Wiring
• Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment
damage.
• Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used
to supply inductive loads such as motors. Make all connections in accordance with national and local codes.
• Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the wire diagram for the
applicable power supply and output signal type.
• Select desired signal output type (mA or Vdc) by placing the output switch in required position, as shown in Figure 5.
Factory default is mA (4-20 mA).
• If mA was selected, no further Output set up is required. If VOLT output is selected in Figure 5, place Voltage Output Jumper
to desired span position, as shown in Figure 6. ie: 10 = 0-10 Vdc. Factory default is 10v = 0-10Vdc.
• Connect the DC positive or the AC voltage hot side to the PWR terminal. For voltage output or AC power, the supply
Common is connected to the COM terminal. The device is reverse voltage protected and will not operate if connected
backwards. It has a half-wave power supply so the supply Common is the same as the signal Common. See Figure 7.
•The analog output is available on the OUT terminal. Check the controller Analog Input to determine the proper
connection before applying power as shown in Figure 7.
• If installed, the resistance temperature output is available on the two terminals labelled TEMPERATURE SENSORas shown in
See Figure 8.
Voltage
Output
Selection
0-10 Vdc
(Factory
default)
mA = 4-20 mA
(Factory Default)
Output Type
Selection Switch
Figure 6
Figure 5
Figure 8
Dimensions:
PRINTED IN C
ANAD
A
V. RH200A 10/14
Figure 7
Wiring for voltage output signal
and 24 Vdc power from controller
Wiring for all output signals and
external 24 Vac power transformer
24 Vdc Power Supply
0-5 Vdc
VOLT = Vdc
* No setting required if output selection switch is set to mA in Figure 5
Specification:
Sensor Type:...................Thermoset Polymer based Capactive
Range:..............................0 to 100% RH
Accuracy:........................±2, 3, or 5% RH (5 to 95% RH)
Response:.......................15 Seconds typical
Temp Dependence:....±0.05% RH/ ˚C
Hysteresis:......................±1.5% RH maximum
Repeatability:...............±0.5% RH typical
Linearity:........................±0.5% RH typical
Operating Range:........-40 to 85˚C (-40 to 185˚F)
Power Supply:...............18 to 30 Vdc, 15 to 26 Vac
Consumption:...............22 mA maximum
Protection Circuitry:...Reverse voltage protected and output
limited
Output Signal:..............4-20 mA current loop, 0-5 or 0-10 Vdc
(selectable)
Output Drive @ 24 Vdc:..550 ohms max for current output
10K ohms min for voltage output
Internal Adjustments:.Clearly marked ZERO and SPAN pots
Optional Temp.:............RTD’s or Thermistors. 2 Wire
Probe:..............................230 mm (9”) probe length x 12.7 mm (1/2”)
diameter stainless steel with 60 micron HDPE
porous filter
Enclosure:......................ABS - UL94-5VB - IP61 (NEMA 2)
*In order to maintain the published NEMA/IP
ratings, properly rated conduit or cable gland
adapters must be used.
Termination:.................Screw terminal block (14 to 22 AWG)
84.3 mm
3.320 “
115.8 mm
4.56 “
53.6 mm
2.110 “
228.60 mm
9”
2X Ø 0.850”
12.70 mm
0.50“
304 Series S/S Probe
60 micron HDPE filter
Wiring for 4-20 mA loop-powered
output and external 24 Vdc external
power supply
Wiring for 4-20 mA loop-powered
output and external 24 Vdc power
from controller
Optional Temperature Sensor
Greystone Energy Systems, Inc. 150 English Drive, Moncton, NB E1E 4G7 Canada Tel: +1-506-853-3057 Tollfree (North America): +1-800-561-5611 Fax: +1-506-853-6014
Email: [email protected] Web: www.greystoneenergy.com
Cop
yr
igh
t © Gr
ey
stone Ener
gy S
yst
ems I
nc
. A
ll R
igh
ts R
eser
ved