English (GB)
49
8.7.43 Reduced operation (4.3.24)
Fig. 93
Reduced operation
Description
This function makes it possible to limit the number of pumps in
operation, or for MPC-E systems, to limit power consumption.
The limit is activated by a digital input.
Setting range
• Setting of digital input (
• Setting of digital output (
8.7.31 Digital outputs (4.3.9)
).
• Maximum number of pumps in operation.
• Maximum power consumption.
Setting via control panel
• Settings > Secondary functions > Stop function > Reduced
operation > Go to setting of digital input.
1. Select digital input.
2. Select: Reduced operation.
3.
x 2.
4. Select: Go to setting of digital output.
5. Select digital output.
6. Select: Reduced operation.
7.
x 2.
8. Set: Number of pumps in operation / Power consumption.
Factory setting
No digital input is selected (disabled).
8.7.44 Monitoring functions (4.4)
Fig. 94
Monitoring functions
Description
The system has a series of functions that constantly monitor the
operation of the system.
The primary purpose of the monitoring functions is to ensure that
faults do not damage pumps or the system.
Setting range
•
Dry-running protection (4.4.1)
•
•
•
•
Limit 1 exceeded (4.4.5 - 4.4.6)
•
Pumps outside duty range (4.4.7)
•
•
•
Fault, primary sensor (4.4.10)
Setting via control panel
• Settings > Monitoring functions.