Vacuum chlorine gas dosing system up to 20 kg/h, with drums
14
12
7
11
3
4
1a 2
5
1
6
13
15
9
8
10
16
TM080280
Pos.
Component
1
VGS-147 vacuum regulator with heated liquid trap (pressure inlet right)
1a
VGS-147 vacuum regulator with heated liquid trap (pressure inlet left)
2
Chlorine drum lifting device
3
Header line for chlorine drums
4
LiquFilt 524 heated liquid chlorine trap with filter
5
186 change-over device
6
Shut-off valve
7
VGA-117 dosing regulator up to 20 kg/h
8
VGB injector
9
Injection unit
10
CR booster pump
11
Nitrogen rinsing device
12
Conex DIA-G gas warning system
13
Gas sensor
14
Horn and flashlight
15
Vent to a Grundfos chlorine gas neutralisation system
16
Ventilation of the building
2.4 Operating principle of a VGA-117 dosing regulator
The chlorine gas volume flow is adjusted by the dosing regulator.
This can be done manually or automatically with a servomotor.
VGA-117 dosing regulators can have a differential-pressure
regulator that reduces and regulates the injector vacuum to a
constant level to secure a constant and linear gas flow.
VGA-117-110 and VGA-117-190 dosing regulators operate without
a differential-pressure regulator. They achieve a constant and linear
chlorine gas flow under sonic flow conditions.
Dosing regulators without a differential-pressure regulator operate
with VGB injectors. VGB injectors have a higher performance but
require larger motive water flow and higher motive water
pressure. Dosing regulators without a differential-pressure regulator
do not comply with DIN 19606.