Grundfos UPZC-1 Installation And Operating Instructions Manual Download Page 3

Model

Part 

Number

Maximum 

Number of 

Zones

Input 

Power

60 HZ

Relay 

Type

Current 

Output to 

Thermostat

Transformer 

Voltage

Single phase 

Motor Rating Per 

Zone @ 120VAC

Maximum 
Combined 

Load 

Min/Max 

Ambient 

Temperature

UPZC-3

96741788

3

120 VAC

+/- 10%

DPDT

0.13A

120V AC, 

24V, 25VA 

1/3 HP, 10 A GP

30A

32°F (0°C)

104°F (40°C)

UPZC-4/6

96741789

4 to 6

Description:

 

The Grundfos Zone Control family are non-networked devices intended to be used for  

 

 

circulator and boiler control in hydronic heating systems. 

 

Warning:  

Electrical shock and potential circuit damage.  Disconnect power supply before beginning  

 

 

installation.  All wiring must comply with national and local electrical codes, ordinances and regulations.  

 

Failure to follow electrical codes could result in serious personal injury, death, and property damages.

 

 

 

 

 

 

 

Cold Start Boiler Installation:

>

  Do not remove factory installed jumper between ZCCP & L1  

>

  Attach low voltage thermostat leads to respective thermostat  

  terminals T1R1 & T1W1, if thermostat requires voltage use 24AC  
  C terminal 

 

 

 

>

  Attach circulator leads to respective terminals (LC1 & NC1) 

>

  Connect isolation end switch (terminals X1 & ZRX2) to TT    

  terminals on boiler aquastat 

>

  Select priority switch setting  

 

>

  Connect supply voltage to terminals (N & L1) 

 

 

 

Tankless Coil Boiler Installation:

>

 

Move factory installed jumper

 to terminals L1 & X1 

 

>

  Attach low voltage thermostat leads to respective thermostat  

  terminals T1 R1 & T1 W1, if thermostat requires voltage use 24AC  
  C terminal 

 

 

>

  Attach circulator leads to respective terminals (LC1 & NC1)   

>

  Connect terminals ZCCP & ZRX2 to boiler aquastat ZR & ZC  

>

  Select priority switch setting 

>

  Connect supply voltage to terminals (N & L1) 

 

 

   
 

External Diagnostics:

 

>

  

Green

 LED indicates presence of 24VAC at secondary side of transformer. 

 

 

 

   

 

>

  

Yellow

 LED indicates a thermostat(s) call for heat

   

 

>

  

Red

 LED indicates Zone 1 priority is active

Agency Listings:

 

 

USL    UL 873 Temperature Indicating and Regulating Equipment

   

 

CNL    CAN/CSA C22.2 No. 24.

Warranty:

 

 

3 years

Priority Switch Settings:

 

OFF

 Position: 

No set priority, all zones operate independently 

 

 

 

ON

 Position: 

Zone 1 has priority until the demand is satisfied 

 

 

 

TMR

 Position: 

Zone 1 has priority for 1-Hour.   The remaining zones will stop operation  

 

 

 

until Zone 1 is satisfied or until the 1-Hour priority has expired.

120 VAC

Power

Optional 3-wire

Thermostat

Factory 

Installed

Jumper

Class 2

wiring

Class 1

wiring

Boiler

UPZC-3

Expandable

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

“TT”

Connections

PRIORITY

O
N

O

F
F

T

M

R

T6

W6

T6

R6

T5

W5

T5

R5

T4

W4

T4

R4

T3

W3

T3

R3

T2

W2

T2

R2

T1

W1

T1

R1

C

R

N

C6

L

C6

N

C5

L

C5

N

C4

L

C4

N

C3

L

C3

N

C2

L

C2

N

N

C1

L

L

C1

P2

P1

ZR

X2

X1

L1

ZC

CP

120

VAC

120

VAC

N

UPZC-4/6

Optional 3-wire

Thermostat

Factory

Jumper must

be moved to
this position

Class 2

wiring

Class 1

wiring

Boiler

“ZR & ZC”

PRIORITY

Connections

T6

W6

T6

R6

T5

W5

T5

R5

T4

W4

T4

R4

T3

W3

T3

R3

T2

W2

T2

R2

T1

W1

T1

R1

C

R

N

C6

L

C6

N

C5

L

C5

N

C4

L

C4

N

C3

L

C3

N

C2

L

C2

120 VAC

Power

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

O
N

O

F
F

T

M

R

N

C1

L

N

L

C1

P2

P1

ZR

X2

X1

L1

ZC

CP

120

VAC

120

VAC

N

UPZC-3

Expandable

UPZC-4/6

120 VAC

Power

Optional 3-wire

Thermostat

Factory 

Installed

Jumper

Class 2

wiring

Class 1

wiring

Boiler

UPZC-3

Expandable

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

Th

er

mo

sta

t

“TT”

Connections

PRIORITY

O
N

O

F
F

T

M

R

T6

W6

T6

R6

T5

W5

T5

R5

T4

W4

T4

R4

T3

W3

T3

R3

T2

W2

T2

R2

T1

W1

T1

R1

C

R

N

C6

L

C6

N

C5

L

C5

N

C4

L

C4

N

C3

L

C3

N

C2

L

C2

N

N

C1

L

L

C1

P2

P1

ZR

X2

X1

L1

ZC

CP

120

VAC

120

VAC

N

UPZC-4/6

Additional wiring schematics,  specs, and trouble shooting help can be found on our WEB link: www.grundfos.us/controls

Wiring Connections:

 

 

>

  All electrical connections must be made using copper wire only

 

>

   12-16 AWG wire is recommended for 120VAC connections

 

>

  12-22 AWG wire for thermostat connections   

>

  12-22 AWG wire for 24VAC connections 

 

>

  Use approved UL conduit fittings

     

 

Caution:

 

Wire all circuits as Class 1, Electric Light or Power Circuits.

Summary of Contents for UPZC-1

Page 1: ...FOS ZONE CONTROL INSTRUCTIONS US Installation and operating instructions Zone Controls Models UPZC 1 UPZC 3 UPZC 4 6 FR Notice d installation et d entretien SP Instrucciones de instalaci n y funcionam...

Page 2: ...ars R T W T 24 AC COM COM 5 NO 6 NC 6 Neutral L2 Line L1 COM 3 NO 4 NC 4 120 VAC Power Circulator Optional 3 wire Thermostat Boiler TT Connections Dry Contacts Factory Installed Jumper Class 2 wiring...

Page 3: ...nt CNL CAN CSA C22 2 No 24 Warranty 3 years Priority Switch Settings OFF Position No set priority all zones operate independently ON Position Zone 1 has priority until the demand is satisfied TMR Posi...

Page 4: ...4 NC 4 120 VAC Power Circulator Optional 3 wire Thermostat Boiler TT Connections Dry Contacts Factory Installed Jumper Class 2 wiring Class 1 wiring Therm ostat R T W T 24 AC COM COM 5 NO 6 NC 6 Neut...

Page 5: ...rioridad hasta que se satisfaga la demanda Posici n TMR Zona 1 tiene prioridad durante 1 hora Las zonas restantes dejar n de operar hasta que la Zona 1 sea satisfecha o hasta que la prioridad de 1 hor...

Page 6: ...COM 5 NO 6 NC 6 Neutral L2 Line L1 COM 3 NO 4 NC 4 120 VAC Power Circulator Optional 3 wire Thermostat Boiler Dry Contacts ZR ZC Factory Installed Jumper Class 2 wiring Class 1 wiring Therm ostat Mise...

Page 7: ...t Therm ostat Therm ostat Therm ostat Therm ostat Therm ostat TT Connections PRIORITY O N O F F T M R T6 W6 T6 R6 T5 W5 T5 R5 T4 W4 T4 R4 T3 W3 T3 R3 T2 W2 T2 R2 T1 W1 T1 R1 C R N C6 L C6 N C5 L C5 N...

Page 8: ...truc tions To obtain service under this warranty the defective product must be re turned to the distributor or dealer of GRUNDFOS products from which it was pur chased together with proof of purchase...

Reviews: