background image

 

30302556                                                                                                                                                                    Issue 2.04

 

 

If  the  sounder/sounder  strobe  is  required 

anti-removal, knock down the arch knock-off hole as 
shown  in  Fig.  1  and  fix  it  with  ST2.9

×

6.5  tapping 

screws (in this case, it must be removed by a special 
tool). 

Application 

the  sounder/sounder  strobe  can  match  I-9333 
Interface  to  form  an  intrinsically  safe  system.  The 
system wiring is shown in Fig. 5.

 

Non-intrinsincally Safe Loop 

Intrinsincally Safe Loop

 D1   D2     Z1  Z2

24VDC

Fire Alarm Control Panel

L-

L+

2(-)

1(+)

N

F928 Zener 

Safety Barrier

Safety Area

4(-)

3(+)

Hazardous Area

1

Z

2

Z

K

2

S

D

2

G

1

K

D

1

I-9333 Interface

I-9333 Circuit 
Board

  Fig. 5 

Cautions 

1

  I-9333  Interface  should  be  installed  in  safety 

area,  the  wires  of  "Safety  Area"  should  be 
separated from those of "Hazardous Area", and 
be kept a certain distance (at least 50mm). 

2

  The  safety  barrier  should  be  well  grounded. 

The  screws  should  not  be  loose.  Ground 
resistance  should  not  be  over  1

Ω.  The 

parameters  assigned  in  the  intrinsically  safe 
loop should not be over the specified value, that 
is, the capacity assigned among cables should 
not  be  over  0.02μF,  the  inductance  assigned 
not over 2mH. 

3

  During  maintenance,  products  passing  the 

explosion-proof test should not be replaced and 
parts  and  structure  affecting  explosion-proof 
functions should not be modified.   

Sound Level Data (

Complies to EN54-3

Fixed tone, Maximum Volume 

Angle 

Horizontal 

Vertical 

 

 

18V 

28V 

18V 

28V 

15° 

74.47 

78.16 

71.95 

75.55 

45° 

81.85 

86.44 

82.03 

85.36 

75° 

88.06 

92.47 

87.88 

91.66 

105° 

88.15 

91.93 

89.14 

92.92 

135° 

80.50 

85.54 

82.48 

87.07 

165° 

62.32 

66.37 

73.93 

78.07 

 

 

 

 

 

Specification 

Power 

Loop 

voltage 

when 

activating 

24VDC

16VDC

28VDC

 

Power 

Loop 

voltage  in  standby 
state 

7VDC

5VDC

8VDC

 

standby current 

≤5mA 

active 

current 

≤50mA 

Wiring 

Polarized  two-wire  with  I-9333 
Interface 

Sound Level 

See  the  above  sound  level  data 
table

   

Flashing 
Frequency 

1.4×(1±20

)Hz

C-9403(Ex)

 

Tone  Modification 
Period 

0.7s±20

 

Explosion-proof 
marking 

Exib

CT6 

Security 

Barrier 

Parameters

NF928

 

U

0

28V

I

0

93mA 

Ingress  Protection 
Rating 

IP33 

Operating 
Temperature 

-10

℃~

+50

 

Relative Humidity 

≤95%, non condensing 

Material and Color 
of Enclosure 

ABS

red

PANTONE 1795C

 

Dimension 
(L×W×H) 

ф110mm×97.5mm (deep base) 

ф110mm×83mm(shallow base) 

Mounting 

Hole 

Spacing 

55mm

80mm 

Weight 

C-9404(Ex)

 

About  340g(deep  base)About 
312.2g(shallow base) 
C-9403(Ex)

 

About  350g(deep  base)About 
322.2g(shallow base) 

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  from 

defects in design, materials and workmanship during 
the warranty period. This warranty shall not apply to 
any  product  that  is  found  to  have  been  improperly 
installed or used in any way not in accordance with 
the instructions supplied with the product. Anybody, 
including  the  agents,  distributors  or  employees,  is 
not  in  the  position  to  amend  the  contents  of  this 
warranty.  Please  contact  your  local  distributor  for 
products not covered by this warranty. 

 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 