background image

C-9102 (UL)

 

Conventional Photoelectric Smoke Detector

 

              

                             

 

                

Installation and Operation Manual

 

  

                                                  

      

    

 

 

Page 1  

General 

C-9102  (UL)  Conventional  Photoelectric  Smoke  Detector  (hereinafter  called  the 

detector)  is  a  non-addressable  detector,  applicable  to  hotels,  restaurants,  office 

buildings, teaching buildings, banks, warehouses, libraries, computer rooms and switch 

rooms, etc. It can be connected with compatible fire alarm control panel (FACP) through 

a 4.7k

Ω  terminal resistor to detect fire. 

II  Features

 

The  detector  adopts  the  latest  scattering  technology  and  excellent  photoelectric 

components,  improving  the  reliability,  stability  and  conformity  of  the  sensor.    With 

special  optical  sensing  chamber,  it  has  high  ability  of  insect-proof,  dust-proof,  and 

interference-proof of external rays. With novel structure and attractive appearance, the 

detector has stable and reliable performance and high damp-proof ability.  

III  Technical Specifications 

1. 

Operating Voltage: 12VDC

28VDC 

2. 

Operating Current: 

Standby Current:

6

0μA  

Alarm Current: 10mA

I

30mA  

(Note: The alarm current depends on the current limit of the FACP. It’s not 
allowed to power the detector directly by 24VDC.  Otherwise the detector will 

be blown as a result of without current limiting resistor.) 

3. 

Alarm Reset: Instantaneous Cut-out (5s MAX, 2.5VDC MAX) 

4. 

Initiating Time:

10s  

5. 

Sensitivity:1.23%/ft

2.02%/ft 

6. 

Maximum Ripple Voltage: 4V(peak-to-peak value) 

7. 

Alarm Confirming LED: Red, not lit when in normal operation, constantly lit when 

alarming. 

8. 

Monitoring Area: When space height is 6m

12m, the monitoring area of a detector 

is 80m

2

 for normal protection area; When space height is less than 6m, it is 60 m

2

9. 

Wiring: Connecting with the power cable by polarized two-wire. 

10.  Operating Environment:      

Temperature:  

0

℃~

37.8

 (UL268) 

Relative Humidity:

95%, non-condensing 

11.  Dimension: Diameter: 100mm   Height: 42mm (without base) 

    Diameter: 105mm   Height: 56mm (with base) 

12.  Ingress Protection: IP22 

13.  Material and Color of Enclosure: ABS, ivory white  

14.  Weight: About 120g 

15.  Matching Parts: DZ-03 Base 

16.  Standard Applied: UL268 

Summary of Contents for C-9102

Page 1: ...C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual Issue 1 04 July 2012...

Page 2: ...Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Testing 4 VII Troubleshooting 5 VI...

Page 3: ...ons 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current 60 A Alarm Current 10mA I 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the det...

Page 4: ...rticles In smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output a...

Page 5: ...There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3...

Page 6: ...this function only when necessary to avoid trouble in maintenance and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m...

Page 7: ...s sensitivity Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 If a detector fails in testing clean it as described...

Page 8: ...totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove the dust on the sensing chamber by vacuum pump or cleaner and...

Page 9: ...ions and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty This detector is approved by UL as a recognized component It s strongly recommended th...