Greenheck DS-M Installation, Operation And Maintenance Manual Download Page 21

High Volume, Low Speed Ceiling Fans

21

®

5.    Verify that the fan is hanging so that the airfoils 

and downtube are level and the fan is plumb to 
the floor. Adjust guy wire tension as necessary (if 
applicable).

Operation

IMPORTANT: 

If unusual vibration or oscillating 

movement is observed during fan operation, 
immediately discontinue use of the fan and contact the 
manufacturer or a suitably qualified maintenance/repair 
technician.
  1.  When the fan is started, observe the operation 

and check for any unusual noise, vibration or 
overheating. Refer to the Troubleshooting section 
of this manual if a problem develops. 

  2.  With the system in full operation, measure current 

input to the VFD and compare with the FLA ratings 
in the table above to determine if the motor/VFD 
system is operating under safe load conditions. 

  3.  Keep approaches to fan clean and free from 

obstruction.

Inspection

DANGER

Disconnect and secure to the ‘OFF’ position all 
electrical power to the fan prior to inspection or 
servicing. Failure to comply with this safety precaution 
could result in serious injury or death.

Inspection of the fan should be conducted at the first 30 
minute and 24 hour intervals of satisfactory operation. 
•  30 Minute Interval - Check all fasteners of tightness. 

Adjust and tighten as necessary

•  24 Hour Interval - Inspect all fan components. 

Check all fasteners, airfoil retaining ring, the safety 
cable, and guy wires (if applicable). Adjust and 
tighten as necessary.

Maintenance

NOTE: 

Installation and maintenance are to be 

performed only by qualified personnel who are familiar 
with local codes and regulations and have experience 
with this type of equipment. 
Once the fan has been put into operation, a periodic 
maintenance program should be set up to ensure 
reliable fan performance. A proper maintenance 
program will help deliver years of dependable service. 
Items to be included in this program are as follows:
  1.  Verify that all fasteners are tight and properly 

torqued.

  2.  Verify that all of the fan’s safety systems – safety 

cable, airfoil retaining ring, and guy wires (if 
applicable) are properly installed. Inspect for signs 
of damage or failure. Safety cable and guy wire 
tension should also be checked. Safety cable 
should be wrapped around the building structure 
leaving as little slack as possible. Guy wires 
should be under enough tension to prevent any 
lateral movement of the motor and downtube (if 
applicable).

  3.  Inspect the fan for signs of fatigue, corrosion, or 

wear.

 4.  Impellers require little attention when moving clean 

air. Occasionally, oil and dust may accumulate 
causing imbalance. When this occurs, clean 
the impeller and other fan components to 
ensure smooth and safe operation. Remove any 
accumulated dust and dirt using hot water or mild 
cleaning solutions. Harsh chemicals should not 
be used to clean the fan as they may damage the 
fan’s finish or motor.

IMPORTANT:

 Do not allow water or solvents to enter 

the motor. Under no circumstances should motors be 
sprayed with steam, water or solvents.
  5.  Motor maintenance is generally limited to cleaning. 

Limit cleaning to exterior surfaces only. Removing 
dust buildup on motor housing ensures proper 
motor cooling.

  6.  Prior to restarting unit, check all fasteners for 

tightness each time maintenance checks are 
performed. 

Summary of Contents for DS-M

Page 1: ...e servicing or cleaning unit switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot...

Page 2: ...ailability of transportation and truck space Confirmation of shipment s must be limited to only items on the bill of lading Storage Fans are protected against damage during shipment If the unit cannot...

Page 3: ...n 1 General Information 4 Minimum Spacing Requirements 4 Fan Components 5 Optional Fan Components 6 Required Tools 6 Mounting Installation 7 Motor Hub to Downtube Installation 10 Fan Networking 11 Saf...

Page 4: ...fan will not interfere with correct sprinkler operation and that the fan installation complies with all national state and local codes For NFPA 13 compliance fan must be installed in the center of fou...

Page 5: ...VFD Cover 1 DOWNTUBE MOU MOTOR HUB ASSEMBLY FRONT VFD COVER RE POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUN...

Page 6: ...lt 4 Wood Beam Hardware Kit Optional Bag 915429 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT WOOD BEAM WOOD BEAM BRACKET 1 2 in 13 GRADE B Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1...

Page 7: ...versal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknut I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSA...

Page 8: ...Downtube Installation Wood Beam Mounting Kit For Beams 41 2 87 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut...

Page 9: ...e to 80 ft lbf 108 5 N m STRUCTURAL STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m T...

Page 10: ...OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL SAFETY RETENTION CABLE 4 Using a Phillips screwdriver remove the front VFD cover and set aside 5...

Page 11: ...be adjusted using the following instructions DIPSWITCH 3 DIPSWITCH 2 First Fan FIRST FAN IN SERIES ALL OTHER FANS IN SERIES 1 Determine the first fan in the network daisy chain by identifying the fan...

Page 12: ...Positions 6 8 are used to set parameters needed for fan operation and should not be adjusted NOTE It is good practice to use successive Modbus addresses for networked fans but this is not necessary f...

Page 13: ...ve end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be installed a minimum of 5 inches away from...

Page 14: ...ome in contact with any sharp edges 5 Insert the loose end of the safety cable into the open hole of the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one...

Page 15: ...y from the dead end of the guy wire to ensure proper functioning IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over t...

Page 16: ...ll 4 turnbuckles to the guy wire attachment ring located on the downtube using 4 supplied quick links Pull the loose end of each guy wire through the No 4 Gripple connector until each guy wire is taut...

Page 17: ...e installed bolts to 25 ft lbf 34 N m 5 16 in 18 x 2 GRADE 8 BOLT 2 PER BLADE TORQUE TO 25 FT LBF 34 N m IMPORTANT If airfoils must be removed and reinstalled for any reason do not re use the supplied...

Page 18: ...ncy stop landing point and the building s fire suppression system using the wiring diagram shown Communication Wiring Fan Control Installation IMPORTANT DS M fans must be installed with the supplied C...

Page 19: ...ns on page 11 to complete network setup for the fans With Optional 1 000 ft Bulk Spool of CAT 5e Cable Included Component 1 000 ft Bulk Spool of CAT 5e Control Cable 1 Shielded Pass Through RJ45 Conne...

Page 20: ...1 Refer to the wiring diagrams below to complete power wiring 2 Secure any loose power cable to the building structure to ensure it does not interfere with fan performance POWER CABLE FROM FAN POWER...

Page 21: ...personnel who are familiar with local codes and regulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to...

Page 22: ...ension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switches turned off or disconnected Check for cor...

Page 23: ...Volts 1 units 15 Voltage Output RMS R xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 M...

Page 24: ...___________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ______________________________...

Reviews: