8.5 Operation (2)
In this menu, you can set the basic parameters, such as setpoint,
operating mode, control mode and individual pump control.
8.5.1 Operation (2)
Fig. 17
Operation
Description
The column shows the setting range. In closed-loop control, it
corresponds to the range of the primary sensor, here 0-16 bar. In
open-loop control, the setting range is 0-100 %.
At the left hand of the column, you can see the selected setpoint
1 (A), that is the value set in the display. At the right hand of the
column, you can see the actual setpoint (B), that is the setpoint
acting as reference for the PI controller. If no kind of external
setpoint influence has been selected, the two values will be
identical. The measured value (outlet pressure) is shown as the
grey part of the column (C). See sections
and
8.7.6 Setting of influence function (4.1.3.2)
.
Below the display is a menu line for setting of setpoint 1 and
selection of operating mode, including the operating modes
"Normal" and "Stop". You can select further settings: "System
operating mode", "Control mode", "Alternative setpoints" and
"Individual pump control".
Setting range
Setpoint:
Setting via the operating panel
Setpoint
• Operation > Set setpoint 1, open loop / Set setpoint 1, closed
loop.
Set the value.
Operating mode
• Operation
Select: Normal or Stop.
Further settings
• Operation > Further settings.
Select one of the settings below:
• System operating mode. See section
• Control mode. See section
.
• Alternative setpoints. See section
.
• Individual pump control. See section
Factory setting
The setpoint is a value suitable for the system in question. The
factory setting may have been changed in the startup menu.
8.5.2 System operating mode (2.1.1)
Fig. 18
System operating mode
Description
The system can be set to six different operating modes. "Normal"
is the typical setting. See section
.
You can set the performance of the operating modes in this
menu:
• Min.
• Max.
• User-defined
• Emergency.
Setting range
• Normal
• Max.
• Min.
• User-defined
• Stop
• Emergency.
Setting via the operating panel
• Operation > Further settings > System operating mode >
Operating mode.
Select the desired line at the bottom of the display to set the
performance for "Max.", "Min.", "User-defined" and "Emergency"
run. See sections
8.7.38 Min., max. and user-defined duty
and
.
Factory setting
Normal.
Closed-loop control:
Measuring range of the primary sensor
Open-loop control:
0-100 %
A
C
B
Summary of Contents for Control MPC 2000 Series
Page 1: ...Control MPC Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 2: ...2...
Page 394: ...CN 394 8 3 CU 352 8 4 1 15 6 PV SP H G A MPC E I GENI RS 485 B D E F A B C D E F G H I C 64...
Page 411: ...CN 411 8 7 16 4 2 3 55 1 0 8 7 17 4 2 4 56 24 CU 352 1 2 3 03 00...
Page 412: ...CN 412 8 7 18 4 2 5 57 1 2 3 4 8 7 19 4 2 7 58 8 7 20 4 2 8 1 2 3...
Page 416: ...CN 416 2 Qmin 69 1 8 7 28 4 3 7 2 3 4 70 1 8 7 30 4 3 8 2 3 4 2 71 5 3 15 0 25 0 6 10 25 30 50...
Page 423: ...CN 423 8 7 39 4 3 14 1 87 MPC S MPC S 100 25 100 8 7 40 4 3 14 2 88 100 100 1 70...
Page 430: ...CN 430 8 7 53 4 3 27 1 4 104 1 4 1 2 1 4 1 1 2 2 3 4 8 7 54 4 3 28 105 8 1 2 3...
Page 433: ...CN 433 8 7 59 4 4 1 2 110 8 7 30 4 3 8 1 2 3 4 5 8 7 60 4 4 1 3 111 8 7 30 4 3 8 1 2 3 3 4 5...
Page 434: ...CN 434 8 7 61 4 4 2 112 CU 352 1 2 3 8 7 62 4 4 3 113 CU 352 8 7 14 4 2 1 1 2...
Page 438: ...CN 438 8 7 68 4 4 10 120 1 2 8 7 69 4 4 11 121 CU 352 NRV NRV 1 2 G H I J MGE MPC E...
Page 439: ...CN 439 8 7 70 1 2 4 4 13 4 4 14 122 1 2 CU 352 1 2 3 4 123 1 2 3 4 124 1 2 3 4 5 125...
Page 447: ...CN 447 9 9 1 9 2 CU 352 CU 352 12 10 5 0 20 mA 4 20 mA CU 352...
Page 452: ...Arabic AR 452 20 0 20 4 CU 352...
Page 518: ...Arabic AR 518 O26 O27 O28 CUE EC Control MPC LC Control MPC F E B A Cont r ol MPC...