4

ec1: outdoor temperature reference

The economizer controller positions the mixing box 
dampers to achieve 55° F mixed temperature when 
the thermostat calls for cooling AND the outdoor air 
temperature is below the economizer 
setpoint. If outdoor air temperature is 
between 55° F and the economizer 
setpoint, the dampers will modulate 
to the 100% outdoor air position. 
Above the setpoint, the outdoor 
air damper is held at the minimum 
position. The setpoint is field 
adjustable and the outdoor air sensor 
is factory mounted.

The economizer controls package enables free cooling using outdoor air. All EC options include a modulating 
actuator for controlling outdoor and return air dampers, and a minimum outdoor air positioner. During a call for 
heating the economizer is locked out and the outdoor air damper holds at the minimum position.

MB1: Minimum outdoor air Positioner

The MB1 option includes a modulating 
actuator and potentiometer that control 
the outdoor air and return air damper 
positions. When the unit is energized, 
the dampers will travel to the position 
corresponding to the potentiometer 
setting, providing the desired amount of outdoor air. 
When the unit is powered off, the outdoor air damper 
closes to prevent backdrafting. To adjust the damper 
settings, simply dial the potentiometer (shown above) to 
desired operating position of the outdoor air damper.

MB2: 2-10 Volt external signal

The MB2 option includes a modulating actuator that is 
controlled by an external 2-10 volt signal. This option 
is appropriate for applications that call for a building 

automation system that will control the mixing box 
dampers.

MB3: 4-20 ma external signal

The MB3 option includes a modulating actuator that is 
controlled by an external 4-20 mA signal. Like the MB2 
option, this option is appropriate for applications that 
call for a building automation system that will control the 
mixing box dampers.

MB4: Manual Quadrant

The MB4 option consists of a manual 
quadrant that enables the outdoor air 
and return air dampers to be secured 
into a single position. The primary 
function is to introduce the specified minimum outdoor 
air volume during operation. Dampers remain in the 
same position when the unit is powered off.

In addition to the EC options described above, Greenheck offers four MB mixing box control options for 
applications where a factory provided economizer package is not desired. 

The mixing box (shown at right) includes 
outdoor air and return air low leakage 
control dampers in a face and bypass 
configuration. Either two inch pleated 
or aluminum mesh filters are available 
within the mixing box section. Double wall 
construction is optional.

A mixing box control option must be 
specified for every IGX-HV unit. Greenheck 
offers eight mixing box control options 
that accommodate a wide variety of 
applications. The four EC and four MB 
options are described below. Specify only 
one control box option per unit. 

ec2: outdoor enthalpy reference

Same as EC1, except economizer setpoint is based on 
outdoor air 

enthalpy

.

ec3: airstream temperature reference

The economizer controller compares the temperatures 
of the outdoor air and return air when the thermostat 
calls for cooling. The mixing box dampers are then 

positioned to maximize the 
airflow of the cooler airstream. 
When outdoor air temperature 
is sufficiently cool, the mixing 
box dampers will modulate to 
provide 55° F mixed air. The 
outdoor air sensor is factory 
mounted. The return air sensors 
are field installed.

ec4: airstream enthalpy reference

Same as EC3, except airstream 

enthalpy

 values are 

compared.

MIXInG BoX controLs

Mixing Box controls with economizer cooling

Mixing Box controls (no economizer)

Supply

Return Air

Outdoor Air

Summary of Contents for IGX-HV

Page 1: ...Modular Heating Ventilating Unit Model IGX HV Indirect Gas Fired Heating Evaporative Chilled Water DX Cooling October 2008...

Page 2: ...s steel heat exchanger Direct spark ignition system Easy access burner controls ETL listed to ANSI Standard Z83 8 Solid state automatic ignition module Vibration Isolators The entire fan and motor ass...

Page 3: ...cooling The Intelligent Fan feature energizes the fan continuously during occupied mode and intermittently with a call for heating or cooling in unoccupied mode TC3 2 Stage Heating 2 Stage Cooling TC...

Page 4: ...Like the MB2 option this option is appropriate for applications that call for a building automation system that will control the mixing box dampers MB4 Manual Quadrant The MB4 option consists of a man...

Page 5: ...ng section includes the cooling coil stainless steel drain pan and insulated double wall construction Drain and coil connections are stubbed through the wall for convenience For proper coil sizing use...

Page 6: ...1 3 000 RPM 1014 1097 1172 1244 1315 1386 250 BHP 1 22 1 39 1 55 1 72 1 88 2 05 MODEL CFM TOTAL STATIC PRESSURE in inches of WG Maximum Furnace Size Input MBH 0 50 0 75 1 00 1 25 1 50 1 75 IGX HV 112...

Page 7: ...mist eliminating intake hood is standard on outdoor IGX HV models The mist eliminating intake hood provides a double layer of protection against moisture entering the mixing box section Propane Gas C...

Page 8: ...d for a minimum of 150 of driven horsepower Pulleys shall be cast and have machined surfaces 10 horsepower and less shall be supplied with an adjustable drive pulley Electrical All internal electrical...

Reviews: