Ensure that all materials meet the requirements of the system maximum voltage, current,
moisture, and temperature when they expose to sunlight.
Under normal conditions, a photovoltaic module is likely to produce more current and/or
voltage than that reported under standard test conditions.
Accordingly, the values of Isc and Voc marked on this module should be
multiplied by a factor of 1.25 when selecting electricity components voltage ratings,
conductor capacities, fuse type, and type of control components connected to the PV
output.
The maximum series Fuse rating is 20A. And the maximum reverse current is known as
series Fuse rating multiplied by a factor of 1.35.
·
Bypass Diodes
When modules in series are shaded partially, it may cause reverse voltage across cells
or modules, this may cause undesirable heating to occur. The use of a diode to bypass
the shaded area can minimize both heating and array current reduction.
All
“
GSE
”
modules are equipped with factory installed bypass diodes. The factory
installed diodes provide proper circuit protection for the system. Rating of bypass diodes:
Current 10A; Voltage 50V
·
Others
During installation, be sure to tie the cable from the junction box to the mounting
substructure with nylon line, etc. to avoid direct contact of the cable with the back surface
of the module.
Module mounting
GSE’
s Limited Warranty for modules is based upon modules being mounted in
accordance with following conditions
.
1) Operating conditions
Install
GSE
Solar Crystalline series modules in the following conditions:
.Operating temperature:
-40
℃
to +85
℃
. Storage temperature:
-20
℃
to +50
℃
. Humidity:
below 85RH%
. Altitude:
≤
2000m
. Mechanical Load Pressure:
2400Pa (245 Kg/m2)
*Mechanical load bearing specifications of the module is based on
GSE
Solar mounting
methods. A professional system installer must be responsible for the mechanical load
calculations based on the specific system design.
*The modules have been evaluated by TUV according to IEC61215 for a maximum positive
design loading of below 2400Pa, and negative design loading 1600Pa,with 1.5 times safety
factor.
2)
Limited conditions
Installation environment with following conditions should be avoided.
·
The installation area with extreme sand and dust damage.