Flow estimation (option)

The PWM feedback signal can be used to measure the flow of the 
pump.

Fig. 13

PWM feedback signal

6.2.2 0-10 VDC

GRUNDFOS UPML and UPMXL circulators are externally speed-
controlled by a analogue 0-10 V DC signal. The pump requires a 
0-10 V signal on the signal port to control the speed of the pump. 
The pump will run at its minimum speed, if the signal fails (cable 
break).

Profile R

Fig. 14

Profile R

TM

07

 05

96

 05

18

Pos.

Description

1

UPML saturation point, 140 W

2

UPMXL saturation point, 210 W

PWM output 

signal [%]

Indicates

Pump operation

95

Standby

Stop

90

Rotor blocked

Stop

85

Undervoltage stop

Stop

75

Undervoltage warning 
at Un -15 %

Pump performance is 
reduced from Un -10 %.

0-70

Power [W]

Pump is running 
according to setpoint.

Rating

Value

Rated input voltage - high level

U

IH

4-24 V

Rated input voltage - low level

U

IL

< 1 V

High-level input current

I

IH

< 10 mA

Input duty cycle

PWM

0-100 %

PWM frequency output, open collector

f

75 Hz ± 5 %

Accuracy of output signal regarding 
power consumption

-

± 2 % of PWM 

signal

Output duty cycle

PWM

0-100 %

Collector-emitter breakdown voltage 
on output transistor

U

C

< 70 V

Collector current on output transistor

I

C

< 50 mA

Max. power dissipation on output 
resistor

P

R

125 mW

Zener diode working voltage

U

Z

36 V

Max. power dissipation in Zener diode

P

Z

300 mW

25

50

100

150

200

250

10

20

30

40

50

60

70

80

90

100

1

2

Standby (stop)

Alarm stop: Fault, blocked pump

Alarm stop: Electrical fault

Warning

P

W

M

 out

put 

[%]

 

Outp

ut f

reque

ncy:

 75 

Hz 

± 5 

%

Power [W]

Sl

op

e: 

3 W

/%

Sl

op

e:

 2

 W

/%

T

M

07

 0

4

39

 50

17

TM

07 07

84 051

8

U [V]

Pump status

 U <= 0.5

MAX speed

0.5 < U <= 1

Standby (STOP)

1 < U <= 2

Hysteresis

2 < U <= 3

MIN speed

3 < U <= 10

Speed between MIN and MAX

470 R

36 V

0-10 V

PWM

Signal input

Signal output

Signal ref

0.5

4

5

U[V]

1

2

3

9

6

7

8

10

Max.

Min.

Stop

UPMM_UPML_UPMXL_US.book  Page 12  Tuesday, February 26, 2019  10:18 PM

Summary of Contents for UPML

Page 1: ...GRUNDFOS INSTRUCTIONS UPML UPMXL Installation and operating instructions UPMM_UPML_UPMXL_US book Page 1 Tuesday February 26 2019 10 18 PM...

Page 2: ...2 UPMM_UPML_UPMXL_US book Page 2 Tuesday February 26 2019 10 18 PM...

Page 3: ...nt for more than thirty 30 days and canceling any balance still owing on the equipment or c in the case of service at the seller s option redoing the service or refunding the purchase order amount of...

Page 4: ...or circulating liquids in heating and air conditioning systems They are suitable for cold water applications and can be integrated in geothermal heating pumps DANGER Indicates a hazardous situation wh...

Page 5: ...zard Death or serious personal injury In domestic hot water systems the temperature of the pumped liquid must always be above 122 F 50 C due to the risk of legionella WARNING Biological hazard Death o...

Page 6: ...MXL Nominal diameter DN of inlet and outlet ports mm Maximum head dm _ N F Cast iron pump housing Stainless steel pump housing 2 bolt flanges Port to port length mm AUTO PWM VDC Internally controlled...

Page 7: ...th or serious personal injury Before dismantling the pump drain the system or close the isolating valve on either side of the pump before the screws are removed The pumped liquid may be scalding hot a...

Page 8: ...iquid may be scalding hot and under high pressure CAUTION Hot surface Minor or moderate personal injury Position the pump so that persons cannot accidentally come into contact with hot surfaces Do not...

Page 9: ...of filter damage Ground fault circuit interrupter GFCI If the pump is connected to an electrical installation where a ground fault circuit interrupter GFCI is used for additional protection this Groun...

Page 10: ...e has two or three leads The signal cable must be connected to the control box by a dubox housing with an FCI terminal block and terminals Fig 10 VDC signal cable connection The ground symbol identifi...

Page 11: ...s feedback signal The PWM frequency of the feedback signal is fixed at 75 Hz in the pump Duty cycle d 100 x t T Fig 11 PWM signal Fig 12 PWM input profile A heating PWM feedback signal Power consumpti...

Page 12: ...ted input voltage low level UIL 1 V High level input current IIH 10 mA Input duty cycle PWM 0 100 PWM frequency output open collector f 75 Hz 5 Accuracy of output signal regarding power consumption 2...

Page 13: ...mA Input duty cycle PWM 0 100 PWM frequency output open collector f 75 Hz 5 Accuracy of output signal regarding power consumption 2 of PWM signal Output duty cycle PWM 0 100 Collector emitter breakdo...

Page 14: ...rial curve setting For first start up Start at factory pre setting If a setting has already been selected Start at the actual setting Press the button for two seconds The pump enters setting mode and...

Page 15: ...The current operated or voltage operated circuit breaker has tripped Cut in the circuit breaker d Power supply failure Check that the power supply falls within the specified range Normal power supply...

Page 16: ...16 UPMM_UPML_UPMXL_US book Page 16 Tuesday February 26 2019 10 18 PM...

Page 17: ...17 UPMM_UPML_UPMXL_US book Page 17 Tuesday February 26 2019 10 18 PM...

Page 18: ...18 UPMM_UPML_UPMXL_US book Page 18 Tuesday February 26 2019 10 18 PM...

Page 19: ...2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industrial Stiva Aeropuerto C P 66600 Apodaca...

Page 20: ...e Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com UPMM...

Reviews: