8.7.55 Log values (4.4.9)
Fig. 106
Log values
Description
Select the values to be logged and the number of samples per
hour. The resulting timespan will be shown. When the timespan
has elapsed, old logged values will be deleted and overwritten by
the new ones.
Log values
• Estimated flow rate
(only if no flowmeter is installed)
• Speed of pumps
• Process value
• Setpoint
• Power consumption
(MPC-E systems)
• Inlet pressure
(if an inlet-pressure sensor is installed).
Setting range
Samples per hour: 1-3600.
Setting via control panel
• Settings > Monitoring functions > Log values.
1. Set: Samples per hour.
2. Select the values to be logged.
8.7.56 Fault, primary sensor (4.4.10)
Fig. 107
Fault, primary sensor
Description
You can set how the system is to react if the primary sensor fails.
Setting range
• Stop (without delay)
• Stop (with delay)
• Min.
• Max.
• User-defined
• Operating mode "Local"
• Emergency run
• Reset: Manual / Auto.
Setting via control panel
• Settings > Monitoring functions > Fault, primary sensor.
1. Select reaction in case of a fault in the primary sensor.
2. Select resetting: Auto / Manual.