Indicator light
Indication
Description
The green indicator light in the middle flashes
quickly four times.
Grundfos Eye flashes four times when you press the Grundfos Eye
symbol next to the motor name in Grundfos GO Remote.
The green indicator light in the middle is flashing
continuously.
You have selected the motor in Grundfos GO Remote, and the motor
is ready to be connected.
The green indicator light in the middle flashes
quickly for a few seconds.
The motor is controlled by Grundfos GO Remote or exchanging data
with Grundfos GO Remote.
The green indicator light in the middle is
permanently on.
The motor is connected to Grundfos GO Remote.
8.5 Standard operating panel
Stop
1
2
3
4
5
TM054848
Pos. Symbol Description
1
Grundfos Eye:
The indicator light shows the
operating status of the product.
2
-
Light fields for indication of the setpoint.
3
Up
/
Down
: The buttons change the setpoint.
4
Radio communication
: The button enables radio
communication with Grundfos GO Remote and
other products of the same type.
5
Start/Stop
: Press the button to make the product
ready for operation or to start and stop the
product.
Start
: If you press the button when the
product is stopped, the product starts if no other
functions with higher priority have been
enabled.
Stop
: If you press the button when the
product is running, the product always stops. When
you press the button, the stop icon appears at the
bottom of the display.
8.5.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or
. The
light fields on the control panel will indicate the setpoint set.
Pump in constant-pressure control mode
The following example applies to a pump in an application where a
pressure sensor gives feedback to the pump. If the sensor is
retrofitted to the pump, it must be set up manually as the pump
does not automatically register a connected sensor.
Figure Setpoint set to 72.5 psi (3 bar), constant-pressure control
mode shows that the light fields 5 and 6 are activated, indicating the
desired setpoint of 72.5 psi (5 bar) with a sensor measuring range
from 0 to 145 psi (0 to 10 bar). The setting range is equal to the
sensor measuring range.
14