Sequence of Operation

CAUTION

WAIT AT LEAST 60 SECONDS BEFORE

ATTEMPTING TO RE-LIGHT THE MAIN

BURNER AFTER IT SHUTS OFF.

When electrical power is turned on to the unit, the following happens:

•      The drain valve closes

•      The water valve opens

•      The unit fills with water

As the boiler fills, the water is detected by two probes. The first of these is the “mid” 

probe, which activates the RESET light. The second (“hi” probe) is reached when the 

boiler is full, and shuts off the water supply. As the water supply drops below this 

probe, the water supply opens until it is again reached.

The gas valve has a step-opening feature. When the control calls for the main burner 

to light, the outlet pressure of the valve is maintained at a preset (non-adjustable) rate 

for several seconds, before full rated pressure is allowed to develop.

Once the main burner shuts down, step-opening gas valves need at least 60 seconds 

to reset. If an attempt to re-light the burner is made before these valves reset, it may 

bypass or shorten the length of the low pressure step, and could re-light the main 

burner under full flow rate.

A thermostatically-controlled air vent remains open while the boiler fills. As steam 

begins to develop, this vent will close. Some steam may escape from this vent before 

it is fully closed (at approximately 200ºF).

Once the pressure has reached 9-1/2 PSI, the main burner will be shut off by an 

operating pressure switch. Residual heat stored in the boiler’s heat exchanger can, 

however, cause the pressure to continue to build, even after the burner has shut down. 

This is especially true when the unit is heated for the first time.

If/when the pressure reaches 12 PSI, a relief valve will open to prevent pressure from 

increasing past 12 PSI. As pressure decreases, the main burner will automatically re-

light to maintain 9-1/2 PSI.

Even if something causes the pressure to pass 12PSI, a high-limit safety switch will 

shut down the boiler electrically when it reaches 14-1/2 PSI. If this happens, the unit 

should not be re-started until the problem which caused the shut-down has been 

corrected.

As an additional safety measure, the unit is equipped with an A.S.M.E.-certified safety 

valve which will open to relieve excess pressure at 15 PSI. The ability of this valve to 

discharge steam pressure is greater than the boiler’s ability to generate steam.

When electrical power is turned off, the gas valve automatically shuts off flow to the 

main gas burner.

A thermostatic switch (mounted on the boiler shell) keeps the drain valve closed until 

the temperature drops to approximately 170ºF.

At that point, the thermostatic switch opens and water drains from the boiler. A 

vacuum breaker allows air to enter the boiler for this purpose.

CAUTION

ESCAPING STEAM MAY CAUSE SEVER 

BURNS.  STAY AWAY FROM THERMOSTATIC 

AIR VENT AND PRESSURE RELIEF VALVES.

Summary of Contents for CNGB/3-24

Page 1: ...ustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipmen...

Page 2: ...MANUFACTURER WARNING DO NOT MIX DE LIMING AGENTS ACID AND DE GREASERS ALKALI IN THE STEAM GENERATOR OR ON THE COOKING CHAMBER WALLS NOTICE Do not use a cleaning or de liming agent that contains any S...

Page 3: ...0 NATIONAL FIRE PROTECTION ASSOCIATION 60 Batterymarch Park Quincy Massachusetts 02269 NFPA 70 The National Electrical Code NFPA 54 Installation of Gas Appliances Piping NFPA 96 Ventilating Hoods NSF...

Page 4: ...The boiler is constructed of 1 4 thick steel which is certified by the American Society of Mechanical Engineers ASME for pressure vessels All welds are hydrostatically tested The boiler is also equip...

Page 5: ...0 to 60 ppm Chlorine and Chloramine less than 0 1 ppm Total Chloride less than 30 ppm Silica less than 12 ppm Undissolved Solids less than 5 microns 1 Do not rely on unproven water treatments which ar...

Page 6: ...system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSI 3 45 kPA 1 Gas Supply Connection a Co...

Page 7: ...Connection a The drain connection is made at the rear of the unit with 1 1 4 NPT pipe DO NOT USE PLASTIC PIPE DRAIN PIPING MUST WITHSTAND STEAM AND BOILING WATER Extend the drain piping to a nearby fl...

Page 8: ...repeat the trial for ignition 5 Turn the on off switch on the cabinet front panel to the ON position The amber light in the switch will come on The boiler drain valve will close The unit will fill wit...

Page 9: ...ically stop the gas flow and terminate the ignition trial If ignition is terminated turn the switch off and then ON again to repeat the trial Normally the pilot should light within five seconds of tur...

Page 10: ...nce the pressure has reached 9 1 2 PSI the main burner will be shut off by an operating pressure switch Residual heat stored in the boiler s heat exchanger can however cause the pressure to continue t...

Page 11: ...under the boiler 3 Close the manual drain valve 4 Turn off water supply to the boiler 5 Allow the boiler to cool This takes several hours so it is recommended that you cool the boiler overnight 6 Tur...

Page 12: ...r doors 19 Turn the on off switch OFF and slowly open the manual drain valve 20 When the boiler has drained completely close the manual drain valve and turn the on off switch to ON to fill the boiler...

Page 13: ...hnician a weekly check of the following will help prevent down time and ensure continued efficient operation 1 Pressure gauge operation 2 Proper water level gauge 3 Strainer in water feed line clear 4...

Page 14: ...reater than 60 PSI Authorized Service Rep Only c Is the Water Level Control Board defective Check for loose electrical connections on hi water fill solenoid X d Is the water fill solenoid valve defect...

Page 15: ...uilds pressure but shuts down RESET light comes on User a Is the water level below the mid water level probe Verify that the water supply is sufficient to maintain the water level at or above the mid...

Page 16: ...7a Main Burner Assy 0 2000 Ft Elev Incl 29 Gas Jets W 54 Drill Dia Hole For Natural Gas 047267 7a Main Burner Assy 0 2000 Ft Elev Incl 29 Gas Jets W 68 Drill Dia Hole For Propane Gas 050491 8 Gas Val...

Page 17: ...ressure Relief Valve 12PSI 099228 7 Water Level Probes lo med hi 076526 8 Solenoid Valve Water in 099220 9 Check Valve 004187 10 Air Vent 145167 11 Vacuum Breaker 090787 12 Globe Valve 1 2 NPT 099255...

Page 18: ...nal Block 2 Pole 003887 Bushing Snap 11 16 ID 012864 7 Circuit Board Support 099292 8 Water Level Control Board Assembly 116016 9 Lug Ground 14 6 AWG 119829 10 Circuit Breaker 119860 11 Transformer 75...

Page 19: ...ED 11 WHITE P1 J1 1 TSTAT DRAIN VALVE 1 2 2 T1 LO 14 5 PSI OPERATING PRESSURE GAS VALVE 7 YELLOW 8 BLACK C HL 12 BLACK 10 BLACK 9 RED C PS SW H C G BLACK YELLOW BLUE WHITE 4 BLACK 6 BROWN 5 BLUE 3 BRO...

Page 20: ...20 OM NGB 3 Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 21: ...OM NGB 3 21 Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 22: ...22 OM NGB 3 Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 23: ...OM NGB 3 23 Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 24: ...REV D 07 14 1055 Mendell Davis Drive Jackson MS 39272 888 994 7636 601 372 3903 Fax 888 864 7636 unifiedbrands net 2014 Unified Brands All Rights Reserved Unified Brands is a wholly owned subsidiary o...

Reviews: