Page 36
PSL 5.0 Pump Station Level Controller
POWER INPUT OPTION
9-32VDC
PSL 5.0 Level Monitors may be ordered factory-configured for 9-32VDC power input.
QUICK BENCH TEST:
Connect Sensor as shown below, then Power. When properly connected figures will show on the large
LCD display. Test operation of the PSL 5.0 by holding the sensor steadily and aiming at a flat, stable
target 16 to 48" (400 to 1200 mm) away from the end of the sensor. Allow a few seconds for the PSL
5.0 to lock onto the target before displaying its distance. The PSL 5.0 will now display Range in ft or cm
(factory calibration).
CONNECTIONS:
POWER INPUT: Connect 9-32VDC/0.5 Amps to the + and - terminals. The Power Input GND must be
connected to the nearest Ground pole. A 1 amp fuse in line is recommended.
NO
C
NC
NO
C
NC
–
+
4-20mA
RLY2
RLY1
DC
GND
GND
USB HARNESS
CONNECTOR
DATA LOGGER OPTION
PRESSURE
SENSOR
DC
+ –
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
RLY3
RLY4
RLY5
RLY6
RELAYS
+ – + –
CORE
WHT
SHLD
GRN
SRC SNK
PZ
SENSOR