5.1 Fixing
The unit can be used both rested on floor and fixed onto a structure. The unit can operate in any position.
Use the four Ø4.5 holes (0.18”) on the box in order to fix the
device
5.2 Connection to mains power
The unit can operate with voltage from 90 to 250Vac with frequency of 50 and 60Hz.
5.0 Installation
1
33
m
m
5,
24
in
24mm
0,94in
Warning!
Make sure that the structure can hold up to 10 times its weight.
Warning!
• Before connecting the unit, verify that power supplies features are compatible with the unit features.
• The unit must never be installed if not grounded electrically.
• It is suggested to use a magnetothermic switch along the power supply line, as prescribed by in force rules.
• The unit must not be powered up through a dimmer power device.
• Wiring and connection actions are to be performed by a qualified staff.