background image

5

Model 

Number

Motor 

HP

Fan 

RPM

CFM / Static Pressure in Inches wg

0.000

0.125

0.250

0.300

0.375

0.500

0.625

0.750

0.875

1.000

NYD-75-A

1/4

1725

CFM

488

438

382

359

325

258

169

BHP

0.05

0.05

0.05

0.06

0.06

0.06

0.06

NYD-90-B

1/6

1140

CFM

723

617

484

418

253

BHP

0.04

0.05

0.05

0.05

0.05

NYD-90-A

1/4

1725

CFM

1094

1028

957

924

874

787

690

575

339

BHP

0.14

0.15

0.16

0.17

0.17

0.18

0.19

0.19

0.15

NYD-100-B

1/6

1140

CFM

1363

1223

1081

1017

920

713

417

BHP

0.11

0.12

0.13

0.14

0.14

0.14

0.12

NYD-100-A

1/4

1725

CFM

2062

1970

1877

1841

1787

1700

1590

1486

1377

1255

BHP

0.37

0.39

0.42

0.43

0.44

0.45

0.46

0.48

0.49

0.50

NYD-120-B

1/6

1140

CFM

1429

1303

1168

1108

1010

800

BHP

0.12

0.14

0.16

0.16

0.17

0.17

NYD-120-A

3/4

1725

CFM

2162

2080

1996

1962

1908

1819

1725

1623

1513

1387

BHP

0.43

0.45

0.48

0.49

0.50

0.53

0.55

0.57

0.58

0.59

NYD-130-B

1/4

1140

CFM

2184

2005

1815

1741

1627

1421

1180

745

BHP

0.22

0.23

0.24

0.25

0.25

0.26

0.26

0.22

NYD-140-B

1/2

1140

CFM

2705

2534

2376

2308

2199

1999

1765

1483

1090

BHP

0.30

0.33

0.35

0.36

0.38

0.40

0.40

0.40

0.36

Performance certified is for installation type A: free inlet, free outlet. Performance ratings include the effects of a birdscreen.

Performance Data 

NYD - Direct Drive Models

0

500

1000

1500

2000

2500

3000

3500

0

50

100

150

200

250

300

350

400

0

300

600

900

1200

1500

1800

2100

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

 Static Pr

essur

e in. wg

cfm

m

3

/hr

Static Pr

essur

e Pa

NYD-100-A

NYD-90-A

NYD-100-B

NYD-90-B

NYD-75-A

 RPM

Density 0.075 lb/ft³

0

500

1000

1500

2000

2500

3000

3500

4000

4500

0

50

100

150

200

250

300

350

400

0

400

800

1200

1600

2000

2400

2800

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

 Static Pr

essur

e in. wg

cfm

m

3

/hr

Static Pr

essur

e Pa

NYD-120-A 

NYD-140-B

NYD-120-B 

NYD-130-B

 RPM

Density 0.075 lb/ft³

Summary of Contents for Centrifugal Roof Exhaust Fans NYB

Page 1: ...Centrifugal Roof Exhaust Fans Models NYD and NYB Direct and Belt Drive August 2008 ...

Page 2: ... is safely supported and will not drop closed Hinge is steel with protective coating Internal structural supports are heavy gauge galvanized steel angles Drive frames and motor supports are heavy gauge galvanized steel and are mounted on resilient isolators Backward inclined non overloading wheel is constructed of aluminum Heavy duty ball bearing motor Single and three phase fans include a NEMA 1 ...

Page 3: ...ss A wide variety of roof curbs are available including flanged pitched and sound absorbing Curb Seal Rubber seal between fan and curb to assure proper sealing when attached to a curb Coatings Wide variety of coatings and colors are available for decorative to corrosive applications Permatector is our standard coating Typically used for applications that require corrosion resistance in indoor and ...

Page 4: ... 11 2 Model NYD Direct Drive NYB Belt Drive Fan Size 75 through 240 4 Motor RPM for Direct Drive A 1725 B 1140 Dimensional Data Model A B C Damper Square NYD 75 19 483 303 4 781 201 2 521 10 254 NYD 90 19 483 303 4 781 201 2 521 10 254 NYD NYB 100 22 559 351 2 902 25 635 12 305 NYD 120 24 610 37 940 231 8 587 14 356 NYD 130 24 610 37 940 231 8 587 14 356 NYD NYB 140 26 660 411 2 1054 267 8 683 16 ...

Page 5: ...0 43 0 45 0 48 0 49 0 50 0 53 0 55 0 57 0 58 0 59 NYD 130 B 1 4 1140 CFM 2184 2005 1815 1741 1627 1421 1180 745 BHP 0 22 0 23 0 24 0 25 0 25 0 26 0 26 0 22 NYD 140 B 1 2 1140 CFM 2705 2534 2376 2308 2199 1999 1765 1483 1090 BHP 0 30 0 33 0 35 0 36 0 38 0 40 0 40 0 40 0 36 Performance certified is for installation type A free inlet free outlet Performance ratings include the effects of a birdscreen...

Page 6: ...0 3 1 3 1060 CFM 2178 2073 1951 1901 1823 1676 1495 BHP 0 24 0 25 0 26 0 27 0 27 0 27 0 27 1130 CFM 2322 2224 2112 2065 1994 1866 1721 1520 BHP 0 29 0 31 0 32 0 32 0 33 0 33 0 33 0 32 NYB 140 5 1 2 1190 CFM 2445 2352 2247 2204 2136 2020 1887 1732 1515 BHP 0 34 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 37 1250 CFM 2569 2480 2382 2341 2277 2170 2051 1919 1756 1465 BHP 0 40 0 41 0 42 0 43 0 44 0 44 0 45 0...

Page 7: ...M 6434 6098 5751 5598 5361 4947 4383 BHP 0 66 0 70 0 73 0 74 0 75 0 76 0 75 NYB 240 10 1 650 CFM 6691 6368 6041 5894 5669 5283 4784 4053 BHP 0 74 0 78 0 81 0 83 0 84 0 86 0 85 0 80 685 CFM 7052 6745 6440 6304 6095 5731 5332 4807 BHP 0 86 0 91 0 94 0 96 0 98 0 99 1 01 0 99 NYB 240 15 11 2 730 CFM 7515 7227 6941 6825 6629 6294 5949 5524 5013 BHP 1 05 1 09 1 13 1 15 1 17 1 19 1 21 1 21 1 19 785 CFM 8...

Page 8: ...enance and quiet dependable operation they experience long after the construction project ends NYD NYB Rev 4 August 2008 RG Copyright 2008 Greenheck Fan Corp Exhaust Fans The spun aluminum downblast centrifugal roof exhaust fan models G and GB direct or belt drive are an economical means of exhausting air They utilize a backward inclined wheel and are available in 45 different sizes Capacities ran...

Reviews: