background image

Energy Core Ventilator

18

®

Factory Set Points

Variable frequency drives (VFDs) for the blowers are 
factory setup to operate in one of the three following 
modes:

• Modulating:

 0-10 VDC signal wired in the field by 

others varies the speed of the blower between the 
min and max Hz (Max. 90 Hz)

• Multi-speed:

 Digital contact closures by others 

command the VFD to run at multiple speed settings: 

  Open - Drive runs at 100%

 

  SC to S4 - Drive runs at 67%

 

  SC to S5 - Drive runs at 50%

• CO

2

 Sensor:

 

  

Set Point Control:

 A carbon dioxide sensor is 

provided from the factory for field mounting OR 
unit mounting in the space(s) being served by the 
energy recovery unit. The CO

2

 sensors are wired 

to the unit VFD’s with two preset speeds of 700 
PPM or less CO

2

 = 50% fan speed and 800 PPM 

or greater CO

2

 = 100% fan speed.

 

   Proportional  Control:

 A carbon dioxide sensor 

is provided from the factory for field mounting OR 
unit mounting in the space(s) being served by the 
energy recovery unit. The CO

2

 sensors are wired 

to the unit VFD’s with default factory settings 
of 500 PPM or less CO

2

 = 50% fan speed and 

1000 PPM or greater CO

2

 = 100% fan speed. 

Modulation of VFD occurs proportional to CO

2

 

between 500 and 1000 PPM.

The terminal locations for modulating and multi-speed 
are shown on the previous page. Most of the set points 
in the VFDs are Yaskawa factory defaults. However, 
a few set points are changed at Greenheck and are 
shown in the tables. These settings are based on the 
VFD mode selected.

Change Set Points

To gain access to change set points on the V1000 and 
J1000 drives, parameter A1-01 needs to be set at “2”. 
To prevent access or tampering with drive settings on 
either drive, change parameter A1-01 to “0”.

•  Drive Operation
 

 

SC to S1 contact for On/Off

 

   A1 (0-10 VDC) referenced to AC.  

Can use +15 VDC from +V.

Resetting the V1000 drive to factory 
defaults

To reset the V1000 drive back to Greenheck factory 
defaults, go to parameter A1-01 and set it to “2”. Then 
go to A1-03 and change it to “1110” and press enter. 
The drive is now reset to the settings programmed at 
Greenheck. This option is not available on the J1000.

Variable Frequency Drives

Optional factory installed, wired, and programmed 
variable frequency drives (VFDs) may have been 
provided for modulating or multi-speed control of the 
blowers. One VFD, either Yaskawa model V1000 or 
J1000, is provided for each blower (supply air and 
exhaust). 
Refer to the tables in this section for factory settings 
and field wiring requirements. Refer to the unit control 
center for unit specific wiring diagram. When making 
adjustments outside of the factory set points, refer to 
Yaskawa VFD instruction manual, which can be found 
online at www.drives.com. 

MAMBMC

RP

H1

SC

HC

S7

S6

S5

S4

S3

S2

S1

MP

AC

AM

AC

+V

A2

A1

PC

P2

P1

IG

S-

S+

R-

R+

V1000

MAMBMC

AC

AM

AC

+V

A1

SC

S5

S4

S3

S2

S1

J1000

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC = 100%

0 VDC = 50%

A1 AC

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 100%

DRIVE SPEED = 67%

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)

DRIVE SPEED = 50%

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.

PARAMETER n01 CHANGE TO 1

PARAMETER n22 FOR NEW 40Hz SETTING

PARAMETER n21 FOR NEW 60Hz SETTING

PARAMETER n23 FOR NEW 30Hz SETTING

PARAMETER n01 CHANGE TO 0

USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

ERV

MAMBMC

RP

H1

SC

HC

S7

S6

S5

S4

S3

S2

S1

MP

AC

AM

AC

+V

A2

A1

PC

P2

P1

IG

S-

S+

R-

R+

V1000

MAMBMC

AC

AM

AC

+V

A1

SC

S5

S4

S3

S2

S1

J1000

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC = 100%

0 VDC = 50%

A1 AC

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 100%

DRIVE SPEED = 67%

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)

DRIVE SPEED = 50%

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.

PARAMETER n01 CHANGE TO 1

PARAMETER n22 FOR NEW 40Hz SETTING

PARAMETER n21 FOR NEW 60Hz SETTING

PARAMETER n23 FOR NEW 30Hz SETTING

PARAMETER n01 CHANGE TO 0

USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

ERV

MAMBMC

RP

H1

SC

HC

S7

S6

S5

S4

S3

S2

S1

MP

AC

AM

AC

+V

A2

A1

PC

P2

P1

IG

S-

S+

R-

R+

V1000

MAMBMC

AC

AM

AC

+V

A1

SC

S5

S4

S3

S2

S1

J1000

OPTION 1 - 0-10 VDC CONTROL

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

USER TO PROVIDE ISOLATION AS REQUIRED

FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.

WIRED TO A1 (+) AND AC (COMMON)

0-10 VDC CONTROL SIGNAL (BY OTHERS)

10 VDC = 100%

0 VDC = 50%

A1 AC

FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL

OPTION 2 - MULTI SPEED CONTROL

S5

S4

SC

NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 100%

DRIVE SPEED = 67%

S4 TO SC CONTACT CLOSED (BY OTHERS)

S5 TO SC CONTACT CLOSED (BY OTHERS)

DRIVE SPEED = 50%

TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.

PARAMETER n01 CHANGE TO 1

PARAMETER n22 FOR NEW 40Hz SETTING

PARAMETER n21 FOR NEW 60Hz SETTING

PARAMETER n23 FOR NEW 30Hz SETTING

PARAMETER n01 CHANGE TO 0

USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED

SEE VFD INSTALLATION MANUAL FOR MORE DETAIL

ERV

Summary of Contents for ECV Series

Page 1: ...plicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded...

Page 2: ...contactor in the air handler closes to start the unit Summer Operation Outdoor air is preconditioned temperature and moisture levels are decreased by the transfer of energy from the cooler drier retu...

Page 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Page 4: ...AIR INTAKE OUTDOOR AIR INTAKE A B C EXHAUST AIR DISCHARGE SUPPLY AIR DISCHARGE NON ELECTRICAL SIDE D G E F Top and Bottom Connections Top and End Connections OUTDOOR AIR INLET A B C EXHAUST AIR DISCH...

Page 5: ...Discharge End Recommended Minimum Recommended Minimum Weatherhood Yes Weatherhood No Weatherhood Yes Weatherhood No ECV 10 30 20 30 No Access Required 33 No Access Required 24 No Access Required ECV...

Page 6: ...r replacement and maintenance Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary Lifting WARNING All factory provided li...

Page 7: ...et the Unit Lift unit to a point directly above the curb and duct openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seat...

Page 8: ...52 x 16 6 Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute FPM at minimum airflow and up to 1600 fpm at maximum airflow Recommende...

Page 9: ...em Voltage Supply See voltage use range on the rating plate Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate...

Page 10: ...to switch Dirty filter light Economizer light Frost control light On Off Auto Switch Indictor Light Wiring Typical Control Center Components 1 Main Disconnect nonfusible lockable 2 Motor Starter Exhau...

Page 11: ...VG reference unit wiring diagram ST2 M1 WHITE T1 T3 SUPPLY FAN MOTOR 15 16 0 10VDC BLACK POT BLACK 2CBL M1 RED RED CLOSED 115 120V OPEN 208 230 277V M2 EXHAUST FAN MOTOR 17 18 0 10VDC POT BLACK RED RE...

Page 12: ...ature and enable the preheater if required If the temperature falls below the set point the electric preheater will turn on Access to the electric preheat is through the outdoor air filter access door...

Page 13: ...Unit Serial Number ________________________________ e g 04C99999 or 10111000 Start Up Date ________________________________ Start Up Personnel Name___________________________ Start Up Company ________...

Page 14: ...thermostat 36 F Differential 2 F Timer Refer to page 17 Economizer Application Operation section Yes No Economizer temperature Set point 65 F Offset 20 F Differential 2 F Yes No Economizer enthalpy S...

Page 15: ...AUTION When operating conditions of the fan are to be changed speed pressure temperature etc consult Greenheck to determine if the unit can operate safely at the new conditions Direction of Fan Wheel...

Page 16: ...CHANGE STORED displays 9 Press enter to return the current menu parameter 10 Press escape to return to the current menu parameter When values are displayed pressing and holding the or button causes t...

Page 17: ...PPM CO2 Variable Frequency Drive The ECV 20 and ECV 30 are wired to the Variable Frequency Drive VFD Refer to the Variable Frequency Drive section for control sequence and programming Timer Scale Time...

Page 18: ...ctory set points refer to Yaskawa VFD instruction manual which can be found online at www drives com MAMBMC RP H1 SC HC S7 S6 S5 S4 S3 S2 S1 MP AC AM AC V A2 A1 PC P2 P1 IG S S R R V1000 MAMBMC AC AM...

Page 19: ...er rectangular panel This will allow access to the supply blower that is located on the control side of the housing Replace panel after service reinstall core support that was removed then reinstall c...

Page 20: ...power to the unit Remove access panel Removing the energy recovery core Once the energy core access doors are removed the core can be pulled from the housing To replace the core reverse the procedure...

Page 21: ...consult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the...

Page 22: ...w prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SM...

Page 23: ...power too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper li...

Page 24: ...Resources Library Literature Greenheck catalog Energy Core Ventilators Model MiniCore and ECV provides additional information describing the equipment fan performance available accessories and specif...

Reviews: