5.10 Frequency converter operation
The Grundfos CRN-H MAGdrive pumps are designed for
operation with variable speed for pump performance control.
If variable-speed operation is desired, we recommend that you
use a Grundfos CUE frequency converter. In addition to variable-
speed control, CUE has special features that can be used to
perform all of the protective tasks required for CRN-H MAGdrive
pumps (see section
). Contact your
local Grundfos company for more information about the use of
CRN-H MAGdrive pumps with CUE frequency converters.
The use of frequency converters may result in increased acoustic
noise from the motor. Furthermore, it may expose the motor to
detrimental voltage peaks. Both these disturbances can be
eliminated by fitting a filter between the frequency converter and
the motor.
The wires in the terminal box must be as short as possible. The
exception is the ground wire which must be so long that it is the
last wire to be disconnected in case the cable is inadvertently
pulled out of the cable entry.
Fig. 8
Wiring diagram, three-phase mains connection
Fig. 9
Wiring diagram, signal terminals
Note:
Terminals 27, 29 and 37 are not used.
TM
0
3
8
799
2
507
Terminal
Function
91
(L1)
Three-phase supply
92
(L2)
93
(L3)
95/99
(PE)
Ground connection
96
(U)
Three-phase motor connection, 0-100
% of mains voltage
97
(V)
98
(W)
T
M
06
99
10
08
1
7
Terminal
Type
Function
12
+24 V out
Supply to sensor
13
+24 V out
Additional supply
18
DI 1
Digital input, start-stop
19
DI 2
Digital input, programmable
20
GND
Ground for digital inputs
32
DI 3
Digital input, programmable
33
DI 4
Digital input, programmable
39
GND
Ground for analog output
42
AO1
Analog output, 0+20 mA
50
+10 V out
Supply to potentiometer
53
AI 1
External setpoint, 0-10 V / 0/4-20
mA
54
AI 2
Sensor input, sensor 1, 0/4-20
mA
55
GND
Ground for analog inputs
61
RS-485 GND Y
GENibus, GND
68
RS-485 A
GENibus, signal A (+)
69
RS+485 B
GENibus, signal B (-)
-
+
+
0/4-20 mA
0/4-20 mA
39 42 50 53 54 55
GND
AO 1
+10V out
Ext. setpoint
Sensor 1
GND
RS-485 GND
Y
RS-485 A
RS-485 B
+24 V out
+24 V out
Start/stop
DI 2
DI 3
DI 4
GND
12 13 18 19 27 29 32 33 20
61
61
68
68
69
69
0-20 mA
55
55
0-10 V
0-10 V
12
12
1 K
Terminals
A53
A54
U I
U I
See section
5.6
54
53
53 and 54: