Inspection 

According to DIN EN 806-5, the owner/user must inspect the filters every 2 months. 

To conduct an inspection, proceed as follows: 

1. 

Check the installation for leaks. 

2. 

Open several water withdrawal points (generate max. flow). 

3. 

Read off the inlet and outlet pressure at the pressure gauges. 

4. 

Calculate the differential pressure: inlet pressure (upper pressure gauge) 

  

  

  outlet 

pressure (lower pressure gauge) = differential pressure (max. 0.8 bar). 

5. 

Replace the filter elements if the differential pressure is > 0.8 bar. 

6. 

If the differential pressure of the device cannot be reduced by replacing the filter 
elements, there is a malfunction. 

6.4 

Maintenance 

 

 

WARNING:

 If the intervals for inspection and replacement are not observed, the filter 

elements will become excessively polluted. 

 

●  Health risk due to contamination of the drinking water. 

►  Observe the intervals for inspection and replacement of the filter elements. 

 

Some regular work is necessary in order to ensure the proper functioning of the product in 
the long term. For this purpose, DIN EN 806-5 recommends a semi-annual and an annual 
maintenance. 

 

 

The filter elements must be replaced every 6 months for hygiene reasons, in line with DIN 
EN 806-5. We recommend replacing the O-ring of the cover every 2 years. 

 

Summary of Contents for GENO-fine FM 150

Page 1: ...We understand water Filters GENO fine filter FM Operation manual...

Page 2: ...written consent of Gr nbeck Wasseraufbereitung GmbH no part of this manual may be reproduced in any way nor may any part be processed duplicated or distributed using electronic systems Non compliance...

Page 3: ...description 10 3 1 Intended use 10 3 2 Foreseeable misuse 10 3 3 Product components 11 3 4 Functional description 12 3 5 Accessories 12 4 Installation 13 4 2 Requirements regarding the installation si...

Page 4: ...1 4 Symbols used This symbol identifies instructions that you must comply with for your own personal safety as well as to avoid damage to property This symbol identifies instructions that you must com...

Page 5: ...tion Instruction Multi step instruction and chronological sequence of actions is important 1 First action a first step b second step 2 Second action Result following an instruction Result Lists Listed...

Page 6: ...quiries or orders Enter the necessary information in the table below to have it readily available whenever necessary Item Designation Item Designation 1 EAC mark 2 Product designation 3 Nominal connec...

Page 7: ...y with the hygiene instructions in chapter 6 Failure to comply can result in microbiological contamination of your drinking water installation Keep your product permanently connected to the water supp...

Page 8: ...e to property may occur 2 3 Regulations When installing and starting up the system amongst others comply with the following regulations and guidelines Statutory regulations on environmental protection...

Page 9: ...explicitly designated for a specialist installer Only use this product as intended Make sure that the required inspection and maintenance work is carried out Keep this manual 2 6 Product specific saf...

Page 10: ...for positive and negative pressure applications The filters are designed according to the stipulations of DIN EN 13443 1 and DIN 19628 and are intended for installation into drinking water pipes accor...

Page 11: ...components Item Designation Item Designation 1 Deaerator 2 Cover 3 Cover ring 4 O ring 5 Screws 6 Filter housing 7 Pressure gauge for inlet pressure 8 Flange 9 Draining valve 10 Pressure gauge for out...

Page 12: ...ial pressure between the raw water inlet and the pure water outlet increases If the differential pressure of 0 8 bar at the flow rate of the filter is exceeded the filter elements must be replaced 3 5...

Page 13: ...specialist installer Installation in the drinking water system In accordance with DIN EN 806 2 and DIN EN 1717 the product is installed in the water pipe downstream of the water meter and upstream of...

Page 14: ...Installation 14 40 BA_TD3 AF001en_004_Feinfilter FM docx Installation into systems It is possible to use the filter in the partial flow...

Page 15: ...e 4 2 Requirements regarding the installation site Observe local installation directives general guidelines and technical specifications The installation site must be frost proof and ensure the filter...

Page 16: ...the scope of supply Item Designation Item Designation 1 Deaerator 2 GENO fine filter with flange connection according to DIN EN 1092 1 3 Operation manual 4 Draining valve 5 Pressure gauge 2 pieces 6...

Page 17: ...ction prior to assembling the individual parts Install the individual parts in accordance with the direction of flow NOTE Seal loose parts during assembly Leakage at the filter Seal the pressure gauge...

Page 18: ...the filter in the pipe 1 Prepare the pipe with flange connection according to DIN EN 1092 1 the distance between the two seals must be 690 mm 2 Check the flow direction given on site 3 By way of the s...

Page 19: ...fitting with male thread must be mounted at the draining valve by the client on site female thread of draining valve 1 inch Make sure that the draining valve is closed 1 Open the deaerator 2 Slowly o...

Page 20: ...plain to the owner user how the product works Use the manual to brief the owner user and answer any questions Inform the owner user about the need for inspections and maintenance Hand over all documen...

Page 21: ...all maintenance work is carried out on time Only use genuine spare and wearing parts from Gr nbeck 6 1 Cleaning Only clean the outside of the product Do not use any strong or abrasive cleaning agents...

Page 22: ...tial pressure is 0 8 bar 6 If the differential pressure of the device cannot be reduced by replacing the filter elements there is a malfunction 6 4 Maintenance WARNING If the intervals for inspection...

Page 23: ...he replacement of the filter elements 1 Install a hose fitting with male thread at the draining valve on site 2 Direct a waste water pipe towards the sewer 3 Close shut off valves 1 inlet and 2 outlet...

Page 24: ...40 BA_TD3 AF001en_004_Feinfilter FM docx 1 Loosen the nuts 2 Remove the washers 3 Remove the cover ring 4 Remove the cover 5 Flush the sunk dirt particles from the filter housing via the draining val...

Page 25: ...f the used filter element in accordance with local regulations For hygienic reasons the new filter element must not be touched with bare hands 4 Slide the new filter element in its foil packaging over...

Page 26: ...en_004_Feinfilter FM docx 9 Put on the filter cover 10 Put on the cover ring 11 Evenly and gradually screw on the nuts with washers crosswise The cover is fully tightened 12 Put the filter into operat...

Page 27: ...s to be done 1 Check the O ring for wear and tear 2 Check the filter for tight fit and leaks 6 5 Consumables Designation Order no FM 150 filter element 80 m 2 pieces 103 077 FM 200 filter element 50 m...

Page 28: ...e filter elements The shut off valves are not open completely Completely open the shut off valves Water escapes at the screw connections of the filter housing The screw connections are leaky Have the...

Page 29: ...eans that this product and the electrical and electronic components must not be disposed of as household waste Find out about the local regulations on the separate collection of electrical and electro...

Page 30: ...wall to centre of connection mm 300 300 F Clearance required for replacement of filter element mm 600 900 Filter elements quantity piece s 14 28 Operating weight approx kg 255 327 Empty weight kg 100...

Page 31: ...Technical specifications 31 40 BA_TD3 AF001en_004_Feinfilter FM docx 9 1 Pressure loss curves Item Designation Item Designation 1 Pressure difference bar 2 Flow rate m3 h...

Page 32: ...__________________________ 10 1 Start up log Customer Name Address Installation Accessories Floor drain available yes no Safety device yes no Operating values Water pressure at raw water inlet bar Wat...

Page 33: ...Operation log 33 40 BA_TD3 AF001en_004_Feinfilter FM docx 10 2 Maintenance Date Work performed Signature...

Page 34: ...Operation log 34 40 BA_TD3 AF001en_004_Feinfilter FM docx Date Work performed Signature...

Page 35: ...Operation log 35 40 BA_TD3 AF001en_004_Feinfilter FM docx Date Work performed Signature...

Page 36: ...Operation log 36 40 BA_TD3 AF001en_004_Feinfilter FM docx Date Work performed Signature...

Page 37: ...Notes 37 40 Notes...

Page 38: ...27 H Hygienic replacement of the filter element 25 I Inspection 22 Installation of the filter in the pipe 18 Installing the product 17 M Maintenance 22 P Pressure loss curves 31 S Spare parts 27 Start...

Page 39: ......

Page 40: ...Gr nbeck Wasseraufbereitung GmbH Josef Gr nbeck Str 1 89420 Hoechstaedt Germany For more information go to www gruenbeck com 49 9074 41 0 49 9074 41 100 info gruenbeck com www gruenbeck com...

Reviews: