5

5. Again hold hand at a distance of approx. 5 - 10cm in front 

of the sensor system.
The flow volumes are indicated via the indicator lamp in the 
sensor system by groups of flashing signals separated 
by a pause.

6. Flow volumes and display: 

The number of flashing signals of the consecutive groups 
corresponds to the following flow volumes:

1

 = flow volume 1 litres

Pause

2

 = flow volume 2 litres

Pause

3

 = flow volume 3 litres (factory setting)

Pause
...

7

 = flow volume 7 litres

Pause
After the group with 7 flashing signals, the routine starts 
from the beginning

1

 = flow volume 1 litres

...

7. Selecting the flow volume

The flow volume is selected by removing the hand from the 
detection zone (at least 60cm) in the pause after a group 
of flashing signals. Once the hand is removed, the fitting 
immediately flushes with the selected flow volume 
(the corresponding flashing signals are displayed 
again during flushing).

8. The flow volume can be readjusted within the next 20 s 

if necessary by again holding the hand at a distance 
of 5 - 10cm in front of the sensor system (see point 5).

The selected flow volume is accepted as the new setting and 
setting mode is automatically terminated if there is no hand in 
front of the sensor system 20 s after flushing. The area directly 
in front of the sensor system must be kept free from objects for 
these 20 s as otherwise the flow volume will be unintentionally 
adjusted once more.

Additional functions of the urinal fitting

The following settings can be made and changed 
with the remote control (Prod. no.: 36 206):

Switch on/off 24-hour flush

(factory setting: switched on)
1. Press and hold the 

RESET 

button.

2. Then additionally press the 

OFF AUTO

 button within 2 s.

The indicator lamp in the sensor system of the fitting flashes:

4 x short

 = 24-hour flush is switched on,

2 x long

 = 24-hour flush is switched off.

No-use flush interval: 24 hours.

Switch on/off intermediate flush

(factory setting: switched on)
1. Press the 

TEST

 button => test mode is switched on.

2. Press the 

OFF AUTO

 button as required.

The indicator lamp in the sensor system of the fitting flashes:

4 x short

 = intermediate flush is switched on,

2 x long

 = intermediate flush is switched off.

Setting mode is quit by pressing the 

TEST

 button, 

or automatically after 60 s.

Switch on/off pre-flush

(factory setting: switched off)
1. Press the 

TEST

 button => test mode is switched on.

2. Press the 

ON AUTO

 button as required.

The indicator lamp in the sensor system of the fitting flashes:

4 x short

 = pre-flush is switched on,

2 x long

 = pre-flush is switched off.

Setting mode is quit by pressing the 

TEST

 button, 

or automatically after 60 s.

Set minimum delay time

(factory setting: 7 s)
1. Press the 

TEST

 button => test mode is switched on.

Using the 

+

 and 

 buttons (

 button), the minimum 

delay time can be increased (

+

) or reduced (

).

2. Press the 

+

 or 

 button (

 button).

The indicator lamp in the sensor system of the fitting flashes:

4 x short

 = adjustment by one step (approx. 1 s),

2 x long

 = end position reached.

Setting mode is quit by pressing the 

TEST

 button, 

or automatically after 60 s.

Maintenance

Inspect and clean all components and replace if necessary.

Shut off the water supply and switch off the voltage 
supply.

Cleaning or replacing filter

1. Remove locking screw (E1), see Fig. [9].
2. Remove plate (E) upwards from frame (I), see Fig. [9].
3. Disconnect plug-in connector between solenoid valve (D) 

and electronics (E), see Fig. [11].

4. Close isolating valve (H), see Fig. [12].
5. Remove solenoid valve (D), see Fig. [13].
6. Remove filter (K) and clean or replace, see Fig. [14].
7. Insert filter (K).
8. Fit solenoid valve (D), during this process pay attention to 

the seals (D1) and the direction of flow, see Fig. [15].

9. Connect electronics (E) to solenoid valve (D), see Fig. [16].

10. Open isolating valve (H), see Fig. [7].
Assemble in reverse order.

Replacing solenoid valve

1. Remove locking screw (E1), see Fig. [9].
2. Remove plate (E) upwards from frame (I), see Fig. [9].
3. Disconnect plug-in connector between solenoid valve (D) 

and electronics (E), see Fig. [11].

4. Close isolating valve (H), see Fig. [12].
5. Remove solenoid valve (D), see Fig. [13].
6. Fit new solenoid valve (D), during this process pay attention 

to the seals (D1) and the direction of flow, see Fig. [15].

7. Open isolating valve (H), see Fig. [7].
Assemble in reverse order.

Replacing the transformer

Switch off voltage supply!

1. Remove locking screw (E1), see Fig. [9].
2. Remove plate (E) upwards from frame (I), see Fig. [9].
3. Disconnect plug-in connector between transformer (F) 

and electronics, see Fig. [17].

4. Pull headpart (F) of the transformer off the base (G), 

see Fig. [17].

5. Attach new headpart, see Fig. [18].
6. Connect electronics and transformer (F), see Fig. [18].
Assemble in reverse order.

Replacing the top plate with electronics

1. Remove locking screw (E1), see Fig. [9].
2. Remove plate (E) upwards from frame (I), see Fig. [9].

Summary of Contents for Tectron 37749

Page 1: ...19 LV 23 RUS 27 E 4 DK 8 UAE 12 P 16 HR 20 LT 24 94 329 331 ÄM 203841 10 08 Tectron Tectron 37 749 38 451 D 1 I 13 N 25 GR 37 TR 49 BG 61 RO 73 GB 4 NL 16 FIN 28 CZ 40 SK 52 EST 64 CN 76 F 7 S 19 PL 31 H 43 SLO 55 LV 67 RUS 79 E 10 DK 22 UAE 34 P 46 HR 58 LT 70 Design Quality Engineering GROHE Germany ...

Page 2: ... 749 Please pass these instructions on to the end user of the fitting S v p remettre cette instruction à l utilisateur de la robinetterie Bitte diese Anleitung an den Benutzer der Armatur weitergeben 38 451 ...

Page 3: ...II 1 A A1 1 2 H 5 s 2 3 B1 B 4 D1 D1 D C 30mm 6 F E D 2 1 H 7 8 I E E1 1 2 3 2mm 9 I E E1 2mm 1 2 3 10 5 s 1 2 11 E D D1 D1 D 30mm 13 5 G F H 12 ...

Page 4: ...ews B1 see Fig 3 5 Replace spacer C with solenoid valve D during this process pay attention to the seals D1 and the direction of flow see Fig 4 6 Fit headpart F of the transformer to the base G see Fig 5 remove protection first 7 Connect headpart F of the transformer to the electronics E see Fig 6 8 Connect solenoid valve D to electronics E see Fig 6 9 Open isolating valve H see Fig 7 10 Engage pl...

Page 5: ...tch on off pre flush factory setting switched off 1 Press the TEST button test mode is switched on 2 Press the ON AUTO button as required The indicator lamp in the sensor system of the fitting flashes 4 x short pre flush is switched on 2 x long pre flush is switched off Setting mode is quit by pressing the TEST button or automatically after 60 s Set minimum delay time factory setting 7 s 1 Press t...

Page 6: ...rease reduce detection zone using remote control special accessories 36 206 Solenoid valve defective Replace solenoid valve see Replacing solenoid valve Transformer faulty Replace transformer see Replacing transformer Electronics defective indicator lamp not flashing or permanently on Replace electronics see Replacing the top plate with electronics Water flowing continuously Solenoid valve defecti...

Page 7: ...III 19 E D F 20 E2 E E3 E4 18 F 1 2 17 G F 1 2 15 D1 D1 D 14 K 2 1 16 D E ...

Page 8: ......

Page 9: ......

Reviews: