TECHNICAL SPECIFICATIONS
1
17
-,#*.#)(
, ì
, î
*x #
,x|{ *| 'x ~
1 X 115V +/- 10% or 1 X 230V +/- 10%
Input Voltage
Single Phase Input
Output Voltage
3 X 220V
3 X 230V
Continuous Output Current (230V input)
6.05A
8.25A
Continuous Output Current (115V input)
6.05A
6.50A
*x ##
{x| x *xx||
Control System
PWM
Output Voltage
Clamp @ 220V
Clamp @ 230V
Carrier Freq.
Selectable: 1-5 KHz
Freq. Resolution
0.1Hz*
Input Freq. Range
48 – 62 Hz
Maximum Output Frequency(230V input)
400 Hz
100 Hz
Maximum Output Frequency(115V input)
400 Hz
80 Hz
Base Frequency
400 Hz
100 Hz
Torque Boost
0 – 15% Nominal Voltage
V/F Pattern
Selectable Linear/Square Law
Accel Time
0.5 – 3600 Seconds
Decel Time
0.5 – 3600 seconds
Accel/Decel Pattern
Linear
*x ###
*|z| z
Ground Fault
Ground Fault detection for Equipment Protection
Overcurrent
Output Short Circuit
Locked Rotor
Over Voltage
400VDC
Under Voltage
200VDC
Motor Overload
I
2
x T Characteristic
Line Start Lock Out
VFD will not start upon input power application
Line Transient Rating
860 VAV, 810J MOV Between any power
input terminal & Ground
360 VAC, 380 J MOV Between any two
power input terminals
*x #0
y| )|x ~ {
Operating Temp.
-10 to 40 degree C
Storage Temp.
-30 to 65 degree C
Vibration
0.5G, Max / 57-150 Hz
Elevation
3300 ft. without derating
Max source fault current
5 Kamps
Enclosure rating
UL Type 4, No Direct Sunlight