384V500AH
4
Battery modules must be placed in the specified order.
Battery module is heavy, in order to reduce the risk of injury, please do a good
job of protective measures.
After the battery module is arranged as required, connect each battery module according
to the battery line connection diagram.
If the battery module is placed for too long time, check the appearance of each battery
module for damage and deformation before wiring for safe operation and compliance.
Without the above situation, the voltage value of each battery module is measured by
multimeter in turn. When the maximum and minimum voltage difference of the battery
module exceeds 0.5 V, it can not be connected directly. The battery module needs to charge
and discharge separately so that the voltage difference is within 0.5 V.
When the battery module is connected in series, use the battery connection we provide
to ensure that the terminal positive (+) on the adjacent battery module is connected to the
negative (-), negative (-) to the positive (+) and tighten the bolt.
All wiring must be done by professionals.
1. Please follow the following steps to implement batteryconnection
:
After it is stuck on the connector base,
tighten the bolts with an M 6 hex wrench.
Use a multimeter to measure the B+ and
B- of each battery module and the B+
and B- of the high-voltage package to
see if the voltage of each module is
basically the same. Is the pressure
normal
Remove orange and
black connectors from
battery module
Connect the signal
lines and power
lines of each cluster
of battery modules
according to the
CAD drawings
Insert the connector