8

IV. Sensor element

1. Loosen screw (D1) and push sensor bracket (D) 

downwards, see Fig. [3].

2. Disconnect plug-in connector between sensor cable (E1) 

and electronic module (A), see Fig. [15].

3. Disengage sensor (E) at the bottom and detach from 

bracket (D), see Fig. [4].

Assemble in reverse order.

Disconnect and reconnect plug-in connector between 
electronic module (A) and transformer (H), see Fig. [11].

After reconnecting power supply, position detection begins.

V. Sensor for wall installation

1. Disconnect plug-in connector between sensor cable (E1) 

and electronic module (A), see Fig. [16].

2. Close isolating valve (B), see Fig. [8].
3. Remove urinal.
4. Turn retaining tabs (K) and remove sensor (E), see Fig. [6].

Assemble in reverse order.

Disconnect and reconnect plug-in connector between 
electronic module (A) and transformer (H), see Fig. [11].

After reconnecting power supply, position detection begins.

Replacement parts, 

see fold-out page I 

( * = special accessories). 

Fault/ cause/ remedy

Fault

Cause

Remedy

No flushing

• Water supply interrupted

- Open isolating valve

• Filter in solenoid valve blocked

- Clean or replace filter, see Solenoid 

valve and filter maintenance

• Plug-in connector without contact

- Attach plug-in connector

• The detection zone of the sensor system 

is set too low/too high

- Increase/reduce range, see Settings, 

Setting the range

• Solenoid valve defective

- Replace solenoid valve, see Solenoid 

valve and filter maintenance

• Transformer faulty

- Replace transformer, see Transformer 

maintenance

• Software lock activated because 

compensation routine has been 
performed 25- times

- Reset counter, see Resetting counter

• Electronics defective (indicator lamp 

not flashing or permanently on)

- Replace electronic module, see 

Maintenance of electronic module

Water flowing continuously

• Solenoid valve defective 

- Replace solenoid valve, see Solenoid 

valve and filter maintenance

Undesired flushing

• The detection zone of the sensor system 

is set too high

- An opposite object will be detected. 

Reduce range, see Settings, 
Setting the range

Flow volume too low

• Flow volume set too low

- Adjust flow volume, see Settings, 

Setting the flow volume

• Filter in solenoid valve defective

- Clean or replace filter, see Solenoid 

valve and filter maintenance

• Filter in solenoid valve blocked

- Clean or replace filter, see Solenoid 

valve and filter maintenance

• Solenoid valve defective 

- Replace solenoid valve, see Solenoid 

valve and filter maintenance

Flow volume too high

• Flow volume set too high

- Adjust flow volume, see Settings, Setting 

the flow volume

• Solenoid valve defective 

- Replace solenoid valve, see Solenoid 

valve and filter maintenance

Position detection is not 
performed (No flushing)

• Replacement part exchanged, 

no position detection

- Reset counter, see Resetting counter

• Software lock activated because 

compensation routine has been 
performed 25- times

- Reset counter, see Resetting counter