Greenheck DS-M Installation, Operation And Maintenance Manual Download Page 22

High Volume, Low Speed Ceiling Fans

22

®

DANGER

Disconnect and secure to the ‘OFF’ position all 
electrical power to the fan prior to inspection or 
servicing. Failure to comply with this safety precaution 
could result in serious injury or death.

Each fan bears a manufacturer’s nameplate with the 
fan’s model number and a unique serial number for 
identification. This information will assist the local 
representative and the manufacturer in providing service 
and replacement parts. 

Troubleshooting

PROBLEM

CAUSE

CORRECTIVE ACTION

Reduced airflow

Fan speed too low

Increase fan speed

Fan operating in reverse

Reverse the direction of operation using the fan controller

Excessive dirt buildup on impeller

Clean impeller

Excessive noise

Excessive vibration

Clean dirt buildup from impeller. Check all setscrews and fasteners 
for tightness. Check guy wire tension (if applicable).

Defective motor

Replace motor

Defective variable frequency drive (VFD)

Replace VFD 

Fan does not operate

Electrical supply

Check for switches turned off or disconnected. Check for correct 
supply voltage. Check fuses/circuit breakers. In the event of blown 
fuses, contact the factory before proceeding with troubleshooting. 

Motor/VFD system

Check for faults. Refer to instruction manual for controller. 

Fault Code Causes and Possible Solution

CODE

FAULT

DESCRIPTION

0

No Fault

1

Modbus Timeout

No activity on Modbus (check control connection)

2

Impact Detection

Unexpected change in speed and/or torque indicates impact

3

Motor Over Temperature

Motor temperature exceeds 110°C

4

Drive Over Temperature

Drive components over 110°C

5

Bus Over Voltage

DC Bus voltage is greater than 385v

6

Bus Under Voltage

DC Bus voltage is less than 140v

7

Phase Over Current

Phase Current is greater than 6A RMS

8

Microcontroller High Temp

Microcontroller Unit Temperature is greater than 110°C

9

Overspeed Fault

Blade Speed is greater than 300 rpm

Summary of Contents for DS-M

Page 1: ...e servicing or cleaning unit switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot...

Page 2: ...ailability of transportation and truck space Confirmation of shipment s must be limited to only items on the bill of lading Storage Fans are protected against damage during shipment If the unit cannot...

Page 3: ...n 1 General Information 4 Minimum Spacing Requirements 4 Fan Components 5 Optional Fan Components 6 Required Tools 6 Mounting Installation 7 Motor Hub to Downtube Installation 10 Fan Networking 11 Saf...

Page 4: ...fan will not interfere with correct sprinkler operation and that the fan installation complies with all national state and local codes For NFPA 13 compliance fan must be installed in the center of fou...

Page 5: ...VFD Cover 1 DOWNTUBE MOU MOTOR HUB ASSEMBLY FRONT VFD COVER RE POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUN...

Page 6: ...lt 4 Wood Beam Hardware Kit Optional Bag 915429 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT WOOD BEAM WOOD BEAM BRACKET 1 2 in 13 GRADE B Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1...

Page 7: ...versal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknut I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSA...

Page 8: ...Downtube Installation Wood Beam Mounting Kit For Beams 41 2 87 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut...

Page 9: ...e to 80 ft lbf 108 5 N m STRUCTURAL STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m T...

Page 10: ...OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL SAFETY RETENTION CABLE 4 Using a Phillips screwdriver remove the front VFD cover and set aside 5...

Page 11: ...be adjusted using the following instructions DIPSWITCH 3 DIPSWITCH 2 First Fan FIRST FAN IN SERIES ALL OTHER FANS IN SERIES 1 Determine the first fan in the network daisy chain by identifying the fan...

Page 12: ...Positions 6 8 are used to set parameters needed for fan operation and should not be adjusted NOTE It is good practice to use successive Modbus addresses for networked fans but this is not necessary f...

Page 13: ...ve end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be installed a minimum of 5 inches away from...

Page 14: ...ome in contact with any sharp edges 5 Insert the loose end of the safety cable into the open hole of the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one...

Page 15: ...y from the dead end of the guy wire to ensure proper functioning IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over t...

Page 16: ...ll 4 turnbuckles to the guy wire attachment ring located on the downtube using 4 supplied quick links Pull the loose end of each guy wire through the No 4 Gripple connector until each guy wire is taut...

Page 17: ...e installed bolts to 25 ft lbf 34 N m 5 16 in 18 x 2 GRADE 8 BOLT 2 PER BLADE TORQUE TO 25 FT LBF 34 N m IMPORTANT If airfoils must be removed and reinstalled for any reason do not re use the supplied...

Page 18: ...ncy stop landing point and the building s fire suppression system using the wiring diagram shown Communication Wiring Fan Control Installation IMPORTANT DS M fans must be installed with the supplied C...

Page 19: ...ns on page 11 to complete network setup for the fans With Optional 1 000 ft Bulk Spool of CAT 5e Cable Included Component 1 000 ft Bulk Spool of CAT 5e Control Cable 1 Shielded Pass Through RJ45 Conne...

Page 20: ...1 Refer to the wiring diagrams below to complete power wiring 2 Secure any loose power cable to the building structure to ensure it does not interfere with fan performance POWER CABLE FROM FAN POWER...

Page 21: ...personnel who are familiar with local codes and regulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to...

Page 22: ...ension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switches turned off or disconnected Check for cor...

Page 23: ...Volts 1 units 15 Voltage Output RMS R xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 M...

Page 24: ...___________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ______________________________...

Reviews: