background image

9

7.2 Electrical installation

The following must be observed:

The electrical installation of the booster set must comply with 
enclosure class IP54.

Make sure that the booster set is suitable for the electricity 
supply to which it is connected.

Make sure that the wire cross-section corresponds to the 
specifications in the wiring diagram.

8. Control panel

The Grundfos Hydro Multi-S booster set can be controlled via the 
control panel integrated in the control cabinet. See fig. 4.

Fig. 4

Control panel

9. Start-up

To start up the booster set, proceed as follows:

1. Connect water and power supplies.

2. Close the valve on the discharge side of all the pumps. 

3. Prime all pumps, and make sure that the suction manifold and 

the suction pipe are primed as well.

4. Check that the tank pre-charge pressure is equal to 0.9 x 

cut-in pressure.

5. Switch on the electricity supply.

6. Start the first pump by pressing and holding down the button 

for manual operation.

7. Check the direction of rotation of the pump. 

If the direction of rotation is wrong, interchange two phases of 
the electricity supply.

8. Vent the pump by slowly opening its discharge valve.

9. Repeat the same procedure for the other pumps.

10. Release the booster set for automatic operation by pressing 

the button for automatic operation.

10. Operating modes

The operating mode of each pump can be selected with the 
dedicated buttons for "Automatic operation", "Stop" and "Manual 
operation" as described in section 

8. Control panel

.

10.1 Manual operation

Manual operation is generally used during commissioning, testing 
or for maintenance and service purposes.

To enable manual operation, press and hold down the button for 
manual operation. 

10.2 Automatic operation

When this operating mode is selected, the pumps operate 
automatically according to the system requirements, e.g. the 
pressures set on the pressure switches.

When a tap is opened, water is drawn from the diaphragm tank 
until the tank is empty.

When the pressure drops to the first cut-in pressure, the first 
pump will start.

If the consumption is still increasing, more pumps will be cut in 
until the performance of the pumps in operation corresponds 
to the requirements.

When the water consumption decreases, the discharge 
pressure rises to the first cut-out pressure and the pressure 
switch cuts out and one pump is stopped.

If the consumption is still decreasing, more pumps will be cut 
out until the last pump finally fills the diaphragm tank and 
stops.

10.3 Dry-running protection

The Hydro Multi-S incorporates dry-running protection to protect 
the pumps from running dry. The dry-running protection is 
activated by a pressure switch or a level switch connected on the 
suction side and then connected to the control cabinet.

Warning

The electrical connection must be carried out by 
an authorised person in accordance with local 
regulations and the relevant wiring diagram.

Make sure to disconnect the electricity supply 
using the mains switch and lock it with a padlock 
to ensure that it cannot be accidentally switched 
on.

Note

For the electrical connection, please refer to the 
wiring diagram supplied with the booster set.

T

M

03

 97

20

 43

0

7

Pos.

Description

1

LED indication for dry-running alarm

2

Pump number 

3

LED indication for fault status 
(three-phase pumps only) 

4

LED indication for pump running 

5

Push-buttons for manual operation 

6

Push-buttons for stopping the pumps 

7

Push-buttons for automatic operation 

8

LED indication for power on

1
2
3

8

4

5

6

7

Caution

Do not start the booster set until the pumps and 
the suction pipe have been filled with liquid.

Note

The button for manual operation has no 
permanent position. Therefore, keep the button 
pressed during the test cycle.

Note

Each pressure switch is related to one pump only 
and not necessarily to the same pump when the 
pumps alternate after each cycle.

Summary of Contents for Hydro Multi-S

Page 1: ...Hydro Multi S GRUNDFOS INSTRUCTIONS Installation and operating instructions...

Page 2: ...Hydro Multi S 2006 42 EC EN 809 1998 EN 60204 1 2006 2006 95 EC EN 60439 1 2002 EMC 2004 108 EC EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 Overeenkomstigheidsverklaring Wi...

Page 3: ...ladu s ustanoven mi sm rnice Rady pro sbl en pr vn ch p edpis lensk ch st t Evropsk ho spole enstv v oblastech Sm rnice pro strojn za zen 2006 42 ES Pou it normy EN 809 1998 a EN 60204 1 2006 Sm rnice...

Page 4: ...ulti S 2006 42 EN 809 1998 EN 60204 1 2006 2006 95 EC EN 60439 1 2002 2004 108 EC EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 Bjerringbro 25th January 2010 Jan Strandgaard...

Page 5: ...56 Asennus ja k ytt ohjeet 63 Monterings og driftsinstruktion 70 Instrukcja monta u i eksploatacji 77 85 Szerel si s zemeltet si utas t s 94 Navodila za monta o in obratovanje 102 Monta ne i pogonske...

Page 6: ...o Multi S booster set is designed for pressure boosting of clean water Examples blocks of flats hotels schools Hydro Multi S consists of two or three identical Grundfos CH or CR pumps connected in par...

Page 7: ...Number of mains operated pumps S pumps 8 Motor power in kW 9 Country of origin Type Model Main supply Q Max H Min Weight S pumps Motor size Made in 96763706 1 2 3 4 5 6 7 8 9 Example Hydro Multi S P 2...

Page 8: ...hould always be fitted on the manifolds This is important to prevent the booster set from hanging in the pipework 7 1 3 Foundation The booster set should be positioned on an even and solid surface If...

Page 9: ...g the pressures set on the pressure switches When a tap is opened water is drawn from the diaphragm tank until the tank is empty When the pressure drops to the first cut in pressure the first pump wil...

Page 10: ...Pressure switch 12 1 1 Setting the cut out pressure To set the cut out pressure pcut out proceed as follows 1 Turn the P1 screw clockwise to increase the cut out pressure and counter clockwise to decr...

Page 11: ...nd shaft seals are maintenance free 13 2 Settings To ensure reliable and correct operation the pre charge pressure of the diaphragm tank and the setting of the pressure switches should be checked regu...

Page 12: ...tive Repair or replace the motor j Electronic circuit board failure Replace the fuse if defective Switch to emergency operation and replace the electronic circuit board if defective 2 Pump starts but...

Page 13: ...ashi gotanda Shiagawa ku Tokyo 141 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone...

Page 14: ...d makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark A...

Reviews: