Page 12

wiring may be shorted, there may be moisture in the
070 or the 070 may be defective.  To test for a
defective 070 sensor, measure the resistance directly at
the 070 sensor location.

Replace the front cover of the 070 sensor enclosure.

Test the Power Supply or Heat Demand.
Make sure exposed wires and bare terminals are not in
contact with other wires or grounded surfaces.  Turn on
the power or provide a heat demand and measure the
voltage across the leads.  The voltmeter should read
between plus and minus 4 volts of the supplied voltage.

 Temperature  Resistance   Temperature Resistance

o

F

o

C

o

F

o

C

-50

-46

490,813

  90

 32

46,218

-45

-43

405,710

  95

 35

7,334

-40

-40

336,606

100

 38

5,828

-35

-37

280,279

105

 41

5,210

-30

-34

234,196

110

 43

4,665

-25

-32

196,358

115

 46

4,184

-20

-29

165,180

120

 49

3,760

-15

-26

139,402

125

 52

3,383

-10

-23

118,018

130

 54

3,050

-5

-21

100,221

135

 57

2,754

  0

-18

 85,362

140

 60

2,490

  5

-15

 72,918

145

 63

2,255

 10

-12

 62,465

150

 66

2,045

 15

-9

 53,658

155

 68

1,857

 20

-7

 46,218

160

 71

1,689

 25

-4

 39,913

165

 74

1,538

 30

-1

 34,558

170

 77

1,403

 35

 2

 29,996

175

 79

1,281

 40

 4

 26,099

180

 82

1,172

 45

 7

 22,763

185

 85

1,073

 50

 10

 19,900

190

 88

   983

 55

 13

 17,436

195

 91

   903

 60

 16

 15,311

200

 93

   829

 65

 18

 13,474

205

 96

   763

 70

 21

 11,883

210

 99

   703

 75

 24

 10,501

215

102

   648

 80

 27

  9,299

220

104

   598

 85

 29

  8,250

225

107

   553

Temperature/Resistance Chart

Summary of Contents for MixiMizer UP15-42

Page 1: ...t Control 1 Shipment Inspection Page 3 2 General Page 3 3 Operational Limits Page 4 4 Pump Installation Page 6 5 Installation Requirements Page 7 6 Mounting Control System Page 7 7 Rough in Wiring Pag...

Page 2: ...o avoid this unwanted heat transfer standard primary secondary piping tech niques are used This piping arrangement requires that the injection piping be at least one pipe diameter smaller than the pip...

Page 3: ...is connected CAUTION The non metallic enclosure does not provide grounding between conduit connections Use grounding type bushings and jumper wires CAUTION Improper installation and operation of this...

Page 4: ...m and maximum settings are operating not safety limits Necessary auxiliary equipment and safety devices must be added The boiler return minimum temperature is fixed at 135 F This function can be disab...

Page 5: ...patible with their bronze pump housing construction and can be used in both open and closed systems Grundfos MixiMizer pumps are for Indoor Use Only Grundfos MixiMizer Pumps are intended for use with...

Page 6: ...r Pump UP43 64BFC MR 115V 60 Hz MixiMizer Pump Maximum fluid temperature 195 F 90 C Maximum ambient 105 F 40 C with control module vertical Fig 4A 105 F 40 C with control module under pump and horizon...

Page 7: ...lly separate the stator from the pump chamber and rotate it to the correct terminal box orientation Replace the Allen screws and tighten diagonally and evenly 7 ft lb torque Check that the motor shaft...

Page 8: ...o vent the system Never operate the pump dry The bearings require water lubrication and will be damaged otherwise Fill system with water This will result in immedi ate lubrication of the bearings Oper...

Page 9: ...ermistor is built into the PVC plastic enclosure Remove the screw and pull the front cover off the sensor enclosure The 070 can either be mounted directly onto a wall or a 2 x 4 electrical box When th...

Page 10: ...damage or tampering Water Temperature Sensor 071 The Water Temperature 071 Sensor has a zinc sleeve for fast response and a wide operating range Fig 6D Note The 071 sensor is designed to mount on a pi...

Page 11: ...one or power cables If the sensor wires are located in an area with strong sources of electromagnetic interference EMI shielded cable or twisted pair should be used If using shielded cable the shield...

Page 12: ...good quality digital thermometer or if a thermometer is not available a second 070 sensor can be placed alongside the one to be tested and the readings compared Connect the wire to the two terminals...

Page 13: ...re Resistance o F o C o F o C 50 46 490 813 90 32 46 218 45 43 405 710 95 35 7 334 40 40 336 606 100 38 5 828 35 37 280 279 105 41 5 210 30 34 234 196 110 43 4 665 25 32 196 358 115 46 4 184 20 29 165...

Page 14: ...DEM I Fig 7B Outdoor Air Temperature Sensor 070 Connections CAUTION Do not apply power to these terminals at any time as this will damage the control Connect the two wires from the Outdoor Air Temper...

Page 15: ...ture design outdoor temperature Example A system is designed to supply 120 F 49 C water when the outdoor temperature is 10 F 12 C The Occupied temperature is 70 F 21 C Heating Curve 120 70 F 49 21 C 7...

Page 16: ...5 20 10 0 10 20 30 40 50 60 70 80 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 6 3 6 3 0 Heating Curve System Design Tempe rature F...

Page 17: ...Heating Curve Table Warm Weather Shut Down 70 F Page 16...

Page 18: ...grounded 115 V outlet This will apply power to the pump control Performance Indicator LEDs Fig 8c Power ON green indicates power is applied Call For Heat Green indicates demand is applied from perman...

Page 19: ...rature of 30 F Pump Performance Reduced LED is flashing Fig 9B Then the system supply sensor is short or open circuit And the control runs pump at 10 and does boiler protection if enabled Call For Hea...

Page 20: ...VA Max WARNING All field wiring to be low voltage Power for control is provided through the power cord supplying power to the pump Use copper conductors only Disconnect all power sources prior to serv...

Page 21: ...z 240 VA Var Speed 120 V ac 1 8 A 1 12 hp Out V Com Dem I Demand Sup Com Ret ON OFF AB C D Made in Canada 1 Meets Class B Canadian ICES FCC Part 15 106 1 106 0 Demand 20 30 V ac 0 1 VA Class II only U...

Page 22: ...tor or dealer of GRUNDFOS products from which it was purchased together with proof of purchase and installation date failure date and sup porting installation data Unless otherwise provided the distri...

Reviews: