Page  2

pushbutton to select the switching point (e.g. 5.05 m/s = NC) of the relay. The chosen value (m/s) is shown 

on the display. Remove and store the jumper after the configuration is complete.

To configure the hysteresis (display required) install a jumper to pins labeled hyst. as shown in Figure 7. 

Press down on the pushbutton to select the hysteresis of the relay switching point. The chosen value (m/s) 

is shown on the display. Remove and store the jumper after the configuration is complete. The hysteresis 

maximum setting is based on the range selected.

NOTE: The configuration jumpers must be removed and stored for proper operation.

Figure 4

Figure 5

Figure 6

Figure 7

NC

COM

NO

Tout

Vout

24 V

GND

Tout

Vout

24 V

GND

Analog Input 1

Analog Input 2

Power Supply

Common

Controller

NC

COM

NO

Jumper Placement

Jumper (J1): Installed

Jumper (J2): Not installed

Range 2 (0-2 m/s)

Range 10 (0-10 m/s)

Range 20 (0-20 m/s)

Jumper (J1): Not installed

Jumper (J2): Installed

Jumper (J1): Installed

Jumper (J2): Installed

J1

J2

J1

J2

J1

J2

No jumper

Circuit open

Jumper installed

Circuit closed

Jumper stored

Temperature output (Tout): T = voltage (V)

Velocity output (Vout): V = voltage (V)

Temperature output (Tout): T = current (mA)

Velocity output (Vout): V = current (mA)

Temperature output (Tout): T = voltage (V)

Velocity output (Vout): V = current (mA)

Temperature output (Tout): T = current (mA)

Velocity output (Vout): V = voltage (V)

V       mA

V       mA

V       mA

V       mA

NC

COM

NO

Tout

Vout

24 V

GND

Push button

T

V

J1

J2

sw. p.

hyst

V   mA

IN-GE-AVDTXXX-01 03/20