3.
Operational Limits
Outdoor Sensor 070
Approvals:
CSA, UL
Operating range:
-60 to 140°F (-50 to 60°C)
Sensor:
NTC thermistor, 10 kW
@ 77°F (25°C ± 0.2°C), B=3892
Enclosure:
White U.V. resistant PVC
Universal Sensor 071
Approvals:
CSA, UL
Operating range:
-60 to 255°F (-50 to 125°C)
Sensor:
NTC thermistor, 10 kW
@ 77°F (25°C ± 0.2°C), B=3892
Wire:
6’ 20 AWG XPE Wire
Grundfos MixiMizer pumps with "FC" designation are
designed to pump liquids compatible with their cast
iron pump housing construction. They are recom-
mended for use in closed hydronic systems. Grundfos
MixiMizer pumps with "BUC" and "BF" designations
are designed to pump liquids compatible with their
bronze pump housing construction and can be used in
both open and closed systems. Grundfos MixiMizer
pumps are for Indoor Use Only.
Grundfos MixiMizer Pumps are intended for use with
water, or a 50/50 mixture by weight of propylene
glycol.
Page 4
•
Pump Exercising: After every three days of no
operation, the control will exercise the pump for 10
seconds. The % of Pump Performance LED will be
on during exercising.
•
Post Purge: A 20 second post purge is available
once the heat demand is removed or control
enters WWSD. The purging holds the last speed
used.
•
As variable speed output modulates, the control
flashes the % of Pump Performance LED on for ¼
second and off for ¼ to 2 1/2 seconds.
•
A 2 second delay from demand to actually starting
the pump is used to prevent issues with a noisy
demand relay signal.