Round and Oval Duct Breakaway 
Connections

Factory furnished duct collars, type R and O, are also 
considered breakaway 

(see Figure 12)

.

Round or flat oval ducts connected to Type R or O damper 
collars shall be attached with #10 (19 mm) sheet metal 
screws as follows:
  •  Ducts up to 22 in. (558 mm) wide (or dia.) and less shall 

have three screws.

  •  Ducts larger than 22 in. (558 mm) wide (or dia.) up to 

and including 36 in. (914 mm) wide (or dia.) shall have 
five screws.

Wall or Floo

r

Sleeve

Duct

Damper

Type B

Wall or Floo

r

Sleeve

Duct

Damper

Type R, O

Type R and O
factory furnished
duct collars qualify
as breakaway
connections.

Figure 12:

 Type R and O Transition

Plain “S” Slip           Hemmed “S”

Slip                 Double “S”

Slip

Inside Slip Joint             Standing “S”               Standing “S” (Alt.)

 Standing “S” (Alt.)                Standing “S”                   Standing “S”

                                           (Bar Reinforced)             (Angle Reinforced)

Figure 10

Drive Slip Joint

Figure 11

Approved Breakaway Connections

All breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive 
manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymerics, Grey Pookie, 
Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.

Transverse Joints

The transverse joints shown below are approved as breakaway connections.
  •  A maximum of two #10 (19 mm) sheet metal screws on each side and on the bottom may be used. The screws 

should be located in the center of the slip pocket and penetrate both sides of the slip pocket.

  •  Dampers up to 20 in. (508 mm) high may use transverse joints on the top and bottom and Drive Slip joints (

see 

Figure 11

) on the sides.

Out of Wall Fire and Combination Fire Smoke Dampers

8

®

Summary of Contents for ODFD Series

Page 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Page 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Page 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Page 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Page 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Page 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Page 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Page 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Page 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Page 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Page 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Page 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Reviews: