Ensure the solar cable run is
NOT
connected to the solar panels.
Keep the fuse holders disconnected by keeping them open with the
fuses
OUT
and the PV Array DC isolators are in the off position.
To disconnect the fuses, pull the front
tabs down to open the fuse holders.
Keep the fuse holders open with the
fuses left out of the fuse holders.
10X38 ZTPV-25X
10X38 ZTPV-25X
Ensure the fuse holders are disconnected by keeping them open with the fuses
OUT
.
Use wire
strippers to strip the ends of the solar cable, and terminate them in the fuse holders by inserting the
stripped end and tightening the screw clockwise. Make sure the clamp inside the fuse holders are
contacting the metal conductor, and
NOT
the insulation of the wire.