background image

 

30309828 

                             

 

 

                                                                                                Issue 1.02

 

 

Isolator application in Class A is shown in Fig.4. 

 

 

 

 

 

 

 

 

 

Fig. 4 

Isolator application in Class B is shown in Fig.5. 

+

-

 

 

Fig. 5 

WEEE Information 

2012/19/EU (WEEE  directive):  Products 
marked  with  this  symbol  cannot  be 
disposed of as unsorted municipal waste 
in  the  European  Union.  For  proper 
recycling,  return  this  product  to  your 

local  supplier  upon  the  purchase  of  equivalent  new 
equipment,  or  dispose  of  it  at  designated  collection 
points. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Specification 

Nominal Line Voltage ( V

NOM

24V 

Standby Current   

100μA 

Capacity 

70 devices 

Indicator 

Yellow.  It  flashes  in 
normal 

standby 

state, 

constantly  illuminates  in 
action. 

Wiring 

two-wire 

Maximum Line Voltage    ( V

MAX

28V 

Minimum Line Voltage ( V

MIN

16V 

Maximum  voltage  at  which  the 
device isolates ( V

SO MAX

11V 

Minimum  voltage  at  which  the 
device isolates ( V

SO MIN

8V 

Maximum  voltage  at  which  the 
device reconnects ( V

SC MAX

4V 

Minimum  voltage  at  which  the 
device reconnects ( V

SC MIN

1.4V 

Maximum  rated  continuous  current 
with the switch closed ( I

C MAX

1A 

Maximum  rated  switching  current 
( I

S MAX

5A 

Maximum  leakage  current  with  the 
switch open ( I

L MAX

)   

7.5mA 

Maximum  series  impedance  with 
the switch closed ( Z

C MAX

0.15Ω 

Environmental Temperature 

-10

℃~

+40

 

Relative Humidity 

95%, non condensing 

Ingress Protection Rating 

IP33 with cover 
IP22 without cover 

Material and Color of Enclosure 

ABS, white (RAL 9016) 

Dimension 

ф103mm×20mm 

Mounting Hole Distance 

45mm

75mm 

Weight 

About 85g 

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  of  charge 

for  repairing  or  replacing  from  defects  in  design, 
materials and workmanship during the warranty period. 
This  warranty  shall  not  apply  to  any  product  that  is 
found to have been improperly installed or used in any 
way  not  in  accordance  with  the  instructions  supplied 
with  the  product.  Anybody,  including  the  agents, 
distributors  or  employees,  is  not  in  the  position  to 
amend  the  contents  of  this  warranty.  Please  contact 
your  local  distributor for  products not  covered  by this 
warranty. 

 

 

 

 
 

This part is removed from the loop

 

Loop out    Loop in 

Short Circuit 

+

-

+

-

Detector Isolator 

Loop 

Short Circuit 

This part is removed from the loop 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 