  detector,  and  draw  out  the  sensing 
chamber  by  slightly  lifting  its  two  sides  using  a  straight 
screwdriver, as shown in Fig. 9. 

b) 

Clean the sensing chamber by alcohol cotton swab clipped by 
tweezers, and also by clear water and brush. Please note not 
to leave any cotton in the chamber. 

c) 

Install the sensing chamber and top cover back. 

5.  Before  cleaning,  notify  the  proper  authorities  that  the  system  is 
undergoing  maintenance  and  will  temporarily  be  out  of  service.  Disable 
the zone or system undergoing maintenance to avoid unwanted alarms. 
6. The detector should be tested again after cleaning and re-installing. 
7. Fire simulation test should be made to the detector at least once half a 
year

.

 

Specification

 

Operating Voltage 

24VDC(16VDC

28VDC)     

Standby Current 

6

0μA 

Alarm Current 

55mA 

Fire LED 

Red,  flash  in  polling  and  illuminate  in 
alarming.   

Remote 

indication 

output 

Polarized  output. 

Directly  connect  to 

remote  indicator  (built  in  10k 
resistor  in  series,  output  current  is 
2mA); Flash in alarming and do not 
illuminate in normal.

 

Max. ripple voltage 

2V(peak to peak value) 

Alarm reset 

Instant power down (2s Min, 1.0VDC Max) 

Wiring 

Two-wire,  polarity  sensitive.  When  the 
polarity  is  reversed,  the  detector  can  give 
alarm  but  the  remote  indicator  doesn

work normally.   

Setting  of  sensitivity 
and range 

The  sensitivity  can  be  set  by  programmer 
with two levels: Level 1(default), level 2. 

Detector Class 

A2R 

Action Temperature 

 

62

 

Environment 
Temperature 

 
-10

℃~

+50

 

Relative Humidity 

95%, non condensing 

Material of Enclosure 

ABS   

Ingress 

Protection 

Rating 

IP2X 

Dimension 

Diameter:100mm  Height:  54.5mm  (with 
base) 

Mounting 

Hole 

Spacing 

45mm

75mm 

Weight 

About 110g 

Accessories and Tools

 

Model 

Name 

Remark 

P-9910B 

Hand held programmer 

Supplied separately 

DB-01 

Base   

Supplied separately 

DB-01D 

Base   

Supplied separately 

T-MT 

Commission tool 

Supplied separately 

WEEE Information 

2012/19/EU  (WEEE  directive):  Products  marked  with  this 
symbol cannot be disposed of as unsorted municipal waste in 
the European Union. For proper recycling, return this product 
to  your  local  supplier  upon  the  purchase  of  equivalent  new 
equipment, or dispose of it at designated collection points.  

Limited Warranty

 

GST

  warrants  that  the  product  will  be  free  from  defects  in  design, 

materials  and  workmanship  during  the  warranty  period.  This  warranty 
shall  not  apply  to  any  product  that  is  found  to  have  been  improperly 
installed  or  used  in  any  way  not  in  accordance  with  the  instructions 
supplied  with  the  product.  Anybody,  including  the  agents,  distributors  or 
employees, is not in the position to  amend the contents  of this warranty. 
Please  contact  your  local  distributor  for  products  not  covered  by  this 
warranty. 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions.  