6. Fault finding chart

7. Disposal

This product or parts of it must be disposed of in an 
environmentally sound way:

1. Use the public or private waste collection service.

2. If this is not possible, contact the nearest 

Grundfos company or service workshop.

Subject to alterations.

Fault

Cause

Remedy

1.

Not 
functioning.

a)

In case of too high input voltage, 
strokes of lightning, faulty 
installation, etc., the fuse may be 
blown and/or other components 
may be damaged. 

When the unit is intact, a resistance lower than 
500 

Ω

 must be measured between the terminals

• 1 and 12
• 2 and 22
• 3 and 32
• 4 and 42.
See fig. C, page 17.
The resistance must be 0 

Ω

 between the 

terminals
• PE (controller side) and 31
• PE (controller side) and 41.
The resistance must be lower than 500 

Ω

 

between the terminals
• AC and 11.
If the measured resistances are not correct, 
the FB-Ex4 unit is defective and must be 
replaced, see section 

5.2 Product numbers

.

Summary of Contents for 96440300

Page 1: ...GRUNDFOS INSTRUCTIONS LC Ex4 Installation and operating instructions...

Page 2: ...e of contents 3 LC Ex4 Declaration of conformity 4 English GB Installation and operating instructions 5 Dansk DK Monterings og driftsinstruktion 8 Deutsch DE Montage und Betriebsanleitung 11 Appendix...

Page 3: ...mgivelser II 1 G med et separat ATEX godkendelsesskilt og EF typepr vningscertifikat Yderligere oplysninger se nedenfor Certifikatnummer DEMKO 11 ATEX 1047766X DE EG Konformit tserkl rung Wir Grundfos...

Page 4: ...re 5 4 Electrical connection 6 4 1 Electrical data 6 4 2 Installation 6 5 Maintenance 6 5 1 Replacement of parts 6 5 2 Product numbers 6 6 Fault finding chart 7 7 Disposal 7 Warning Prior to installat...

Page 5: ...able Pg 7 cable diameter of 3 to 6 5 The cable glands of the float switches Pg 9 cable diameter of 4 to 8 5 Maintenance Under normal operating conditions the unit is maintenance free see section 6 Fau...

Page 6: ...ltage strokes of lightning faulty installation etc the fuse may be blown and or other components may be damaged When the unit is intact a resistance lower than 500 must be measured between the termina...

Page 7: ...Appendix 15 Appendix 1 Fig A TM01 9634 2300...

Page 8: ...Appendix 16 Fig B TM01 9533 2300...

Page 9: ...Appendix 17 Fig C TM02 9200 2104...

Page 10: ...91 Finland OY GRUNDFOS Pumput AB Mestarintie 11 FIN 01730 Vantaa Phone 358 3066 5650 Telefax 358 3066 56550 France Pompes GRUNDFOS Distribution S A Parc d Activit s de Chesnes 57 rue de Malacombe F 38...

Page 11: ...g Singapore 619264 Phone 65 6681 9688 Telefax 65 6681 9689 Slovenia GRUNDFOS d o o landrova 8b SI 1231 Ljubljana rnu e Phone 386 1 568 0610 Telefax 386 1 568 0619 E mail slovenia grundfos si South Afr...

Page 12: ...g ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Den...

Reviews: