Sure-Aire™ Flow Monitoring System
9
®
Outlet Area
Press “Edit“ to change the stack outlet area. Press “Inc“
or “Dec“ to increase or decrease the area, respectively.
Then press “Enter“ to store the value.
• 0-10 Ft²
Top and Bottom Views
Top View:
Press “Edit“ to change Main Display Value.
Press “Prev“ or “Next“ to adjust what reading displays
on the Home screen, then press “Enter“ to store the
value.
• Flow (default top display)
• Pressure
• Temperature
• Air density
• Output signal (default bottom display)
• Velocity
• None
Bottom View:
Press “Edit” to change Secondary
Display. Press “Prev” or “Next” to adjust, then press
“Enter” to store the value.
Temperature Compensation
Press “Edit“ to change Temperature Compensation.
Press “Prev“ or “Next“ to adjust, then press “Enter“ to
store the value.
• Yes (default)
• No
Note: If temperature compensation is set to “No“, the
air density will be a function of standard temperature
(70°F /
21°C
).
Output Signal
Output Signal:
Press “Edit“ to change Output Signal
type. Press “Prev“ or “Next“ to adjust, then press
“Enter“ to store the value.
• 4-20 mA (default)
• 2-10 VDC
Linearize By:
Press “Edit“ to change the linearization
settings. The electronics will linearize the transmitter
output with respect to this setting.
• Flow (default)
• Pressure
Note: The maximum measurable flow rate will
automatically calculate based on the electronics
settings. The maximum flow rate is displayed on the
screen.
Greenheck
Sure-Aire V 2.00
Outlet Area: 1.00Ft²
For Outlet Velocity
Exit
Prev
Next
Edit /
Enter
Greenheck
Sure-Aire V 2.00
Top View: Flow
Bottom View: Velocity
Exit
Prev
Next
Edit /
Enter
Greenheck
Sure-Aire V 2.00
Temperature Comp:
No
Exit
Prev
Next
Edit /
Enter
Greenheck
Sure-Aire V 2.00
Output Signal: 2-10V
Linearize By: Flow
Max Flow = 1400 CFM
Exit
Prev
Next
Edit /
Enter
WARNING
Due to load resistance change from product to
product, it may be necessary to recalibrate the
4-20 mA electronics. See 4-20 mA transducer
calibration procedure.