2.1 Installing the device
The PHP device must be installed on a horizontal and solid
floor and it must be set up vertically by using the adjustable
stands (1). The four holes on side of the socket can be
used to transport the device (for example by inserting
2 pipes, max. 1”).
The implementation into the system return must be executed
acc. to the hydraulic diagrams in
Chapter 3 “Hydraulic
diagrams”.
PHP series devices can be used in plants with max.
temperature of 70 °C at the connection point. If the max.
temperature at the connection point exceeds 70 °C,
cooling vessels must be installed.
The implementation into the system return must be done
at a position where no external pressure can occur.
External pressures could affect the trouble-free operation
of the pressure maintenance device.
2.2 Degassing module PHP EMAE-1,
makeup module PHP EMCF-1 V
(Model EMCF-1 V included when
break tank fitted).
PHP series devices factory provided are delivered without
degassing module EMAE-1. The mounting of these modules
is done acc. to the assembly instruction which is delivered
with the module.
04
INFORMATION
Dimensioning of the expansion pipe according
to ÖNORM H 5151-1, see appendix A in instruction
manual PHP A-1. With PHP all the piping must be made
on-site according to the appropriate hydraulic diagram
in Chapter 3.
NOTE
For detailed information about hydraulic connection
of PHP expansion vessels see Chapter 8.
Figure 1:
Adjustable stands and transportation example
Figure 2:
Degassing module EMAE-1
connection
point EMCF-1 V
connection
point EMAE
Summary of Contents for PHP A-4
Page 8: ...4 Wiring diagrams PHP A 4 6 8 9 Instruction Manual Wiring diagrams 08 4 1...
Page 9: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 09...
Page 10: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 10...
Page 23: ...PHP A 4 6 8 9 Instruction Manual Appendix 23 Suction pipe overflow pipe...