background image

Installation Guide

  

CSR-112 / CSR-124 Command Relay

 

 

 
Oct 13, 2009        www.greystoneenergy.com             1-800-561-5611             [email protected]              Page 2           

   

 

 

Wiring 

 
 
 
 
The controller digital output (either 12 Vdc 
for CSR-112 or 24 Vdc for CSR-124) 
controls the CSR command relay coil input. 
When the coil signal is received, the CSR 
relay contacts close to supply 120 Vac power 
to the motor contactor. 
 
The motor contactor then switches the 600 
Vac power to the fan and the fan starts. 
 
The CS-610 current switch monitors the 
current flow to the fan and when it’s trip level 
is exceeded, it supplies a digital input signal 
to the controller to indicate the fan status. 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
The CS-610 monitors the current to the 
heater. When the heater current exceeds 
the CS-610 trip point, the CS output 
contacts close to complete the low 
voltage circuit and 24 Vdc is applied to 
the CSR-124 coil input. 
 
The energized coil input closes the CSR 
relay contacts and applies 120 Vac to 
the fan. 
 
 

 
 
 
 

 
 
 

 

Reviews: