background image

 

Page 15 

PTFM 1.0 Portable Transit Time Flow Meter 

 

CALIBRATION 

 
Press the 

 to   

Calibration

   and 

 to enter. Use 

 or 

 to position 

 

before each menu item and 

 to enter. When settings are completed press 

 to 

store and return to the   

Calibration

   menu. 

 

*20mA at

   

 Press 

 then 

 or 

 to change the numbers and decimal point. 

Use this menu to set the corresponding flow rate that will be 
represented by 20mA analog output. If maximum flow is 
unknown, enter an estimated flow rate and observe actual flow to 
determine the correct maximum value. Any velocity or flow rate 
up to +40 ft/sec (12.2 m/sec) may be selected. 

 

*4mA at

    

Press 

 or 

 to set the flow rate corresponding to 4mA analog 

output. This setting may be left at zero flow (or velocity or can 
be raised to any value less than the 20mA setting, or lowered to 
any velocity or corresponding flow rate down to -40 ft/sec (-12.2 
m/sec). 

 

Min Flow

 

Flow rates below this setting will be displayed as zero flow. 

 

Damping

    

Increase damping to stabilize readings under turbulent flow 
conditions. Decrease for fast response to small changes in flow. 
Damping is shown in percentage (maximum is 99%). Factory 
default is 20%. 

 
 
Press 

 from the   

Units/Mode  

 display to return to  

Menu Selections

 
*

Note

   4-20mA circuitry is only powered by the AC power module. 

 

To conserve power this output is not active in battery power mode. 

 

 

 

 

 

 

--Calibration-------

20mA at

2500.0 USG/m

}

4mA at

0.000 USG/m

Min Flow

2.262 USG/m

5

Damping

%

Summary of Contents for A.1.2 Series

Page 1: ...www greyline com USER S GUIDE Installation Operation Instructions Portable Transit Time Flow Meter Model PTFM 1 0 Manual Series A 1 2 ...

Page 2: ...Page 2 Note This page has been left blank intentionally ...

Page 3: ...ND ANSWERS 26 APPLICATIONS HOTLINE 28 PRODUCT RETURN PROCEDURE 29 FLOW METER DATA SHEET 30 APPENDIX A CONVERSION TABLE 34 PIPE CHARTS 35 APPENDIX C Liquid Speed of Sound 39 IMPORTANT NOTE This instrument is manufactured and calibrated to meet product specifications Please read this manual carefully before installation and operation Any unauthorized repairs or modifications may result in a suspensi...

Page 4: ...ally when the battery is fully discharged Full charge requires approximately 6 hours charging Sleep mode extends battery life for long term data logging Maximum log time is 18 days at 5 minute sample rate CONNECTIONS TRANSDUCERS Use type SE16B supplied with 12 ft 4 m coaxial cables and BNC connectors Set of optional PTXC1 50 ft 15 m transducer cables available 4 20mA Active only when powered by AC...

Page 5: ... Set Pipe material ABS Set Lining None Set Crossings 4 Press to view Signal Strength at bottom of menu Press twice to exit Setup and return to main display From main display press to view Status menu Apply coupling compound to the face of transducers and press together as indicated in the illustration below The Status menu should indicate Noise low and a high Signal Strength 75 100 COUPLING COMPOU...

Page 6: ...Page 6 PTFM 1 0 Portable Transit Time Flow Meter TRANSDUCER INSTALLATION TRANSDUCER TRANSDUCER SEPARATION DISTANCE Shown in display after pipe dimensions are entered Setup ...

Page 7: ...ystem Arrows show the four directions to leave a menu box Pressing a corresponding keypad arrow will move to the next item in the direction shown Move the cursor underline under numerals and increase or decrease numerals with the and keys To store calibration values permanently press the SLEEP BACK LIGHT ON OFF ...

Page 8: ... 1 0 25 0 Transit Time 03 1 14 Logger 1 S Relays 0 Analog Out 1 Password Password 0000 Menu Selections Units Mode Set up Calibration Data Logging Special Functions Simulation Configuration Sleep Mode Logging Stopped Battery 100 Charger Off Sleep Mode Charging USG m Tot 20130 8USG 0 000 Message Data log Logging Log Used 0 Battery 50 Charger Off Sensor Good 24 hr log Date 201 Jul 17 2 Total 135470 0...

Page 9: ... waiting Press Battery 0 Battery 100 1 2 3 4 5 Battery charging Charger connected Data logging off 1 2 Data logging on 1 2 3 4 USB file download File download completed Download Error 1 2 3 PTFM Echo OK PTFM No Echo Empty Pipe PTFM No Sensors Attatched Wrong Settings ...

Page 10: ... The Message icon will appear on the RUN display if error messages are being generated by the instrument Press to return to the main display STATUS Press from the RUN display to view instrument status Velocity Displayed in ft sec or m sec Signal Strength Displays percentage of signal being received by the ultrasonic sensor USG m Tot 20130 8USG 0 000 Message Data log Logging Battery 50 Charger Off ...

Page 11: ...access to the Calibration menu From the Run display press the key to get to Password Factory default password is 0000 and if it has not been changed press the to proceed to the Menu Selections screen If a password is required press to place the cursor under the first digit and or to set the number then to the second digit etc Press or to proceed to the Menu Selections screen A new password can be ...

Page 12: ...and then the or to select your units of measurement Press the to store your selection Press the key to move the symbol to each subsequent menu item and the to save your selections Note the volume selection bbl denotes U S oil barrel Press or to return to the Menu Selections screen Units Mode Mode Flow Linear in Volume USG Time min Temperature C Units Mode Mode Flow Linear in ft m mm Units Mode Mod...

Page 13: ...pe where the transducer is mounted Refer to the Pipe Charts Appendix in this manual for outside diameter of common pipe types and sizes Pipe Wall Enter wall thickness Refer to the Pipe Charts Appendix in this manual for thickness of common pipe materials and sizes Pipe Vel When pipe Other Enter pipe material speed of sound consult factory Pipe Select pipe material Lining Thick When Lining Enter li...

Page 14: ...nd full pipe select Yes to force readings to zero Sens Space Displays the calculated sensor spacing Velocity Displays the measured velocity Signal Strength Displays magnitude of signal being received by the ultrasonic transducer Press from the Units Mode display to return to Menu Selections NOTE Transducer separation distance is automatically calculated by the instrument and will be displayed in t...

Page 15: ...s or to set the flow rate corresponding to 4mA analog output This setting may be left at zero flow or velocity or can be raised to any value less than the 20mA setting or lowered to any velocity or corresponding flow rate down to 40 ft sec 12 2 m sec Min Flow Flow rates below this setting will be displayed as zero flow Damping Increase damping to stabilize readings under turbulent flow conditions ...

Page 16: ... enables the logging wrap function In Wrapping mode the oldest data will be overwritten by the newest If Wrapping is not enabled the logger will stop when its memory becomes full Log Select Delete and then Start to apply any changes that have been made to the logger Interval or Mode The current log file will be erased from memory and a new log file will start RETRIEVE LOG FILE Install Greyline Log...

Page 17: ...to the calibration certificate supplied with your instrument Restore Defaults Select Yes and press to erase all user settings and return the instrument to factory default settings New Password Select any number from 0000 to 9999 and press Default setting of 0000 will allow direct access to the calibration menus Setting of any password greater than 0000 will require the password to be entered to ac...

Page 18: ...ts between minimum and maximum set Test to Actual and then enter for the flow measurement The analog output will respond to the simulated value SLEEP MODE Logging in sleep mode requires a minimum sample time of 30 seconds Selecting sleep mode for 10 second sampling rate is indicated by a flashing display BACKLIGHT Three levels of backlight are selectable to conserve power CHARGING A flashing batte...

Page 19: ... avoid concentrations of gas at the top of the pipe or solids at the bottom VELOCITY INCREASING DEVICES Generally the transducers must be mounted away from flow disturbances such as valves pumps orifice plates venturis or pipe inlets and discharges which tend to increase flow velocity Velocity increasing devices often cause cavitation or rapid release of gas bubbles and readings both up and downst...

Page 20: ...It includes recommended coupling compound in a plastic applicator and a stainless steel mounting bracket with adjustable pipe straps Use the Alignment Bar included to align transducer brackets for V and W mode mounting END VIEW ADJUSTABLE STAINLESS STEEL PIPE CLAMP PIPE TRANSDUCER TRANSDUCER MOUNTING BRACKET Mount the PC16 Mounting Bracket as illustrated on pipes 0 6 15 mm OD or larger Stainless s...

Page 21: ...aration distance with a ruler or tape measure Separation distance is automatically calculated by the PTFM 1 0 based on parameters entered in the Set up menu Sens Space is displayed on the Setup menu TRANSDUCER TRANSDUCER SEPARATION DISTANCE TRANSDUCER TRANSDUCER SEPARATION DISTANCE ...

Page 22: ...coupling compound 4 to the colored face of the transducer A bead similar to toothpaste on a toothbrush is ideal Do not overtighten crush the transducer The transducer must be fixed securely to the pipe with coupling material between the transducer face and the pipe Transducer installation with excessive coupling compound can result in gaps or voids in the coupling and cause errors or loss of signa...

Page 23: ...Page 23 PTFM 1 0 Portable Transit Time Flow Meter SENSOR MOUNTING COUPLING RECOMMENDATIONS BAD GOOD ...

Page 24: ...nect transducer cables ensuring that cable plugs are properly inserted into terminals and tightened METER READING LOWER THAN EXPECTED Calibration Error Review calibration menu Pipe dimensions and fluid selection fluid velocity Lower flow rate than expected Investigate pump valves Compare velocity with alternate instrument Erratic measurement set damping to 0 to check due to electrical noise or poo...

Page 25: ... velocity Higher flow rate than expected Investigate pump valves Compare velocity with alternate instrument Erratic measurement set damping to 0 to check due to electrical noise or poor signal quality Try adjusting transducer spacing 10 and contact Greyline for further assistance Pipe not Full Verify pipe is full by mounting transducers at top of pipe and check echo icon No echo if pipe is not ful...

Page 26: ... corrosion oxidation on the inside of the pipe may prevent the Transit Time signal from penetrating into the flow If the pipe cannot be cleaned a spool piece PVC recommended should be installed for transducer mounting What effect do pipe liners have on the flow meter The air gap between loose insertion liners and the pipe wall prevent the Transit Time signal from entering the flow Better results c...

Page 27: ...on A low signal strength 10 will cause the PTFM to be more susceptible to environmental noise and may indicate a problem with the installation or other qualitative issues Does the PTFM 1 0 require periodic recalibration PTFM 1 0 calibration does not normally drift over time Greyline offers a calibration service to verify instrument accuracy Can the internal batteries be replaced The built in recha...

Page 28: ...our Sales Representative write to Greyline or phone the Applications Hotline below United States Tel 315 788 9500 Fax 315 764 0419 Canada Tel 613 938 8956 Fax 613 938 4857 Toll Free 888 473 9546 Email info greyline com Web Site www greyline com Greyline Instruments Inc Canada USA 16456 Sixsmith Drive 105 Water Street Long Sault Ont K0C 1P0 Massena NY 13662 ...

Page 29: ... Clean the Sensor Product Important unclean products will not be serviced and will be returned to the sender at their expense 1 Rinse sensor and cable to remove debris 2 If the sensor has been exposed to sewage immerse both sensor and cable in a solution of 1 part household bleach Javex Clorox etc to 20 parts water for 5 minutes Important do not immerse plug end of sensor cable 3 Dry with paper to...

Page 30: ...ine flow meters in similar applications and to provide advice and recommendations to you Thank you for your cooperation Contact Information Contact Title Dept Company Address Address Tel Fax Email Mobile Service Conditions Pipe Run Vertical Horizontal Pipe Full Yes No Fluid Type of Solids Nominal Pipe Size and Schedule Pipe Outside Diameter Wall Thickness Pipe Material Liner Material Liner Thickne...

Page 31: ... along with a copy of your invoice This warranty does not cover damages due to improper installation or handling acts of nature or unauthorized service Modifications to or tampering with any part shall void this warranty This warranty does not cover any equipment used in connection with the product or consequential damages due to a defect in the product All implied warranties are limited to the du...

Page 32: ...d or formatted flow reports including total average minimum maximum and times of occurrence PC Software Greyline Logger for Windows 98 or higher Retrieves displays and saves data log files Electronics Operating Temperature 10 to 140 F 23 to 60 C Electronics Enclosure Portable ABS enclosure Carry Case Rated IP67 with protective molded foam insert Accuracy 1 of reading or 0 1 ft sec 0 03 m sec which...

Page 33: ...0 to 300 F 40 to 150 C Operating Frequency 1 28 MHz Transducer Cable 12 ft 4 m with BNC connectors and seal jackets Optional 50 ft 15 m with BNC connectors and seal jackets Submersion Rating Withstands accidental submersion pressure up to 10 psi 0 7 Bar SE16B TRANSDUCER DIMENSIONS 54 mm 2 1 32 mm 1 25 56 mm 2 2 SIDE VIEW 30 mm 1 2 END VIEW ...

Page 34: ...S GALLONS IMPERIAL GALS 0 8327 US GALLONS LITRES 3 785 US GALLONS CUBIC METERS 0 003785 LITRES SEC GPM 15 85 LITRES CUBIC METERS 0 001 BARRELS US GALLONS 42 BARRELS IMPERIAL GALS 34 9726 BARRELS LITRES 158 9886 INCHES MM 25 4 DEGREES F DEGREES C F 32 x 0 556 POUNDS KILOGRAMS 0 453 PSI BAR 0 0676 FOOT METER 0 0929 Note BARRELS are U S oil barrels ...

Page 35: ...32 000 31 250 375 31 000 500 31 376 312 31 000 500 30 750 625 34 34 000 33 250 375 33 000 500 33 376 312 33 000 500 32 750 625 36 36 000 35 250 375 35 000 500 35 376 312 35 000 500 34 750 625 42 42 000 41 250 375 41 000 500 41 000 500 40 750 625 Ductile Iron Pipe Standard Classes Size OUTSIDE Class Class Class Class Class Class Class CEMENT LINING INCH DIA 50 51 52 53 54 55 56 S TD DOUBLE INCH WAL...

Page 36: ... 21 564 218 24 24 000 23 563 218 23 500 250 Pipe Pipe Schedule 60 Schedule 80 Schedule 100 Schedule 120 Schedule 140 Schedule 160 Size O D I D WALL I D WALL I D WALL I D WALL I D WALL I D WALL 840 546 147 466 187 1 050 742 154 614 218 1 1 315 957 179 815 250 1 1 660 1 278 191 1 160 250 1 1 900 1 500 200 1 338 281 2 2 375 1 939 218 1 689 343 2 2 875 2 323 276 2 125 375 3 3 500 2 900 300 2 624 438 3...

Page 37: ... 10 16 11 40 0 68 10 04 12 13 20 0 54 12 12 13 20 0 62 11 96 13 50 0 68 12 14 13 50 0 75 12 00 14 15 30 0 57 14 16 15 30 0 66 13 98 15 65 0 74 14 17 15 65 0 82 14 01 16 17 40 0 60 16 20 17 40 0 70 16 00 17 80 0 80 16 20 17 80 0 89 16 02 18 19 50 0 64 18 22 19 50 0 75 18 00 19 92 0 87 18 18 19 92 0 96 18 00 20 21 60 0 67 20 26 21 60 0 80 20 00 22 06 0 92 20 22 22 06 1 03 20 00 24 25 80 0 76 24 28 2...

Page 38: ...58 2 375 2 062 0 157 2 2 625 2 435 0 095 2 625 2 465 0 080 2 625 2 495 0 065 2 875 2 500 0 188 2 500 2 400 0 050 3 3 125 2 907 0 109 3 125 2 945 0 090 3 125 2 981 0 072 3 500 3 062 0 219 3 000 2 900 0 050 3 3 625 3 385 0 120 3 625 3 425 0 100 3 625 3 459 0 083 4 000 3 500 0 250 4 4 125 3 857 0 134 4 125 3 905 0 110 4 125 3 935 0 095 4 500 3 935 0 095 4 000 4 000 0 250 4 5 000 4 500 0 250 5 5 125 4...

Page 39: ... Ammonia 35 NH3 0 771 1729 6 68 Amorphous Polyolefin 0 98 962 6 t Amyl alcohol C5H12O 0 81 1204 Aminobenzene 41 C6H5NO2 1 022 1639 4 0 Aniline 41 C6H5NO2 1 022 1639 4 0 Argon 45 Ar 1 400 188ºC 853 Azine C6H5N 0 982 1415 4 1 Benzene 29 40 41 C6H6 0 879 1306 4 65 Benzol 29 40 41 C6H6 0 879 1306 4 65 Bromine 21 Br2 2 928 889 3 0 Bromo benzene 46 C6H5Br 1 522 1170 1 Bromo butane 46 C4H9Br 1 276 20ºC 1...

Page 40: ...amylamine C10H23N 1256 3 9 1 2 Dibromo ethane 47 C2H4Br2 2 18 995 trans 1 2 Dibromoethene 47 C2H2Br2 2 231 935 Dibutyl phthalate C8H22O4 1408 Dichloro t butyl alcohol C4H8Cl2O 1304 3 8 2 3 Dichlorodioxane C2H6Cl2O2 1391 3 7 Dichlorodifluoromethane 3 Freon 12 CCl2F2 1 516 40ºC 774 1 4 24 1 2 Dichloro ethane 47 C2H4Cl2 1 253 1193 cis 1 2 Dichloro Ethene 3 47 C2H2Cl2 1 284 1061 trans 1 2 Dichloro eth...

Page 41: ... Ethyl acetate 33 C4H8O2 0 901 1085 4 4 Ethyl alcohol C2H6O 0 789 1207 4 0 Ethyl benzene 46 C8H10 0 867 20ºC 1338 Ethyl bromide 46 C2H5Br 1 461 20ºC 900 Ethyliodide 46 C2H5I 1 950 20ºC 876 Ether C4H10O 0 713 985 4 87 Ethyl ether C4H10O 0 713 985 4 87 Ethylene bromide 47 C2H4Br2 2 18 995 Ethylene chloride 47 C2H4Cl2 1 253 1193 Ethylene glycol C2H6O2 1 113 1658 2 1 50 Glycol 50 H2O 1578 d Fenochone ...

Page 42: ...C7H8O 1 034 20ºC 1500 Iodo benzene 46 C6H5I 1 823 1114 Iodo ethane 46 C2H5I 1 950 20ºC 876 Iodo methane CH3I 2 28 20ºC 978 Isobutyl acetate 22 C6H12O 1180 4 85 Isobutanol C4H10O 0 81 20ºC 1212 Iso Butane 1219 8 Isopentane 36 C5H12 0 62 20ºC 980 4 8 Isopropanol 46 C3H8O 0 785 20ºC 1170 Isopropyl alcohol 46 C3H8O 0 785 20ºC 1170 Kerosene 0 81 1324 3 6 Ketohexamethylene C6H10O 0 948 1423 4 0 Lithium ...

Page 43: ...3 1172 4 14 n Octane 29 C8H18 0 704 20ºC 1212 5 3 50 1 Octene 27 C8H16 0 723 20ºC 1175 5 4 10 Oil of Camphor Sassafrassy 1390 3 8 Oil Car SAE 20a 30 1 74 870 Oil Castor C11H10O10 0 969 1477 3 6 Oil Diesel 0 80 1250 Oil Fuel AA gravity 0 99 1485 3 7 Oil Lubricating X200 1530 5019 9 Oil Olive 0 912 1431 2 75 Oil Peanut 0 936 1458 Oil Sperm 0 88 1440 Oil 6 1509 2 2 Oxydiethanol C4H10O3 1 116 1586 2 4...

Page 44: ...O 0 791 1174 4 5 Propene 17 18 35 C3H6 0 563 13ºC 963 6 32 n Propyl acetate 22 C5H10O2 1280 2ºC 4 63 n Propyl alcohol C3H8O 0 78 20ºC 1222 Propylchloride 47 C3H7Cl 0 892 1058 Propylene 17 18 35 C3H6 0 563 13ºC 963 6 32 Pyridine C6H5N 0 982 1415 4 1 Refrigerant 11 3 4 CCl3F 1 49 828 3 3 56 Refrigerant 12 3 CCl2F2 1 516 40ºC 774 1 4 24 Refrigerant 14 14 CF4 1 75 150ºC 875 24 6 61 Refrigerant 21 3 CH...

Page 45: ...20ºC 918 1 1 1 Trichloro ethane 47 C2H3Cl3 1 33 985 Trichloro ethene 47 C2HCl3 1 464 1028 Trichloro fluoromethane 3 Freon 11 CCl3F 1 49 828 3 3 56 Trichloro methane 47 CHCl3 1 489 979 3 4 1 1 2 Trichloro 1 2 2 Trifluoro Ethane CCl2F CClF2 1 563 783 7 Triethyl amine 33 C6H15N 0 726 1123 4 47 Triethylene glycol C6H14O4 1 123 1608 3 8 1 1 1 Trifluoro 2 Chloro 2 Bromo Ethane C2HClBrF3 1 869 693 1 2 2 ...

Reviews: