Microprocessor Controller for MUA
35
®
Appendix E: Points List
Unit Status Word Table (IV-11)
Bit
Unit_Status_Word
0
Off/Standby
1
Unoccupied Start
2
Occupied Start
3
Opening Dampers
4
Dampers Open
5
Fan Start Delay
6
Exhaust Fan On
7
Supply Fan On
8
System On
9
Soft Shutdown
10
System Disabled
11
Remote Off
12
System Shutdown Alarm
16
Unit Off Flow Active
17
Fans Only
18
Economizing
20
Cooling
21
Heating
28
Morning Warm Up/Cool Down Active
29
Winter Ramp Active
30
Occupancy Override
31
Overrides Active
Device Alarm Word Table
Bit
Device_Alarm_Word -Ext
0
Supply Fan Alarm
1
Exhaust Fan Alarm
2
Drain Pan Alarm
3
Filter Alarm
4
Greentrol OAD AFMS Alarm
5
Outside Air Temp Sensor Alarm
6
Space CO2 Sensor Alarm
7
Supply Air Temp Sensor Alarm
8
Space Temperature Sensor Alarm
9
Supply Temp Low Limit Alarm
10
Supply Temp High Limit Alarm
11
Supply High Duct Static Alarm
12
Supply Duct Static Sensor Alarm
13
Space Static Pressure Sensor Alarm
14
Space High Static Alarm
15
Return CO2 Sensor Alarm
17
Shutdown Input Alarm
Digital Output Word Table
Bit
Digital_Output_Word - Ext
0
Supply Fan Start
1
Exhaust Fan Start
2
Exhaust Relief Enable
3
Compressor 1 Start
4
Compressor 2 Start
5
Condenser Fan Start
7
Furnace 1 Start
8
Furnace 1 Stage 2 Start
9
Furnace 2 Start
10
Furnace 2 Stage 2 Start
11
Furnace 3 Start
13
Damper Actuator Power Enable
14
Direct Gas Start
15
Electric Heat Start
16
Evaporative Cooling Valve Enable
17
Evaporative Cooling Pump Enable
Device Offline Word Table
Bit
Device_Offline_Word - Ext
0
Space TStat 1 Offline
1
Space TStat 2 Offline
2
Space TStat 3 Offline
3
Space TStat 4 Offline
4
IG Furnace Controller 1 Offline
5
IG Furnace Controller 2 Offline
6
Cooling Controller Offline
7
Greentrol Outside Air Offline
8
BMS Offline Alarm
9
Permanent Memory - Too Many Writes