Sure-Aire™ Flow Monitoring System
10
®
Display Setting Options and Parameter Setup (continued)
Protocol and Baud Rate
Protocol:
Press “Edit“ to change the current network
protocol. Press “Prev“ or “Next“ to adjust, then press
“Enter“ to store the value.
• BACnet (default)
• Modbus
Baud Rate:
Press “Edit“ to change the protocol baud
rate. Press “Prev” or “Next” to adjust, then press “Enter”
to store the value.
Baud Rate Options (Modbus):
• 2400
• 4800
• 9600
• 19200
• 38400
• 57600
• 115200
Baud Rate Options (BACnet):
• 9600
• 19200
• 38400
• 57600
• 76800
• 115200
Network Address
Press “Edit“ to adjust the network address, then press
“Enter“ to store the value.
Network Address Options (Modbus):
• 1 – 255
Network Address Options (BACnet):
• 0 – 127
Note: The protocol and baud rate must be set before
the network address can be modified.
Device Instance Number (BACnet only):
The instance number is an unsigned decimal number
that can range from 0 to 4,194,302. Every device on
a BACnet network gets an instance number, and two
devices must not have the same number.
Press “Edit” to adjust the Device Instance Number, then
press “Enter” to store the value.
• 0 - 4,194,302
Transmitter Min/Max Value
Transmitter Min Value:
Press “Edit” to change
Transmitter Min Value. Press “Inc” or “Dec” to adjust,
then press “Enter” to store the value.
Note: See Transmitter Calibration Section.
Transmitter Max Value:
Press “Edit” to change
Transmitter Max Value. Press “Inc” or “Dec” to adjust,
then press “Enter” to store the value.
Note: See Transmitter Calibration Section.