GST8903 
Intelligent Graphic Repeater Panel

  

                                            

 

                

Installation and Operation Manual

 

  

                                                  

      

 

 

The Intelligent Solution

 

 

 

Page 7 

VII Troubleshooting 

Common problems and solutions are shown in the table. 

 

No.      

Fault indication

 

             

Possible Cause

 

                

Solution 

 

No indication  
on the panel or 
incorrect indication

 

after power-up. 

a. Power supply is in bad 

condition.   

b. Loose connection with the 

display board. 

c.  LED is in bad condition 
d.  The main CPU is damaged 

a.  Check the 24V power 

supply 

b.  Check the cable 
c.  Replace the LED 
d.  Replace the main CPU

   2  The  machine  can’t 

start up.  
 

a.  No 5V 

a.  Check the 3M03 and 

its peripheral circuit.  

   3  Report memory fault 

after power-up 

a. Some 24LC04B data are

wrong. 

b. 24LC04B 

is 

damaged. 

c.  No jumper inserted into X1 

a. Write the 24LC04B 

again. 

b. Replace the 24LC04B.
c. Insert the jumper. 

   4  The 

fire 

alarm 

control panel can’t 
register 

a.   A, B communication cable is 

not well connected 

b.  The power supply is not well 

connected. 

c. The transformer secondary

coil is not well soldered. 

d.  75176, optocoupler and other 

nearby components are 
damaged. 

a.  Connect it in a right 

way. 

b.  Connect it in a right 

way. 

c. Solder 

again. 

d.  Replace the damaged 

parts. 

   5  No sound 

a.  Triode VT2 and its peripheral 
components are damaged. 
b.  Buzzer is damaged. 

a. Replace 

the 

damaged

components. 

b.  Replace the buzzer. 
 

6  Can’t register all 

mainboards (with 
multi-mainboards) 

a.  Ribbon cable between Pin 1 of 

mainboards haven’t been cut

b.  Consult No.4 item 

a. Cut the Ribbon cables 
between Pin 1 of 
mainboards 

VIII Cautions 

1.  Before powering up, check all cable problems, such as short circuit, open circuit 
and wrong connections etc. 
2.  This panel is precise electronic product and must be maintained by specific 
personnel. 
3.  Make record on duty. 
4.   We take the responsibility of repairing the repeater. Any problem occurs, please      
contact us in time. The users will be responsible for any result they made by repairing 
themselves. 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Summary of Contents for 8903

Page 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 2: ...eration 4 VII Troubleshooting 7 VIII Cautions 7 Appendix 1 Installation of the Mainboard 8 Appendix 2 Installation of the LED Board 9 Appendix 3 Installation of the Membrane 10 Appendix 4 Installation of the Buzzer 11 Appendix 5 Installation of the LED 12 Appendix 6 Configuration of the Whole 13 Appendix 7 Connection of Repeater Panel 14 Appendix 8 Membrane of Repeater Panel and Corresponding LED ...

Page 3: ... information can be displayed by each mainboard 3 Wiring Connected with fire alarm control panel with two polarized wires connected with power supply with two 24VDC power lines non polarized 4 Operating Current Monitoring Current 25mA Alarming Current 100mA 5 Operating Environment Environment Temperature 0 40 Relative Humidity 95 non condensing 6 Power Centralized power supply by 18VDC 28VDC quies...

Page 4: ...LED Board Installation method is shown in Fig 2 See Appendix 2 and 6 for more information 115 0 2 40 0 2 255 0 2 5 5 265 LED Board Fig 2 LED board 3 Mounting of the Membrane Installation method is shown in Fig 3 See Appendix 3 and 6 for more information 4 R2 0 7 0 2 7 2 0 0 15 Fig 3 Membrane Door 114 15 7 5 Through hole Membrane pasted with in the frame Through hole HTTP GSTRU RU E MAIL hombi homb...

Page 5: ...alarm sound Press this key again or fire alarm recurs the repeater panel will sound again Fig 4 4 Mounting of the Buzzer Installation method is shown in Fig 5 See Appendix 4 and 6 for more information Fig 5 Buzzer 5 Mounting of the LED Installation method is shown in Fig 6 See Appendix 5 and 6 for more information Fig 6 the LED 6 Mounting of the Repeater Panel The repeater panel is wall mounted Dr...

Page 6: ...uld be shielded 1 0mm2 cable and the shield cover should be connected with GNDG on the main board 24VDC power cable should be 4 0mm2 cable 8 Wiring Connection of boards is shown in Fig 7 9 Commission Program the device number and user code before power up The repeater panel should work normally VI Operation Set up the system according to the project requirement 1 The repeater panel is defaulted as...

Page 7: ...speaker will give a trouble sound at the same time You need to reprogram the EEROM write in the indicator number and code again 5 Programming 5 1 Programming is done by P 9910B Hand Held Programmer 5 2 Method for entering and exiting programming to the repeater panel Connect the programmer with the repeater panel then input 2 5 8 and press the Function key to start programming to the repeater pane...

Page 8: ...in the new LED number and user code so that this operation can be used to modify an incorrect LED number and user code At most 100 LED numbers can be written in the screen will show PPPP when all numbers have been finished 2 Every fire alarm signal can only light one LED of GST8903 even if all LED are defined the same It cannot be defined to display by device and by zone at the same time 5 4 4 Aft...

Page 9: ...tion cable is not well connected b The power supply is not well connected c The transformer secondary coil is not well soldered d 75176 optocoupler and other nearby components are damaged a Connect it in a right way b Connect it in a right way c Solder again d Replace the damaged parts 5 No sound a Triode VT2 and its peripheral components are damaged b Buzzer is damaged a Replace the damaged compo...

Page 10: ...ent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 8 Appendix 1 Installation of the Mainboard 97 0 2 106 0 2 214 0 2 116 5 5 Mainboard Box body Weld Nut 6 M3 8 HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 11: ...nt Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 9 Appendix 2 Installation of the LED Board 115 0 2 40 0 2 255 0 2 LED Board Box Body 6 M3 40 5 5 265 Ⅰ Weld nut HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 12: ...d Operation Manual The Intelligent Solution Page 10 Appendix 3 Installation of the Membrane 114 Through hole 4 R2 15 0 7 0 2 0 7 0 2 15 7 5 106 0 2 10 20 136 15 18 18 32 18 3 2 M3 9 5 0 0 1 2 1 Ⅰ M 6 1 Weld nut Ⅰ Remove keyboard Switch Panel HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 13: ...igent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 11 Appendix 4 Installation of the Buzzer 45 0 2 Through hole 2 M3 2 6 14 Ⅰ Ⅰ 2 1 buzzer Box Body Weld nut HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 14: ... RU GST8903 Intelligent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 12 Appendix 5 Installation of the LED 1 2 3 4 A B 6 5 Through hole B HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 15: ...he Whole 上 上 下 下 雨棚 下 A A A A A A Second Floor 室 UP Repeater Panel 1 2 3 4 5 6 5 5 7 8 5 9 10 11 I I remove box body 12 Notes Make memebrane according to plan of the floor Make enclosure according to membrane and fix light emitting diode at corresponding positions with plastic sleeve and nylon sleeve Enlarge A Direction A HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 16: ...0 HL31HL32 HL93HL94 HL95 HL96 HL64 HL61HL62 HL63 HL99HL100 HL32 XS2 Buzzer Buzzer XS1 HL2 HL56 HL55 HL34 HL33 HL97 HL2 HL3 HL4 Mould Zone Discharge Zone A V6 TCC Process Zone F CPerformance Test and Packing Zone die casting zone A HL1 HL5 HL1 N Scaleboard N Mainboard1 LED Board1 HL98 Strategic Area Switchboard Name Cable No Model and Size Length Remarks Buzzer Cable X01 After Mainboard soldered Ri...

Page 17: ...d Operation Manual The Intelligent Solution Page 15 Appendix 8 Membrane of Repeater Panel and Corresponding LED Number Membrane of Repeater Panel and The Corresponding LED Number Stick the relevant drawing according to the project requirement HTTP GSTRU RU E MAIL hombi hombi ru ...

Page 18: ...T UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email info gst uk com www gst uk com HTTP GSTRU RU E MAIL ho...

Reviews: