Certificate
Growatt SPH series inverter apply within the scope of the world, So the inverter have
to satisfy different countries and regions of different safety standards.
15
Contact
If you have technical problems about our products, contact the Growatt Service line
or dealer. We need the following information in order to provide you with the
necessary assistance:
1. SPH inverter Serial number
2. SPH inverter module information
3. SPH inverter communication mode
4. SPH inverter fault information code
5. SPH inverter Display content
6. The manufacturer and model of the battery
7. Battery capacity and connection mode
Model
Certificate
Shenzhen Growatt New Energy Technology Co.,LTD
No.28 Guangming Road, Shiyan Street, Bao'an District, Shenzhen, PR.China
T
:
+86 0755 2951 5888
E
:
W
:
www.ginverter.com
59.S2 Limit
230.8 V - xxx V
59.S2 Testing
Waiting to start
264.5 V 200ms
59.S2 Limit
264.7 V 180ms
59 .S2 Pass
230.8 V - xxx V
59.S2 Testing
195.5 V 400ms
27.S1 Limit
194.7 V 380ms
59 .S2 Pass
50.01-xxxxHz
81>S2 Testing
51.5HZ
100ms
81>S2 Limit
51.52 HZ
80ms
81>S2 Pass
50.01-xxxxHz
81<S2 Testing
47.50HZ
100ms
81<S2 Limit
47.49 HZ
80ms
81<S2 Pass
230.4- xxxxV
59 .S1 Testing
253.0V
3000ms
59.S1 Limit
254.7V
3000ms
59.S1 Pass
230.4- xxxxV
27.S2 Testing
92.0V
200ms
27.S2 Limit
90.8V 180ms
27.S2 Pass
50.01 - xxxxHZ
81 >S1 Testing
50.5HZ 100ms
81>S1 Limit
50.05V 80ms
81>S1 Pass
50.01 - xxxxHZ
81 <S1 Testing
49.5HZ 100ms
81<S1 Limit
49.5HZ 80ms
81<S1 Pass
Auto Test Passed
Auto Testing
WorkMode
YES ?
Press
“
enter
”
more
than 3 seconds to enter
WorkMode
Auto Test
Auto Test (only for Italy)
Follow is the chart of Auto Test, refer to 6.4.4. in the set up surface of “Auto Test”.
Press the “Enter” key, make sure to start auto test by press “enter” key 3 seconds.
The LCD will display the follow message.
Annex
NRS 097-2-1
Growatt SPH3000TL BL-UP
Growatt SPH3600TL BL-UP
Growatt SPH4000TL BL-UP
Growatt SPH4600TL BL-UP
Growatt SPH5000TL BL-UP
Growatt SPH6000TL BL-UP