English (US)
12
Flow estimation (option)
The PWM feedback signal can be used to measure the flow of the
pump.
Fig. 13
PWM feedback signal
6.2.2 0-10 VDC
GRUNDFOS UPML and UPMXL circulators are externally speed-
controlled by a analogue 0-10 V DC signal. The pump requires a
0-10 V signal on the signal port to control the speed of the pump.
The pump will run at its minimum speed, if the signal fails (cable
break).
Profile R
Fig. 14
Profile R
TM
07
05
96
05
18
Pos.
Description
1
UPML saturation point, 140 W
2
UPMXL saturation point, 210 W
PWM output
signal [%]
Indicates
Pump operation
95
Standby
Stop
90
Rotor blocked
Stop
85
Undervoltage stop
Stop
75
Undervoltage warning
at Un -15 %
Pump performance is
reduced from Un -10 %.
0-70
Power [W]
Pump is running
according to setpoint.
Rating
Value
Rated input voltage - high level
U
IH
4-24 V
Rated input voltage - low level
U
IL
< 1 V
High-level input current
I
IH
< 10 mA
Input duty cycle
PWM
0-100 %
PWM frequency output, open collector
f
75 Hz ± 5 %
Accuracy of output signal regarding
power consumption
-
± 2 % of PWM
signal
Output duty cycle
PWM
0-100 %
Collector-emitter breakdown voltage
on output transistor
U
C
< 70 V
Collector current on output transistor
I
C
< 50 mA
Max. power dissipation on output
resistor
P
R
125 mW
Zener diode working voltage
U
Z
36 V
Max. power dissipation in Zener diode
P
Z
300 mW
25
50
100
150
200
250
10
20
30
40
50
60
70
80
90
100
1
2
Standby (stop)
Alarm stop: Fault, blocked pump
Alarm stop: Electrical fault
Warning
P
W
M
out
put
[%]
Outp
ut f
reque
ncy:
75
Hz
± 5
%
Power [W]
Sl
op
e:
3 W
/%
Sl
op
e:
2
W
/%
T
M
07
0
4
39
50
17
TM
07 07
84 051
8
U [V]
Pump status
U <= 0.5
MAX speed
0.5 < U <= 1
Standby (STOP)
1 < U <= 2
Hysteresis
2 < U <= 3
MIN speed
3 < U <= 10
Speed between MIN and MAX
470 R
36 V
0-10 V
PWM
Signal input
Signal output
Signal ref
0.5
4
5
U[V]
1
2
3
9
6
7
8
10
Max.
Min.
Stop
UPMM_UPML_UPMXL_US.book Page 12 Tuesday, February 26, 2019 10:18 PM
Summary of Contents for UPML
Page 2: ...2 UPMM_UPML_UPMXL_US book Page 2 Tuesday February 26 2019 10 18 PM...
Page 16: ...16 UPMM_UPML_UPMXL_US book Page 16 Tuesday February 26 2019 10 18 PM...
Page 17: ...17 UPMM_UPML_UPMXL_US book Page 17 Tuesday February 26 2019 10 18 PM...
Page 18: ...18 UPMM_UPML_UPMXL_US book Page 18 Tuesday February 26 2019 10 18 PM...