GRUNDFOS ALLDOS U 189-010 Technical Information Download Page 9

9

15.710057-V3.0

U 189-010 en

6

Fault Correction

The numbers in brackets occurring in the following refer to the
items of the enclosed sectional drawings 15.189-200 and
12.4188-300.

FAULT

No changing over

The change - over device
switches to the stand - by bat-
tery despite filled cylinder or
drum and opened connecting
valve.

CAUSE

The gas dosing system is
leaky, so that the vacuum
required for the change - over
function cannot be gener-
ated.

The change - over device is
coupled with a chlorine gas
dosing unit V 107 or V 115,
without having provided a
compensation for the main
regulator.

The diaphragm (2) or o - ring
(3) in the change - over de-
vice are leaky.

The vacuum regulator lets
through only an insufficient
amount of chlorine or the
vacuum line is too long (this
fault occurs mainly with a
high flow rate). It can also be
the case that a chlorine cyl-
inder is frozen up.

Using the change - over de-
vice in connection with the
vacuum regulator C 105-230
(all vacuum system) the flow
rate of each regulator can
exceed 600 g/ h or 30 PPD.

DISCERNIBLE FROM

The rotameter indicates a
flow, although the supply bat-
tery (cylinder, drum) is empty
or closed.

The vacuum of 2 - 3 m WS /
52" - 78" WC required for the
change - over function is not
attained (measure the vacu-
um between change - over
device and regulator with a
vacuum meter).

The rotameter indicates a
flow, although the supply bat-
tery (cylinder, drum) is empty
or closed.

Measure the vacuum after
the outlet of the change -
over device with a vacuum
meter. The vacuum must
amount to less than 2 m WS /
52" WC.

Measure the vacuum after
the outlet of the change -
over device with a vacuum
meter. The vacuum has to
be less than 2 m WS / 52" WC.
Adjust a smaller flow rate, so
that the value of the operat-
ing vacuum falls below that
of the vacuum required for
the change - over function.

CORRECTION

Check the dosing system for
leaks. For this purpose dis-
connect the vacuum lines
between the rotameter and
the vacuum regulators one
after the other, close them
with the finger and observe
the rotameter. See 

sections

5.1 and 5.2 Leak test.

Arrange a compensation for
the main regulator.

Replace the defective parts.

Clean the vacuum regulator
and restart it or lay a vacuum
line with a larger cross sec-
tion.

Add a further vacuum regu-
lator with chlorine cylinder to
the supply battery, if the
maximum flow rate is re-
quired.

7

Spare Parts Set

There is a 

spare parts set,

 

order no. 553-1024

 available for

the vacuum change - over device U 189-010. It comprises the
o - rings (1 / 3 / 4 / 5 / 7 / 8 / 9), the diaphragm (2) as well as the
pressure spring (6). If other than the indicated parts are defec-
tive, return the change - over device to the works for repair or
replacement.

Summary of Contents for U 189-010

Page 1: ...1 15 710057 V3 0 U 189 010 en Vacuum Change over Device U 189 010 Technical Information...

Page 2: ...ical Information Version 3 0 Publisher ALLDOS Eichler GmbH Reetzstra e 85 76327 Pfinztal S llingen Postfach 1160 76317 Pfinztal Tel 49 72 40 61 0 Fax 49 72 40 61 211 Mail alldos de alldos com Internet...

Page 3: ...ng commissioning It will help you and your GRUNDFOS Alldos servicing partner to adjust the device during subsequent corrections Owner GRUNDFOS Alldos customer No Contract No Order No of device Serial...

Page 4: ...2 Construction and Function 6 3 Technical Data 6 3 1 Electrical Data of Remote Indicator 6 4 Installation 6 5 Commissioning 8 5 1 Leak Test of the Vacuum Side 8 5 2 Leak Test of the Pressure Side 8 5...

Page 5: ...rms of sale and delivery shall only be valid if the installation is implemented exclu sively by an authorized and suitably qualified personnel The safety instructions and recommendations given in this...

Page 6: ...l2 SO2 Optional connections PE tube 8 x 11 for max 4 kg h Cl2 SO2 PE tube 10 x 14 for max 10 kg h Cl2 SO2 PVC pipe DN 10 for max 10 kg h Cl2 SO2 PE tube 1 2 od 3 8 NPT threaded up to 200 PPD USA PE tu...

Page 7: ...e and connection chart of a chlorine gas dosing system with vacuum change over device 189 010 1 Gasdetect 2 Adsoroption filter 3 Vacuum regulator with liquid trap 4 Vacuum change over device 5 Chlorin...

Page 8: ...lorine gas have to be checked for leaks 5 1 Leak Test of the Vacuum Side 1 Close the connecting valves of the drums or cylinders 2 Start the injector Thereupon the vacuum lines are evacuated and in th...

Page 9: ...ure the vacu um between change over device and regulator with a vacuum meter The rotameter indicates a flow althoughthesupplybat tery cylinder drum isempty or closed Measure the vacuum after the outle...

Page 10: ...2 4 5 32 6 5 1 4 95 25 33 4 white b r o w n gas inlet II g r e e n 15 189 200 gas inlet I gas outlet type plate connection USA 1 2 sealed with Teflon strip connection PVC pipe DN15 connection PVC pipe...

Page 11: ...U 189 010 en g r e e n white b r o w n 12 4188 310 length 3 m Signal transmitter for remote indication switch direct voltage max 1 0 A contact load max 50 W switch direct voltage 75V switch alternati...

Page 12: ...12 V3 0 U 189 010 en...

Reviews: