Grundfos CIU 300 Functional Profile And User Manual Download Page 21

21

9. Fault finding

9.1 LED status

Faults in a CIM/CIU 300 can be detected by observing the status of the two communication LEDs. See the table below.

9.2 BACnet faults

Fault (LED status)

Possible cause

Remedy

1. Both LEDs (LED1 and LED2) remain 

off when the power supply is 

connected, and 5 seconds have 

passed.

a) The CIM 300 is defective.

Replace the CIM 300.

2. The LED for internal 

communication (LED2) is flashing 

red.

a) No internal communication 

between the CIM/CIU 300 and the 

Grundfos booster.

• Check the cable connection between the booster 

and the CIU 300.

• Check that the individual conductors have been 

fitted correctly.

• Check the power supply to the booster.

3. The LED for internal 

communication (LED2) is constantly 

red.

a) The CIU 300 does not support the 

connected booster.

Contact the nearest Grundfos company.

4. The BACnet LED (LED1) is 

constantly red.

a) Fault in the CIM 300 BACnet 

configuration.

• Ensure that the BACnet MAC address has a valid 

setting. 

See section 

3.7 Selecting the BACnet MAC address

.

• Ensure that the Device Object Instance Number is 

within the allowed range. 

See section 

3.5 Selecting the Device Object Instance 

Number

.

5. The BACnet LED (LED1) is flashing 

red.

a) Fault in the BACnet communication 

(cyclic redundancy check).

• Check the transmission speed 

(switches SW4 and SW5). 

See section 

3.4 Setting the BACnet transmission 

speed

.

• Check the cable connection between the CIM 300 

and the BACnet network.

• Check the termination resistor settings (switches 

SW1 and SW2). 

See section 

3.8 Termination resistor

.

Fault

Possible cause

Remedy

1. The CIM/CIU 300 does not 

communicate on the BACnet MS/TP 

network.

a) Configuration or wiring fault.

Ensure that the cable between the BACnet MS/TP 

devices is connected correctly. 

See section 

3.3 Connecting to the BACnet network

.

Ensure that the BACnet MAC address and Device Object 

Instance Number are configured correctly and are 

unique on the network. 

See section 

3.7 Selecting the BACnet MAC address

 and 

3.5 Selecting the Device Object Instance Number

 for 

address selection.
Ensure that the transmission speed is configured 

correctly. 

See section 

3.4 Setting the BACnet transmission speed

.

Ensure that each end of the BACnet MS/TP

trunk cable is terminated, if necessary.

See section 

3.8 Termination resistor

 for line termination 

of the Grundfos CIM/CIU 300.
Ensure that the bus topology for

a BACnet MS/TP network is correct.

b) The CIM/CIU 300 is instructed to 

not communicate on the BACnet 

network via the 

DeviceCommunicationControl 

service.

Use the Device Communication Control service to 

enable communication from the device.

2. The booster does not react to 

control commands from the bus.

a) The booster is running in local 

mode.

• Set the booster to bus control by setting the 

Present_Value of BO, 0 to 1.

• Set bus control on the CU 351display (settings/

secondary functions/control source, and select 

"controlled from bus").

3. There are only a few BACnet 

objects available, and the GENIbus 

LED flashes red.

a) There is no communication 

between the CIM 300 and the 

booster.

Ensure that the GENIbus cable between the CIM 300 

and the booster is connected correctly.

Ensure that the booster is switched on and able to 

communicate on GENIbus.

Summary of Contents for CIU 300

Page 1: ...GRUNDFOS INSTRUCTIONS Grundfos CIU 300 BACnet MS TP for Grundfos Hydro MPC Control MPC and Multi E Functional pro le and user manual...

Page 2: ...2...

Page 3: ...in this document 2 Introduction 2 1 About this functional profile This functional profile describes the CIU 300 BACnet Communication Interface Unit 300 for the following Grundfos booster systems Grund...

Page 4: ...et module It can either be mounted on a DIN rail or on a wall It is used in conjunction with Grundfos Hydro MPC Control MPC and Multi E Fig 1 CIU 300 solution for Hydro MPC and Hydro Multi E Note The...

Page 5: ...s SW6 and SW7 See section 3 7 Selecting the BACnet MAC address Line termination On or Off Set via DIP switches SW1 and SW2 See section 3 8 Termination resistor Supported transmission speeds bits s 960...

Page 6: ...egments can be connected by use of repeaters or bridges thus forming networks Multiple networks may be interconnected by BACnet routers to form a BACnet inter network 3 1 1 Line termination resistors...

Page 7: ...ce Number bits 0 to 21 Fig 5 Bit numbers The Object Type is fixed and determines that it is a Device Object The Instance Number is a numeric code that is used to identify the device It must be unique...

Page 8: ...elected it will be stored in the device and replace the default naming scheme 3 7 Selecting the BACnet MAC address To set the BACnet MAC address use the two hexadecimal rotary switches SW6 and SW7 The...

Page 9: ...Communication active Flashing red Fault in the BACnet communication Permanently red Fault in the CIM 300 BACnet configuration Status Description Off The CIM 300 has been switched off or is starting up...

Page 10: ...a value to be changed over the network X WritePropertyMultiple DS WPM B The CIM CIU 300 allows multiple values to be changed over the network X SubscribeCOV DS COV B The CIM CIU 300 can be a provider...

Page 11: ...BACnetServicesSupported Indicates which standardised protocol services are supported R Protocol_Object_Types_Supported BACnetObjectTypesSupported Indicates which standardised protocol object types ar...

Page 12: ...gital input 2 status R 0 Not active 1 Active X X BI 13 Digital input 3 status R 0 Not active 1 Active X X BI 14 Digital output 1 status R 0 Not active 1 Active X X BI 15 Digital output 2 status R 0 No...

Page 13: ...ESERVED 5 Constant flow 6 Constant temperature 7 Constant level 8 Constant percentage See section 7 1 Control modes for details on the control modes X X MI 1 Actual operating mode R Reads the current...

Page 14: ...level 8 Constant percentage See section 7 1 Control modes for details on the control modes Note Multi E always runs constant pressure mode X MO 1 Set operating mode W Sets the operating mode if bus co...

Page 15: ...bient temperature C S AI 34 Forward temperature R Flow pipe temperature C S AI 35 Return temperature R Return pipe temperature C S AI 36 Differential temperature R Differential temperature C S AI 37 O...

Page 16: ...among others 000 No alarm 003 External fault 010 Pump communication alarm 089 Closed loop feedback sensor signal fault 088 General meas sensor signal fault 203 All pumps in alarm 210 Pressure high 21...

Page 17: ...he pressure is constant regardless of the flow A pressure sensor is required Constant flow Constant level Constant temperature Constant percentage Closed loop Constant flow constant level constant tem...

Page 18: ...nitoring and resetting This example shows how to monitor faults or warnings in the booster and how to manually reset a fault The Fault code object AV 0 and the Warning code object AV 1 can both hold a...

Page 19: ...lue of 1 Now the Hydro MPC should be running at 50 in constant pressure mode with bus control 7 7 Product simulation Product profile simulation booster simulation can be useful for testing and pre com...

Page 20: ...Number See section 3 5 Selecting the Device Object Instance Number 5 If necessary set line termination See section 3 8 Termination resistor 6 Connect the GENIbus cable from the CIU 300 to the booster...

Page 21: ...3 8 Termination resistor Fault Possible cause Remedy 1 The CIM CIU 300 does not communicate on the BACnet MS TP network a Configuration or wiring fault Ensure that the cable between the BACnet MS TP...

Page 22: ...Pad 2 bytes 0x55 0xFF 1 byte 1 byte 1 byte 2 bytes MSB first 1 byte Variable 0 501 bytes 2 bytes LSB first At most 1 byte 0xFF Type Name Description 00 Token Used to pass network mastership to the de...

Page 23: ...or current protection activated MCP 93 Signal fault sensor 2 17 Performance requirement cannot be met 56 Underload 94 Limit exceeded sensor 1 18 Commanded alarm standby trip 57 Dry running 95 Limit ex...

Page 24: ...lt 198 Operation with increased power consumption 230 Network alarm 159 CIM fault Communication Interface Module 199 Process out of range monitoring estimation calculation control 231 Ethernet No IP a...

Page 25: ...7 2 13 0 D 64 4 0 115 7 3 14 0 E 65 4 1 116 7 4 15 0 F 66 4 2 117 7 5 16 1 0 67 4 3 118 7 6 17 1 1 68 4 4 119 7 7 18 1 2 69 4 5 120 7 8 19 1 3 70 4 6 121 7 9 20 1 4 71 4 7 122 7 A 21 1 5 72 4 8 123 7...

Page 26: ...26...

Page 27: ...gotanda Shiagawa ku Tokyo 141 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2...

Page 28: ...nking ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S...

Reviews: