PHP A-4, 6, 8 & 9 Instruction Manual /
Commissioning PHP A-4, 6, 8 & 9
STEP 8
Configuration of the PHP device
• Press key “F2” (operate) in main display
• Select menu item “code input”
• Enter the code (see instruction manual PHP A-1,
chapter 5.7 “user level 3”)
• User level 3 is unlocked
• Go to menu item “device set-up” in user level 3
(if already done: “settings” “device set-up”)
User level 3
.))) device set-up
/))) vessel code
*.))) acc. to the sticker at the vessel
/))) correction value PL1o
*.))) acc. to the sticker at the upper pressure transmitter
/))) correction value PL1u
*.))) acc. to the sticker at the lower pressure transmitter
/))) makeup EMCF-1 V
*/))) not available (default setting)
*.))) is available
/))) water treatment (only if makeup EMCF-1 V is available)
*/))) not available (default setting)
*/))) softening MWE6 resp. softening MWE12
*.))) desalination MVE2 resp. desalination MVE4
/))) degassing
*/))) not available
1)
*/))) pump degassing
2)
*.))) degassing module
3)
/))) bin. signalling (only if module is installed)
*/))) not available (default setting)
*.))) is available
/))) remote acknowledgement (only if module is installed)
*/))) not available (default setting)
*.))) is available
/))) analog signalling (only if module is installed)
*/))) not available (default setting)
*.))) is available
/))) temperature sensor T2
*/))) not available (default setting)
*.))) is available
/))) level measurement L2
*/))) not available (default setting)
*.))) is available
/))) correction value PL2o
*.))) acc. to the sticker at the upper pressure transmitter
*only displayed if level measurement L2 is available
/))) correction value PL2u
*.))) acc. to the sticker at the lower pressure transmitter
*only displayed if level measurement L2 is available
/))) communication
*/))) not available (default setting)
*/)))
SMS-Module
*/)))
ASCII-Logger
*.)))
Busmodule
.))) enable contact
/))) not available (default setting)
.))) is available
1) default setting at PHP-_4...9
2) default setting at PHP A-1_, not available at PHP 4...9
3) only available at PHP-_4...9
INFORMATION
If device setup was completed successfully (only
mandatory inputs necessary) this menu item is removed
permanently. The device setup always is available in
”user level 3” ”settings”.
NOTE
Take care to select the right operating mode of
the degassing function. If the selection happened
incorrectly degassing can‘t work correctly.
Summary of Contents for PHP A-4
Page 8: ...4 Wiring diagrams PHP A 4 6 8 9 Instruction Manual Wiring diagrams 08 4 1...
Page 9: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 09...
Page 10: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 10...
Page 23: ...PHP A 4 6 8 9 Instruction Manual Appendix 23 Suction pipe overflow pipe...