10.3 Simulation functions
10.3.1 Protection functions
ID
Object name
R/W
Description
BO,3
Simulate Overheat Protection W
0: Disable overheat protection (default)
1: Enable overheat protection
When enabled, the valve is closed. The function is only active for underfloor
heating application.
Actual status is read via BI,6 (Warning Flow Temperature High).
BO,4
Simulate Frost Protection
W
0: Disable frost protection (default)
1: Enable frost protection
When enabled, the valve opens fully. The function is only active for heating
coil application.
Actual status is read via BI,7 (Notification Coil Frost Risk Detected).
10.3.2 Alarm/warning simulation
ID
Object name
R/W
Description
AV,2
Set Simulation Event
Code [Enum]
R/W
Set alarm/warning code to simulate.
AV,3
Set Simulation Event Sub
Code [Enum]
R/W
Set sub error code to simulate.
BO,5
Set Fault Simulation ED [Bool] W
Activate (rising edge) or deactivate (falling edge) the alarm/warning
simulation.
BI,5
Status Alarm Simulation
R
0: Inactive
1: Active
Status of alarm/warning simulation.
10.4 System monitoring
10.4.1 System state
ID
Object name
R/W
Description
MI,2
Status System State [Enum]
R
1: Powering up (~30 s)
2: Fault (fault relay activated)
3: Ready (ready relay activated)
4: Preheating heating coil
5: Temperature control state
6: Coil frost protection
7: Underfloor overheat protection
8: Shut down due to removal of start signal
9: Auto tuner on
10: Valve 100 % open (for backup)
11: Return temperature control.