Figure 8a

5. 

For continuous operation, set the manual 

 

switch to the “ON” position. To switch the 

 

circulator off, set the manual switch to the 

 

“OFF” position. The “ON”/”OFF” modes may be 

 

used without affecting the function of either the  

 

programming ring or the timer switch.

6. 

In case of power outage the timer will not keep  

 

time. After power has been restored, the correct  

 

time of day must be reset by rotating the  

 

 

programming ring in the direction of the arrow  

 

until the timing arrow points to the actual time  

 

on the ring.

8. Changing speeds with timer option

• 

Disconnect line cord from  

 

system power. 

• 

Remove (2) timer cover    

 screws. 

• 

Gently rotate speed  

 

 

selection stim to desired   

 speed 

(see Figure 7a). 

• 

Re-install (2) timer cover   

 screws.

 

9. Troubleshooting

When the pump is first started, the shaft may rotate 

slowly until water has fully penetrated the bearings.  
If the pump does not run, the shaft can be rotated 
manually. To accomplish this, switch off the electrical 
supply, and close the isolation valves on each side of 
the pump. Remove the large screw in the middle of the 

nameplate.  Insert a small flat blade screwdriver into the 

end of the shaft, and gently turn until the shaft moves 
freely (see Figure 8a). Replace and tighten the plug.  
Open the isolation valves and wait 2 to 3 minutes for the 
system pressure to equalize before starting the pump.

Figure 7a

Summary of Contents for UP15

Page 1: ...page 2 Pump installation page 3 Electrical page 5 Timer control technical data and application page 5 Timer operation page 6 Failure to operate page 7 Warranty page 8 Maintenance free circulators wit...

Page 2: ...of the solution Check with manufacturer for information regarding suitability of pumping other fluids System applications UP S 15 series pumps with stainless steel or bronze volutes can be used in bo...

Page 3: ...x position needs to be changed it is best to do so before installation However if the pump is already installed ensure that the line cord is unplugged and close the isolation valves before removing th...

Page 4: ...thermal and mechanical stress on the pump Installation requirements 1 Thoroughly clean and flush the system prior to pump installation 2 Do not install the pump at the lowest point of the system wher...

Page 5: ...d Electrical connection Insert the 115V plug on the line cord from the pump into a properly grounded 115V outlet as shown in Figure 4a 5 Timer technical data TIMER CONTROL Supply Voltage 115 120 VAC 6...

Page 6: ...ime on the ring 2 Switch on the power supply to the circulator and set the manual switch to the ON position The circulator will now start 3 Set the required ON OFF times on the programming ring by pus...

Page 7: ...d from system power Remove 2 timer cover screws Gently rotate speed selection stim to desired speed see Figure 7a Re install 2 timer cover screws 9 Troubleshooting When the pump is first started the s...

Page 8: ...thorized alteration or repair or if the product was not installed in accordance with GRUNDFOS printed installation and operation instructions To obtain service under this warranty the defective produc...

Reviews: