Features

 

 

Strong environmental adaptability due to drift compensation. . 

 

Reed switch testing.   

 

Removable 

innovative 

sensing 

chamber, 

easy 

for                   

maintenance. 

 

Fire LED allows 360

°

viewing. 

    Remote indicator output available.   

 

2 levels sensitivities  programmable; fix temperature  or rate  of rise 
programmable.

 

 

2  levels  smoke  sensitivities  programmable,  level  1  complies  with 
EN 54-7. Heat part complies with EN 54-5. 

Description

 

DC-9101E  Conventional  Combination    Heat

 

Photoelectric

 

Smoke

 

Detector, non-addressable, is a kind of combination detector consisting of 

smoke  sensing  parts  and  semi-conductor  heat  sensing  parts  in 

technological structure and circuit structure. 

Together with DP-9907, it can connect to conventional  fire  alarm control 
panel  or  connect  with  intelligent  fire  alarm  control  panel  through  I-9319 
Addressable  Zone  Monitor  Unit  conduct  the  processing  of  detector 
signals.  The  detector  has  the  advantages  of  both  conventional 
photoelectric detector and rate of rise and fixed temperature heat detector. 
Just because  of the combination  of smoke detector  and heat  detector, it 
overcomes  the  non-sensitivity  to  dark  smoke  particles  of  ordinary 
scattering photoelectric detectors. It can also pick up fire with obvious rise 
of  temperature  such  as  alcohol  flame,  thus  extending  the  application 
range. 

Connection and cabling

 

The base is shown in Fig. 2.

 

C

B

A

 

Fig. 1                                Fig. 2

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 

2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator 

Recommended Wiring 

1.0mm

or  above  fire  cable  for  all  terminals  laid  through  metal  conduit  or 

flame proof conduit, subject to local codes. 

Note: Different color cables are used to avoid wiring mistake. 

Installation

 

Fix the flame retardant base with two taping screws. Then align A on the 
bottom of the detector to B of the base, and rotate the detector clockwise 
to mark C (Refer to Fig.1 and Fig. 2 for mark A, B, C).

 

Mounting of the detector is shown in Fig.3.

 

Electrical Box

Conduit

Detector

51.5mm

Orientation Base

 

Fig. 3 

 

 

Application

 

Warning:  The  alarm  current  depends  on  the  current  limit  of  the 
control panel. 24VDC cannot power the detector directly.  Otherwise 
the detector will be blown up for lack of current limit resistor.

 

The  sensitivity  level  1  is  defaulted,  which  can  be  modified  by  P-9910B 
programmer.  Refer  to  P-9910B  Hand  Held  Programmer  Installation  and 
Operation Manual for details.   
In  power-on  state,  input  unlocking  password  and  press 

Clear

  to  unlock. 

Press 

Function

, then number 

“3”, the screen shows “-” at the last digit.   

Input  corresponding  sensitivity  or  parameter  and  press 

Program

,  the 

screen  will 

show  a  “P”,  the  corresponding  sensitivity  or  parameter  is 

programmed.  Press 

Clear

  to  clear  the  "P".  Input  locking  password  and 

press 

Clear

 to return. 

Rate of rise and level 1 is defaulted.   

Parameters set using programmer 

Input Number    Smoke Sensitivity 

Heat Sensitive   

Level 1 

Rate of rise 

Level 2 

Rate of rise 

Read  Sensitivity  Level:  in  power-on  state,  pressing 

Test

the  screen 

displays  address  of  the  detector.  Pressing 

Up”,

  display  sensitivity  level, 

device type and initial sensitivity in turns.

 

 

When  the  detector  connects  with  conventional  fire  alarm  control 

panel or addressable zone monitor unit from GST, and if DP-9907 Active 
End  of  Line  Unit  is  connected  to  the  end  of  output  loop,  DB-01D  base 
should be used.

 

 

Used  as  the  detector  base,  DP-9907  Active  End  of  Line  is 

used  to  be  installed  a  conventional  detector  on  it.  The  system 
connection is shown in Fig. 4.

 

Fig. 4 

 

When  DP-9907  Active  End  of  Line  Unit  is  not  used  as  the 

detector  base,  a  cover  should  be  added  to  it.  The  system 
connection is shown in Fig.5. 

Fig. 5 

 

When the detector is connected with conventional fire alarm control 

DC-9101E Conventional Combination 

  Heat

 

Photoelectric

 

Smoke

 

Detector

 

0832-CPR-F0338 

GST-0507-01 

              14 

             

           

   

 