background image

White

Power 24V AC/DC

Ground/common

Red

Input signal

0-10V DC

Black

FNR.0.2 / FNR.0.2-EQ Actuator

0-10V modulating

FlowCon FNR (analog)

FlowCon FNR (digital)

Power 110/230V AC

Ground/common

Close

Open

FNR.0.3 Actuator

2-Position

Red

White

Black

Power 110/230V AC

Ground/common

Close

Open

Stop

FNR.0.3 Actuator

3-Point Floating

Black

Red

White

Wiring

Start-up Sequence

When power to the actuator is turned on, the 

actuator will automatically calibrate to deter-

mine closing point and stroke length of the in-

sert. Hereafter it will proceed to normal opera-

tion mode (according to control signal).

Manual Override

Before performing override, please turn off the 

power supply. Lift the silicone cap on top of the 

actuator to get access to manual override. Man-

ual override is performed with a 4 mm (~5/32”) 

hex key. Counter-clockwise turning will open the 

valve and clockwise turning will close the valve.

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

FlowCon FNR Actuators

1B95088 - 11/2020

Page 2 of 2

FlowCon International assumes no responsibility for mistakes, if any

, in any printed material.