20
8. Commissioning
8.1 Step-by-step guide to hardware setup (CIU 300)
Step
Action
1
Complete the booster configuration, e.g. sensor configuration.
2
Select the BACnet MAC address (0-127) on the CIM 300. See section
3.7 Selecting the BACnet MAC address
.
3
Select the transmission speed of the CIM 300. See section
3.4 Setting the BACnet transmission speed
.
4
Select Device Object Instance Number. See section
3.5 Selecting the Device Object Instance Number
.
5
If necessary, set line termination. See section
3.8 Termination resistor
.
6
Connect the GENIbus cable from the CIU 300 to the booster.
7
Connect the necessary cables from the CIU 300 to the BACnet network. See section
3.3 Connecting to the BACnet network
.
8
Connect the power supply cable to the CIU 300, and switch it on.
9
Confirm that the GENIbus LED is constantly green and that the BACnet LED is either off or flashing green
(indicating communication). See section
4. LEDs
.
The CIU 300 is now configured and ready.